Fig. 20. Typical LP916B fan coil application, heating and 

cooling with seasonal changeover. 

M5416 

CW IN 
SUMMER 

HW IN 
WINTER 

N.O. 

COIL 

BULB 

FAN 

FILTER 

RETURN AIR 

LP916B 

SUM/WIN 

DISCHARGE AIR 

DISCHARGE AIR 

CHECKOUT AND TESTING 

CAUTION 

Equipment Damage Hazard. 

Do not rotate the thermostat control shaft more 
than two revolutions clockwise from the original 

position as received. Rotating the shaft more than 

two revolutions from the original position can 
cause permanent damage to the thermostat. 

Using a CCT729A Gage Adaptor, insert a 0 to 30 psi (0 to 

207 kPa) gage into the gage plug on the front of the 
thermostat. Turn the setpoint knob above and below the bulb 

ambient temperature. If the branchline pressure can be varied 

from 0 psi (0 kPa) to full main pressure within the rated 
throttling range, the thermostat is operating properly. If not, 

recalibrate (see the CALIBRATION section). 

NOTE:

  

Allow enough time (up to three minutes) for the 

branch pressure to build up. 

See Table 1 for the throttling range and scale increment 

values for various thermostat models. 

Table 1. Throttling Ranges and Scale Increment Values. 

Setpoint 

Range in F 

(C) 

Scale Increments 

Throttling 

Range in 

Degrees F (K) 

65-85 (18-29)

WARMER-COOLER/0.9F 

3.5 (2) 

40-80 (4-27) 

40-50-60-70-80 

7 (3.5) 

60-80 (16-27) 

60-80/1F 

3.5 (2) 

The LP916B1058 WARMER-COOLER model has a throt-

tling range of 2F (1K) when on reverse-acting (9 psi supply 
pressure). 

CALIBRATION 

The thermostat is factory calibrated at midscale (pointer 
vertical) and normally requires no adjustment. Warmer-Cooler 

models are calibrated at 75F. 

IMPORTANT

 

If recalibration is required, always allow enough 

time (up to three minutes) for the branch pressure to 
stabilize. 

LP916A and C Calibration 

1.

  

Apply 18 psi (124 kPa) main line pressure. 

2.

  

Measure the temperature at the bulb location. 

3.

  

Remove the setpoint knob. 

4.

  

Rotate the control shaft to achieve 8 psi (55 kPa) 

branchline pressure. 

Fig. 21. Typical cooling only LP916C fan coil application. 

M5415 

CHILLED 
WATER 
SUPPLY 

N.O. 

COIL 

BULB 

FAN 

FILTER 

RETURN AIR 

LP916C 

7

  

95-5559EF 

Содержание LP916A

Страница 1: ...ived Rotating the shaft more than two revolutions from the original position can cause permanent damage to the thermostat The caution is also on a removable tag attached to the thermostat and should remain attached until the system is ready to start up See Fig 1 M B O O R M E CAUTION DO NOT ROTATE SETPOINT SHAFT MORE THAN TWO COMPLETE CLOCKWISE REVOLUTIONS FROM ITS AS RECEIVED CONDITION THE DEVICE...

Страница 2: ... screws are readily accessible and the setpoint knob easily reached Preferably the scale is visible from the top of unit through the access hatch or from the front of the unit when the front panel is removed 3 Locate air connections in accessible area If necessary add 1 4 in plastic elbow and or tubing extensions to barb connectors before installation 4 Mount the bulb at either of the E points See...

Страница 3: ...ype with the labels M Main and B Branch NOTE When air connections are towards the back connect the appropriate lengths of tubing to the barb connec tors before mounting Duct Mounting Duct mounting requires a 107324A duct bulb holder See Fig 7 The sensing bulb should be located in the duct where air of representative temperature can freely circulate IMPORTANT Do not mount the bulb close to hot pipe...

Страница 4: ...ounted in a terminal unit using a bracket B M 4 1 2 115 4 7 8 124 2 1 16 53 C4653 2 3 16 56 Fig 12 Dimensions of the LP916 mounting kit in in mm Panel Mounting Mounting the LP916 mounting kit model directly on a panel requires a 306016C bag assembly The kit includes a scale plate knob and mounting screws 1 Drill holes in the panel on the centers See Fig 13 C4650 3 8 10 DIA 7 32 6 DIA 2 PANEL 2 1 4...

Страница 5: ...r the length of the mounting bracket and the centers of the bracket mounting holes See Fig 15 and 16 The two sets of holes in the mounting brackets allow the thermostat to be mounted either vertically or horizontally 3 1 4 83 5 8 16 1 7 8 48 2 3 4 70 C4648 Fig 15 Mounting bracket in 316016A bag assembly Dimensions are in in mm 5 5 16 135 5 8 16 2 51 2 3 4 70 C4649 Fig 16 Dimensions of the mounting...

Страница 6: ...ee Fig 6 SENSING BULB CAPILLARY THERMOSTAT SCALEPLATE CONTROL SHAFT MAIN SETPOINT KNOB 10 32 x 1 4 IN SCREW 2 BRANCH PROTECTED BARBS C4651 MOUNT AS SHOWN OR TURN 90 TO ANY OF FOUR POSITIONS AS REQUIRED 10 x 5 8 IN SHEET METAL SCREW 2 MOUNTING BRACKET APPLICATIONS Refer to Figs 18 through 21 for typical applications Fig 18 Typical LP916A duct mounted heating application N O B M LP916A DA DISCHARGE ...

Страница 7: ...ee minutes for the branch pressure to build up See Table 1 for the throttling range and scale increment values for various thermostat models Table 1 Throttling Ranges and Scale Increment Values Setpoint Range in F C Scale Increments Throttling Range in Degrees F K 65 85 18 29 1 WARMER COOLER 0 9F 3 5 2 40 80 4 27 40 50 60 70 80 7 3 5 60 80 16 27 60 80 1F 3 5 2 1 The LP916B1058 WARMER COOLER model ...

Страница 8: ...nt IMPORTANT When making adjustments always allow enough time up to three minutes for the branch pressure to stabilize 1 Back off the switchover spring adjusting nut until flush with the stud See Fig 22 2 Calibrate per Steps 1 through 5 of the LP916A and C Calibration section Increase the branchline pressure by rotating the control shaft clockwise 3 Lower the main line pressure to 16 5 psi 113 kPa...

Страница 9: ...x tours dans le sens horaire par rapport à sa position originale au moment de l expédition Cela pourrait endommager le thermostat et le rendre inutilisable Cet avertissement est imprimé sur une étiquette détachable fixée au thermostat Ne pas enlever cette étiquette tant que le système n est pas prêt à fonctionner Voir la Fig 1 M B O O R M E CAUTION DO NOT ROTATE SETPOINT SHAFT MORE THAN TWO COMPLE...

Страница 10: ...le devant de l unité lorsque le panneau frontal est enlevé 3 Placer les raccords d air dans un endroit d accès facile S il y a lieu fixer des coudes ou des rallonges pour tubes de 1 4 po en plastique au bout des raccords à crans avant d installer le thermostat 4 Monter le bulbe dans l un ou l autre des compartimants E Voir la Fig 3 Prendre garde de plier à angle aigu de tortiller ou de pincer le t...

Страница 11: ...REMARQUE Si les raccords d air sont situés à l arrière poser des canalisations de longueur appro priée sur les raccords à crans avant le mon tage Montage sur gaine Pour le montage sur gaine utiliser le support de bulbe pour montage sur gaine 107324A Voir la Fig 7 Le bulbe sensible doit être posé à un endroit dans la gaine où l air dont la température est typique circule sans obstacle IMPORTANT Ne ...

Страница 12: ...re monté sur un panneau ou dans une unité terminale à l aide d un support B M 115 4 1 2 124 4 7 8 56 2 3 16 53 2 1 16 CF4653 Fig 12 Encombrement de la trousse de montage LP916 en mm po Montage sur panneau Pour poser la trousse de montage LP916 directement sur un panneau utiliser l ensemble 306016C La trousse comprend une plaque graduée un bouton et des vis de montage Percer les trous dans le panne...

Страница 13: ...le bulbe une plaque graduée et un bouton Les deux ensembles sont presque identiques Les seules différences sont la longueur du support de montage et le centre des trous de montage du support Voir les Fig 15 et 16 Les deux séries de trous dans les supports de montage servent à poser le thermostat à l horizontale ou à la verticale 83 3 1 4 16 5 8 48 1 7 8 70 2 3 4 CF4648 Fig 15 Support de montage de...

Страница 14: ...DUÉE ARBRE DE COMMANDE CANALISATION PRINCIPALE VIS 10 32 x 1 4 PO 2 CANALISATION SECONDAIRE CANNELURES PROTÉGÉES CF4651 POSER COMME SUR L ILLUSTRATION OU TOURNER À 90 POUR INSTALLATION DANS L UNE VIS À TÔLE 10 x 5 8 PO 2 SUPPORT DE MONTAGE BOUTON DE RÉGLAGE DU POINT DE CONSIGNE Fig 17 Assemblage du thermostat du support de montage et de la plaque graduée Le support illustré est celui de l ensemble...

Страница 15: ...incipale suivant la bande proportionnelle nominale le thermostat fonctionne correctement Si non il faut reprendre l étalonnage Se reporter à la section ÉTALONNAGE REMARQUE Attendre que la pression s établisse dans la canalisation secondaire jusqu à trois minutes Se reporter au Tableau 1 pour les valeurs incrémentielles de la bande proportionnelle et de l échelle sur les divers modèles de thermosta...

Страница 16: ...le jusqu à trois minutes 1 Dévisser l écrou de réglage du ressort d inversion pour qu il soit au même niveau que la tige Voir la Fig 22 2 Faire l étalonnage en suivant les étapes 1 à 5 de la sec tion Étalonnage du LP916A et C Augmenter la pres sion dans la canalisation secondaire en tournant l arbre de commande dans le sens horaire 3 Abaisser la pression dans la canalisation principale à 113 kPa 1...

Отзывы: