background image

LP907A AIRSTREAM INSERTION THERMOSTAT 

Adjustments 

Refer to Fig. 8 and the Maintenance section. 

Throttling Range 

IMPORTANT 

— Always check calibration after adjusting the throttling 

range. 

— Set the throttling range as near to the minimum value 

that the system permits without causing short cycling. 

NOTE:   For unit ventilator use, the throttling range is factory 

set at 25°F (14K) and requires no further adjustment. 

TO CHECK THE ACTUAL THROTTLING RANGE: 

1.   Turn the setpoint dial until branch line pressure (BLP) is 

less than 1 psi (7 kPa). 

2.   Turn dial counterclockwise until BLP is 3 psi (21 kPa) 

and note setpoint. 

3.   Continue to turn the dial until BLP is 13 psi (90 kPa). 
4.   The difference between the setpoints at 3 and 13 psi 

(21 and 90 kPa) BLP is the throttling range. 

TO ADJUST THE THROTTLING RANGE: 

1.   Loosen the throttling range indicator locking screw with 

the thermostat key. See Fig. 8. 

NOTE:   If there is no locking screw, simply squeeze the 

throttling range adjustment clip to release it. 

2.   Slide the indicator until its leading edge is on the

desired setting. 

IMPORTANT 

When replacing the cover, be careful not to disturb 
the throttling range adjustment clip. 

Calibration 

NOTE:   Calibration procedures are the same for all models 

with the exception that the LP907B (or LP907A used 
with an RP670) cannot be calibrated unless the relay 
main air pressure supply is 18 psi (124 kPa). 

1.   Loosen the setpoint-dial locking screw. 
2.   With 3/16 in. (5 mm) open-end wrench, turn the setpoint 

adjustment screw until the primary lever is parallel with 
the base. 

3.   Turn the calibration screw until the nozzle lever is 

parallel with the base. 

4.   Adjust the setpoint dial until the setpoint indicator 

matches the current temperature at the sensing element. 

5.   Tighten the setpoint-dial locking screw. 
6.   Adjust the calibration screw until BLP is 8 psi (55 kPa). 
7.   Turn the setpoint dial to the desired setpoint. 

IMPORTANT 

When replacing the cover, be careful not to disturb 
the throttling range adjustment clip. 

BASE 

PRIMARY 
LEVER 

NOZZLE 
LEVER 

CALIBRATION 
SCREW 

SETPOINT 

INDICATOR 

SETPOINT 

DIAL 

LOCKING 

SCREW 

SETPOINT 

ADJUSTMENT 

SCREW 

SETPOINT 

DIAL 

THROTTLING 
RANGE 
ADJUSTMENT 
CLIP 

INSET "A" 

THROTTLING RANGE 
INDICATOR LOCKING 
SCREW 

GAGE 
ADAPTER 

GAGE 
TEE 

TANK 
VALVE 

M17677BB 

Fig. 8. LP907A Adjustments. 

TROUBLESHOOTING 

1.   If the LP907 does not operate smoothly when making 

an operational check, replace the filter (located between 
the gage tee and device base). 

2.   If results do not improve, check the pneumatic line 

restriction to determine whether there is proper airflow. 

3.   If the pneumatic line has evidence of oil, purge the line 

with refrigerant and eliminate the source of oil. 

IMPORTANT 

Keep oil out of the pneumatic line to avoid recurring 
problems. 

Home and Building Control  Home and Building Control 

Honeywell 

Honeywell Limited-Honeywell Limitée 

1985 Douglas Drive North 

35 Dynamic Drive 

Golden Valley, MN  55422 

Scarborough, Ontario 
M1V 4Z9 

Printed in U.S.A. on recycled 

95-1612EF  B.B.  4-01 

paper containing at least 10% 

www.honeywell.com 

post-consumer paper fibers. 

Содержание LP907A

Страница 1: ...with locknut on insertion coupling Accessories 14002913 002 External Restriction 0 007 in 0 2 mm 301572A00767 Calibration Adjustment Key 309387 Filter Assembly CCT2085 Gage Adapter BEFORE INSTALLING Use with a 0 007 inch 0 17 mm diameter restriction such as the 14002913 002 Filter Restriction Cartridge or the integral restriction in the MP516B and C Damper Operators When mounting with an immersion...

Страница 2: ... wall with immersion well MAINTENANCE M17678 LP907 19 1 16 484 1 2 NPT IMMERSION WELL ELEMENT 3 8 NPT 1 2 13 HEX COLLAR CONDUCTIVE COMPOUND 1 3 16 29 Mechanical devices require periodic service to provide continued satisfactory performance Controls are no exception How accurate and how trouble free your control system remains in years to come depends largely on the maintenance given to it For best...

Страница 3: ...hermostat in order to obtain equal pressure b Decrease the air temperature at the device sensing element or increase the setpoint RESULT BLP to the valve should decrease and vice versa c Return setpoint to the original setting LP907B or LP907A with RP670A Switching Relay 1 Supply 13 psi 90 kPa main air pressure to the LP907B relay or 18 psi 124 kPa main air pressure to the RP670A to simulate summe...

Страница 4: ...th 3 16 in 5 mm open end wrench turn the setpoint adjustment screw until the primary lever is parallel with the base 3 Turn the calibration screw until the nozzle lever is parallel with the base 4 Adjust the setpoint dial until the setpoint indicator matches the current temperature at the sensing element 5 Tighten the setpoint dial locking screw 6 Adjust the calibration screw until BLP is 8 psi 55...

Страница 5: ...dmissible 138 kPa 20 psig Raccords d air raccord cannelé à pression pour tube de polymère de 6 mm 1 4 po Installation par insertion avec écrou du côté du raccord Accessoires 14002913 002 Restriction externe de 0 2 mm 0 007 po 301572A00767 Clé d étalonnage 309387 Filtre CCT 2085 Adaptateur pour manomètre AVANT D INSTALLER CE PRODUIT Utiliser avec un réducteur de 0 17 mm 0 007 po de diamètre tel que...

Страница 6: ... kPa 14 psig ou moins pression normale 90 à 124 kPa 13 à 18 psig On peut ainsi obtenir une variation de 7 kPa 1 psig dans la canalisation principale MF17676 MANCHON Fig 4 Installation sur la paroi d une chaudière avec gaine d immersion MAINTENANCE MF17678 LP907 484 19 1 16 1 2 NPT GAINE D IMMERSION ÉLÉMENT SENSIBLE 3 8 NPT 13 1 2 HEXAGONAL COMPOSÉ THERMOCONDUCTEUR 29 1 3 16 Les appareils mécanique...

Страница 7: ... provoquer des cycles de fonctionnement trop courts MF5419B AIR REPRIS AIR FRAIS Fig 5 Fonctionnement type Vérification du fonctionnement LP907A 1 S assurer que la pression de la canalisation secondaire en amont du réducteur ou du MP516B est égale à la pression de la canalisation principale Si ce n est pas le cas a Ajuster le thermostat d ambiance pour obtenir une pression égale b Réduire la tempé...

Страница 8: ... l indicateur du point de consigne corresponde à la température actuelle à l élément sensible 5 Resserrer la vis de blocage du cadran de réglage du point de consigne 6 Ajuster la vis d étalonnage jusqu à ce que la pression de la canalisation secondaire atteigne 55 kPa 8 psi 7 Faire tourner le cadran de réglage du point de consigne à la valeur désirée IMPORTANT Prendre soin de ne pas bouger la pinc...

Отзывы: