LP907A

 Airstream Insertion Thermostat 

INSTALLATION INSTRUCTIONS 

APPLICATION 

The LP907 Airstream Insertion Thermostat is a direct-acting, 
single-pipe, bleed-type controller with a rigid element. The 
LP907B (no longer available) was the same as the LP907A 
with lockout capability. It included a pneumatic switching relay 
for lockout during summer (cooling) operation. When 
replacing the LP907B, use an LP907A and an RP670A 
Switching Relay. 

SPECIFICATIONS 

Model: Direct-acting, bleed-type controller. 

Dimensions: See Fig. 1

Temperature Ratings: 
Operating Range: 40°F to 140°F (4°C to 60°C). 
Storage (Maximum Safe): 150°F (66°C). 
Throttling Range (adjustable internally): 10 to 70°F (6 to 39K). 
Setpoint Range(s): 40°F to 140°F (4°C to 60°C); 

Dial Front: 40°F to 90°F (4°C to 32°C), 
Dial Back: 90°F to 140°F (32°C to 60°C). 

Setpoint Adjustment: Dial under cover. 

Element: 18-3/4 in. (476 mm) long x 3/8 in. (10 mm) diameter 

invar rod and seamless brass tube. 

Maximum Safe Air Pressure: 20 psig (138 kPa). 

Air Connections: Push-on barb for 1/4 in. (6 mm) poly tubing. 

Mounting: Insertion with locknut on insertion coupling. 

Accessories: 
14002913-002 External Restriction [0.007 in. (0.2 mm)]. 
301572A00767 Calibration Adjustment Key. 
309387 Filter Assembly. 
CCT2085 Gage Adapter. 

BEFORE INSTALLING 

Use with a 0.007-inch (0.17 mm) diameter restriction such as 
the 14002913-002 Filter/Restriction Cartridge or the integral 
restriction in the MP516B and C Damper Operators. 

When mounting with an immersion well, use 107408 Heat 
Conductive Compound in the well to improve response. 

NOTE:   For further information concerning wells, see Form 

68-0040 Immersion Wells and Compression Fittings 
for Temperature Controllers. 

1-1/16 (27) 

7/8 (22) 

5/8 

(16) 

3/8 NPT 

NUT 

SPACERS (2) 

DUCT WALL 

18-3/4 (476) 

3-7/16 

(87) 

1/8 NPT 

(51) 

2-1/4 (57)

1/2 

(13) 

HONEYWELL 

11/32 

(9) 

3/4 DIAM. HOLE 
(MINIMUM) 
REQUIRED 
FOR MOUNTING 

M7996A 

Fig. 1. Dimensions of LP907A in in. (mm). 

INSTALLATION 

The LP907A can be mounted in any position. See Fig. 2 
through 4 for mounting configurations. 

OPERATION 

Due to its bleed-type construction and wide throttling range, 
the LP907A provides submaster-type operation (most often 
low-limit control) in a normal unit ventilator system. See Fig. 5 
through 7 for typical hookups. 

® U.S. Registered Trademark 
Copyright © 2001 Honeywell •  All Rights Reserved 

95- 1612EF 

Содержание LP907A

Страница 1: ...with locknut on insertion coupling Accessories 14002913 002 External Restriction 0 007 in 0 2 mm 301572A00767 Calibration Adjustment Key 309387 Filter Assembly CCT2085 Gage Adapter BEFORE INSTALLING Use with a 0 007 inch 0 17 mm diameter restriction such as the 14002913 002 Filter Restriction Cartridge or the integral restriction in the MP516B and C Damper Operators When mounting with an immersion...

Страница 2: ... wall with immersion well MAINTENANCE M17678 LP907 19 1 16 484 1 2 NPT IMMERSION WELL ELEMENT 3 8 NPT 1 2 13 HEX COLLAR CONDUCTIVE COMPOUND 1 3 16 29 Mechanical devices require periodic service to provide continued satisfactory performance Controls are no exception How accurate and how trouble free your control system remains in years to come depends largely on the maintenance given to it For best...

Страница 3: ...hermostat in order to obtain equal pressure b Decrease the air temperature at the device sensing element or increase the setpoint RESULT BLP to the valve should decrease and vice versa c Return setpoint to the original setting LP907B or LP907A with RP670A Switching Relay 1 Supply 13 psi 90 kPa main air pressure to the LP907B relay or 18 psi 124 kPa main air pressure to the RP670A to simulate summe...

Страница 4: ...th 3 16 in 5 mm open end wrench turn the setpoint adjustment screw until the primary lever is parallel with the base 3 Turn the calibration screw until the nozzle lever is parallel with the base 4 Adjust the setpoint dial until the setpoint indicator matches the current temperature at the sensing element 5 Tighten the setpoint dial locking screw 6 Adjust the calibration screw until BLP is 8 psi 55...

Страница 5: ...dmissible 138 kPa 20 psig Raccords d air raccord cannelé à pression pour tube de polymère de 6 mm 1 4 po Installation par insertion avec écrou du côté du raccord Accessoires 14002913 002 Restriction externe de 0 2 mm 0 007 po 301572A00767 Clé d étalonnage 309387 Filtre CCT 2085 Adaptateur pour manomètre AVANT D INSTALLER CE PRODUIT Utiliser avec un réducteur de 0 17 mm 0 007 po de diamètre tel que...

Страница 6: ... kPa 14 psig ou moins pression normale 90 à 124 kPa 13 à 18 psig On peut ainsi obtenir une variation de 7 kPa 1 psig dans la canalisation principale MF17676 MANCHON Fig 4 Installation sur la paroi d une chaudière avec gaine d immersion MAINTENANCE MF17678 LP907 484 19 1 16 1 2 NPT GAINE D IMMERSION ÉLÉMENT SENSIBLE 3 8 NPT 13 1 2 HEXAGONAL COMPOSÉ THERMOCONDUCTEUR 29 1 3 16 Les appareils mécanique...

Страница 7: ... provoquer des cycles de fonctionnement trop courts MF5419B AIR REPRIS AIR FRAIS Fig 5 Fonctionnement type Vérification du fonctionnement LP907A 1 S assurer que la pression de la canalisation secondaire en amont du réducteur ou du MP516B est égale à la pression de la canalisation principale Si ce n est pas le cas a Ajuster le thermostat d ambiance pour obtenir une pression égale b Réduire la tempé...

Страница 8: ... l indicateur du point de consigne corresponde à la température actuelle à l élément sensible 5 Resserrer la vis de blocage du cadran de réglage du point de consigne 6 Ajuster la vis d étalonnage jusqu à ce que la pression de la canalisation secondaire atteigne 55 kPa 8 psi 7 Faire tourner le cadran de réglage du point de consigne à la valeur désirée IMPORTANT Prendre soin de ne pas bouger la pinc...

Отзывы: