LP907A AIRSTREAM INSERTION THERMOSTAT 

Fig. 2. Mounting on standard sheet metal duct. 

M17676 

3/8 
WASTE NUT 

DUCT 

3/8 NPT 

SHEET METAL 
MTG. SCREWS (2) 

1-11/16 

(43) 

LP907 

IMPORTANT 

M17679 

3/8 
WASTE NUT 

DUCT 

3/8 CLOSE 
NIPPLE 

3/8 NPT COUPLING 

3/8 NPT 

SHEET METAL 
MTG. SCREWS (2) 

INSULATION 

1-11/16 

(43) 

LP907 

Fig. 3. Mounting on insulated duct. 

When discharge air temperatures are within the throttling 
range, the LP907A control point is reset based upon room 
thermostat branch-line pressure (BLP) changes. This allows 
the LP907A to directly control airstream temperature except 
during morning warm-up and heavy-load conditions. 

NOTE:   Using a damper operator other than an MP516B 

requires a 0.007 in. restriction upstream. The 
restriction allows the LP907A to bleed fast enough to 
control BLP. 

In Fig. 6, the RP670 switching relay is connected directly to 
the main. The relay action locks out the LP907A during the 
summer (cooling) cycle when main pressure is 14 psig 
(97 kPa) or less. (Normal pressure ranges from 13 to 18 psig 
[90 to 124 kPa]). This allows 1 psig (7 kPa) main line variation. 

Fig. 4. Mounting in boiler wall with immersion well. 

MAINTENANCE 

M17678 

LP907 

19-1/16 (484) 

1/2 NPT 

IMMERSION 
WELL 

ELEMENT 

3/8 NPT 

1/2 

(13) 

HEX COLLAR 

CONDUCTIVE 
COMPOUND 

1-3/16 (29) 

•   Mechanical devices require periodic service to 

provide continued satisfactory performance. Controls 
are no exception. 

•   How accurate and how trouble free your control 

system remains in years to come depends largely on 
the maintenance given to it. 

•   For best results, service all devices in your system at 

one time. 

•   Time and trouble can be saved by arranging with 

Honeywell for a maintenance agreement which will 
guarantee expert, economical care, and insure 
maximum life and efficiency from your system. 

Equipment Required 

3/16-in. open end wrench. 

•   Commercial cleaning solvent. 
•   Lubricant (part no. 310879). 
•   Calibration Adjustment Key (part no. 301572A00767). 

Inspection, Cleaning and Lubrication 

1.   Visually inspect the device exterior. 
2.   Remove dirt and corrosion from the element and body. 
3.   Check air lines for damage and leaks. 
4.   Remove the cover and inspect internal parts. 
5.   Remove dirt and corrosion with soft brush or commer­

cial cleaning solvent. 

CAUTION 

Equipment Damage Hazard. 
Can damage the device beyond repair. 
Use lubricant sparingly and keep it away from the air 
nozzle (see Fig. 8). 

6.   Lubricate pivot points and adjustment threads. 

95-1612EF  

Содержание LP907A

Страница 1: ...with locknut on insertion coupling Accessories 14002913 002 External Restriction 0 007 in 0 2 mm 301572A00767 Calibration Adjustment Key 309387 Filter Assembly CCT2085 Gage Adapter BEFORE INSTALLING Use with a 0 007 inch 0 17 mm diameter restriction such as the 14002913 002 Filter Restriction Cartridge or the integral restriction in the MP516B and C Damper Operators When mounting with an immersion...

Страница 2: ... wall with immersion well MAINTENANCE M17678 LP907 19 1 16 484 1 2 NPT IMMERSION WELL ELEMENT 3 8 NPT 1 2 13 HEX COLLAR CONDUCTIVE COMPOUND 1 3 16 29 Mechanical devices require periodic service to provide continued satisfactory performance Controls are no exception How accurate and how trouble free your control system remains in years to come depends largely on the maintenance given to it For best...

Страница 3: ...hermostat in order to obtain equal pressure b Decrease the air temperature at the device sensing element or increase the setpoint RESULT BLP to the valve should decrease and vice versa c Return setpoint to the original setting LP907B or LP907A with RP670A Switching Relay 1 Supply 13 psi 90 kPa main air pressure to the LP907B relay or 18 psi 124 kPa main air pressure to the RP670A to simulate summe...

Страница 4: ...th 3 16 in 5 mm open end wrench turn the setpoint adjustment screw until the primary lever is parallel with the base 3 Turn the calibration screw until the nozzle lever is parallel with the base 4 Adjust the setpoint dial until the setpoint indicator matches the current temperature at the sensing element 5 Tighten the setpoint dial locking screw 6 Adjust the calibration screw until BLP is 8 psi 55...

Страница 5: ...dmissible 138 kPa 20 psig Raccords d air raccord cannelé à pression pour tube de polymère de 6 mm 1 4 po Installation par insertion avec écrou du côté du raccord Accessoires 14002913 002 Restriction externe de 0 2 mm 0 007 po 301572A00767 Clé d étalonnage 309387 Filtre CCT 2085 Adaptateur pour manomètre AVANT D INSTALLER CE PRODUIT Utiliser avec un réducteur de 0 17 mm 0 007 po de diamètre tel que...

Страница 6: ... kPa 14 psig ou moins pression normale 90 à 124 kPa 13 à 18 psig On peut ainsi obtenir une variation de 7 kPa 1 psig dans la canalisation principale MF17676 MANCHON Fig 4 Installation sur la paroi d une chaudière avec gaine d immersion MAINTENANCE MF17678 LP907 484 19 1 16 1 2 NPT GAINE D IMMERSION ÉLÉMENT SENSIBLE 3 8 NPT 13 1 2 HEXAGONAL COMPOSÉ THERMOCONDUCTEUR 29 1 3 16 Les appareils mécanique...

Страница 7: ... provoquer des cycles de fonctionnement trop courts MF5419B AIR REPRIS AIR FRAIS Fig 5 Fonctionnement type Vérification du fonctionnement LP907A 1 S assurer que la pression de la canalisation secondaire en amont du réducteur ou du MP516B est égale à la pression de la canalisation principale Si ce n est pas le cas a Ajuster le thermostat d ambiance pour obtenir une pression égale b Réduire la tempé...

Страница 8: ... l indicateur du point de consigne corresponde à la température actuelle à l élément sensible 5 Resserrer la vis de blocage du cadran de réglage du point de consigne 6 Ajuster la vis d étalonnage jusqu à ce que la pression de la canalisation secondaire atteigne 55 kPa 8 psi 7 Faire tourner le cadran de réglage du point de consigne à la valeur désirée IMPORTANT Prendre soin de ne pas bouger la pinc...

Отзывы: