LonWorks interface
Honeywell
• 21
6.4
Output network variables
NvoStatus
This output network variable reports the status for Node object or Variable Speed Motor Drive
object.
nvoDrvSpeed
This output network variable provides the speed of the drive as a percentage of the nominal
speed.
nvoDrvCurnt
This output network variable provides the drive output current in amperes.
Function
Variable Name
SNVT Type
Min. Value
Max. Value
Node Object status
nvoStatus
SNVT_obj_status
Drive speed feedback
nvoDrvSpeed
SNVT_lev_percent
-163.840%
+163.830%
Actual motor current
nvoDrvCurnt
SNVT_amp
0.0A
3276.7A
Actual drive power
nvoDrvPwr
SNVT_power_kilo
0,0 kW
6553,5 kW
Drive total running
hours
nvoDrvRunHours
SNVT_time_hour
0 h
65535
Status word
nvoDrvStatus
SNVT_state
n/a
n/az
kWh trip counter
nvoDrvEnrgy
SNVT_elect_kwh
0kWh
65535kWh
Active fault code
nvoActFault
SNVT_count
0
41
Process Out
nvoProcessOut1..8
SNVT_
lev_percent
0
65535
Digital Out
nvoDigitalOut1..8
SNVT_switch
0
4
Parameter Out
nvoParResp
SNVT_preset
Table 13. Output network variables
Field
Description
object_id
ID of object within node
invalid_id
1 means requested ID is not
implemented in this node
invalid_request
1 means request for unimple-
mented function
disabled
1 means object disabled
electrical_fault
1 means drive is faulted
in_alarm
1 means drive is in alarm
report_mask
1 means status is an event mask
Table 14.