Honeywell
• 18
LonWorks interface
6.3
Input Network Variables
nviRequest
This input network variable provides the mechanism to request a particular mode for the Node
object or the Variable Speed Motor Drive object within a node. Supported requests are
RQ_NORMAL, RQ_UPDATE_STATUS, RQ_CLEAR_STATUS, RQ_REPORT_MASK,
RQ_DISABLED, RQ_ENABLE and RQ_CLEAR_ALARM.
nviDrvSpeedStpt
This input network variable provides control and a low resolution speed setpoint.
nviDrvSpeedScale
This input network variable provides scaling for nviDrvSpeedStpt. Negative values indicate a
motor direction in reverse. For example, if the nviDrvSpeedStpt value is 50% and nviDrvSpeed-
Scale -150%, then the actual speed setpoint is -75%, or 0.75 times the nominal speed in re-
verse direction. The valid range is -163,840% to 163,830. The value 0x7FFF (+163,835%) will
be handled as an invalid value. Default value is determined by nciDrvSpeedScale. This value
will be adopted at power-up and in case of not receiving an update within the specified Receive
Heartbeat time.
Function
Variable Name
SNVT Type
Min. value
Max.
value
Node Object request
nviRequest
SNVT_obj_request
Driver speed setpoint
nviDrvSpeedStpt
SNVT_switch
n / a
n / a
Driver set point speed
scaling
nviDrvSpeedScale
SNVT_lev_percent
-163.840%
163.830%
Reset fault
nviRstFault
SNVT_switch
n / a
n / a
Clear kWh trip or
Drive total running
hours trip counters
nviClrCntr
SNVT_switch
1
2
Process In Data
nviProcessIn1..8
SNVT_lev_percent
0
65535
Digital Inputs
nviDigitalIn1..8
SNVT_switch
0
4
Parameter Set
nviParCmd
SNVT_preset
n / a
n / a
Table 8.
State
Value
Command
0
NA
Stop
1
0
0%
1
1 to 200
0.5 to 100%
1
201 to 255
100.0%
0xFF
NA
Auto
Table 9.