Pairing Mode
Refer to Section 5.4
6.6
Purge Mode
Purge mode is used to remove a Limitless™ switch or switches from the system that have an insufficient RF link
with the WPMM (see Section 6.2.1 for possible causes and Section 6.3 for determining which Limitless™ switch(s)
have an insufficient RF link). The user will only be allowed to purge one Limitless™ switch with an insufficient RF
link at a time and the WPMM will choose the first Limitless™ switch in the Sequence of #1 to #16 that has an
insufficient RF link. The user will then need to repeat the purge process if there are more Limitless™ switches to
purge (i.e. if the user has ten Limitless™ switches paired to the WPMM and the need is to purge Limitless™ switch
sequence #3, 5, and 7; the first sequence # that will be purged is #3, repeating the process will purge #5, etc.)
Note, a Limitless™ switch with a sufficient RF link cannot be purged. If a Limitless™ switch with a good RF link is
intended to be purged, remove battery first as this will cause an ‘insufficient RF’ indication after a few minutes.
Ensure proper power is applied to the WPMM (green
LED illuminated) before proceeding with this procedure.
Step Action
1
Press the Function button
on WPMM for approximately eight to 12 seconds at which time the green
,
amber
, red
LEDs will be flashing. Refer to Figure 10.
2
The WPMM will then indicate a purge with the red
LED flashing and the buzzer will beep the sequence
number (1 to16) of the Limitless™ switch that is being purged. Once the purge is completed, all LEDs will not
illuminate for one second and then the WPMM will return to normal operation with the green
LED
illuminated.
3
Repeat above steps if necessary to purge more Limitless™ switch(s).
6.7
Factory Reset Mode
Factory reset mode is used to remove/un-pair all Limitless™ switches that were previously paired to the WPMM and
thus it is being returned to the as-manufactured condition. Ensure proper power is applied to the WPMM (green LED
illuminated) before proceeding with this procedure.
Step Action
1
Press the Function button
on WPMM for approximately 16 seconds at which time the green
, amber
, red
LEDs will be flashing and the buzzer will buzz. Continue to hold the Function button on WPMM
until the LEDs turn off and the buzzer stops at which time immediately release the Function button. All LEDs
will not illuminate for one second and then the WPMM will go through the start-up sequence and then return
to normal operation with the green
LED illuminated. Refer to Figure 10.
2
Verification of proper reset can be confirmed by operating each of the Limitless™ switches that were
originally paired to the WPMM that was reset. Repeat procedure if the Limitless™ switches are still indicating
an output on the WPMM.
3
Turn power off to WPMM