L91A,B,D PROPORTIONING PRESSURETROL

®

 CONTROLLERS

60-2152—08

8

CHECKOUT

After the controller is installed, wired, and set, it should be 

tested with the system in operation. First, allow the system to 

stabilize. Then, observe the operation of the controller while 

raising and lowering its setpoint. Pressure should increase 

when the setpoint is raised and decrease when the setpoint is 

lowered. Use accurate pressure testing equipment when 

checking out the controller. Do not rely on inexpensive gauges. 

The controllers are carefully calibrated at the factory.

Make sure the modulating motor or modulating valve actuator 

reaches the low- and high-fire positions at the proper points. If 

the motor or actuator runs in the proper direction when the 

setpoint is adjusted, assume that the controller is operating 

properly. If it runs in the wrong direction, reverse the B and W 

wires. Observe the action of the motor or actuator until it 

stabilizes. If the motor or valve is moving constantly, widen the 

proportioning range (not adjustable on an L91A) incrementally 

until the system is stable.

If a Controller Seems to Operate 
Improperly

If the controller is suspected of operating improperly, it may be 

further checked by:

1.

Leaving the controller installed where it is, but discon-

necting all power to the controller motor or valve.

2.

Loosening the cover screw below the main scaleplate 

and removing the cover.

3.

Disconnecting the wires from the controller.

4.

Connecting an ohmmeter between controller terminals B 

and W to measure the resistance for the potentiometer in 

the controller. The ohmmeter should read about 135 

ohms for an L91A,B, or D.

5.

Connecting the ohmmeter between controller terminals 

W and R (Fig. 8) and raising the setpoint of the controller 

above the actual pressure being measured. The ohmme-

ter should read the full value of the potentiometer mea-

sured in step 4 (135 ohms for an L91A,B, or D).

6.

Slowly lowering the setpoint of the controller while 

observing the ohmmeter reading. The resistance should 

drop to zero at some setpoint below the actual pressure.

7.

Making an approximation of the proportioning range by 

observing the change in setpoint required for a resis-

tance change from zero to full value.

8.

When the controller is operating properly, reconnecting 

the wires, replacing the cover, tightening the cover 

screw, and resetting the controller to the desired value.

9.

Reconnecting power to the controlled motor or valve. 

Fig. 7. Checking L91 Proportioning Pressuretrol

®

 

Controller.

CAUTION

Equipment Damage Hazard.

Failure to follow checkout instructions can damage 

components or systems.

Do not put the system into service until you have 

satisfactorily completed all applicable tests described in 

this Checkout section, all tests in the Checkout section 

of the applicable instructions, all tests for the flame 

safeguard control, and any tests required by the burner 

and boiler manufacturers.

DIFF.

MAIN

MIN

B

D

F

E

C

A

0

4

6

2
1

3

4

5

16
14
12
10

8

0

kPa

 OZS

  IN

2

DIFF. IS

ADDITIVE

2

6

7

M8546A

PROPOTIONING 

RANGE ADJUSTING

SCREW

(L91B,D ONLY)

INPUT

OUTPUT

ZERO

ADJ

0

135

W

W

R

R

B

B

SETPOINT

INCREASE

MAIN SCALE

ADJUSTING SCREW

MAIN SCALE

SETTING

INDICATOR

INCREASES TO

135 OHMS

OHMMETER

1     KNURLED ADJUSTMENT KNOB ON 10 TO 300 PSI [0.07 TO 2.07 MPA]

       MODELS.

2     TERMINALS ARE LABELED

3     135 OHMS ON L91A,B OR D.

3

2

1

Содержание L91A

Страница 1: ...iphon loop is recommended Wiper on controller potentiometer moves in response to pressure changes L91D has two potentiometers for unison control of two motors L91B D models have adjustable proportioning throttling range to allow selection of desired pressure control range Adjustments made with screws on case top Large easily read scaleplates in both U S customary oz sq in psi or in Hg and metric k...

Страница 2: ...rled knob for main scale setting on 10 to 300 psi 0 07 to 2 07 MPa models Setpoint At low pressure end of proportioning throttling range Main Scaleplate Marked in both U S customary oz sq in psi or in Hg and metric kPa MPa or mm Hg units Proportioning Range Scaleplate L91B D only Gradu ated from A to F with a MIN minimum value below A See Table 2 for the value of each division Mounting Means Fitti...

Страница 3: ...6 Steam Trap siphon loop 1 4 in steel pipe with 1 4 18 NPT external threads on both ends 33312B Knurled Adjustment Knob With setscrew fits on main scale pressure adjusting screw 4074BWJ Limit Stop Assembly To limit setpoint ranges includes 129564 Range Stop 107194 Range Stop Screw and 23466 Wrench Table 2 Approximate value of each division A to B B to C etc on proportioning throttling range scalep...

Страница 4: ...RE ALSO AVAILABLE WITH 1 4 19 BSP TR INTERNAL THREADS SEE TABLE 1 PROPORTIONING RANGE ADJUSTING SCREW ON L91B D MODELS ONLY 33312B KNURLED ADJUSTMENT SCREW KNOB 7 8 IN 22 2 MM DIAMETER KNOB IS INCLUDED WITH 10 TO 300 PSI 0 07 TO 07 MPa MODELS OPTIONAL ACCESSORY FOR OTHER MODELS FOR 10 TO 300 PSI 0 07 TO 2 07 MPa MODELS DIM C INCLUDES THE KNURLED ADJUSTMENT KNOB TABULATION OF DIMENSIONS A B AND C O...

Страница 5: ...ns in accordance with approved standards Use only a small amount of pipe compound to seal the connection joints Excess pipe compound may clog the small hole in the fitting and prevent the controller from operating properly To avoid leaks and damage to the case use a parallel jaw wrench on the controller fitting Do not tighten the controller by hand by holding onto the case and turning it Fig 2 App...

Страница 6: ...ain Scale Set Point All models Adjust the main scale setpoint for the desired operating pressure by turning the main scale adjusting screw Fig 7 or knurled adjustment knob on 10 to 300 psi 0 07 to 2 07 MPa models on the top of the case until the main scale setting indicator is at the minimum pressure desired The proportioning range extends above this value The scaleplate is marked in both customar...

Страница 7: ...nced that is equal the relay contacts are open When the circuit is balanced the motor or actuator does not run If the pressure of the medium rises the wiper in the controller moves toward W This unbalances the circuit so a larger current flows through one side of the balancing relay The close contacts in the relay make causing the motor or valve actuator to drive toward its closed position As the ...

Страница 8: ...e controller The ohmmeter should read about 135 ohms for an L91A B or D 5 Connecting the ohmmeter between controller terminals W and R Fig 8 and raising the setpoint of the controller above the actual pressure being measured The ohmme ter should read the full value of the potentiometer mea sured in step 4 135 ohms for an L91A B or D 6 Slowly lowering the setpoint of the controller while observing ...

Страница 9: ... the wiper arm and not to change the wiper tension Any damage or change in tension will decrease the life of the new potentiometer 1 Disconnect all power to the controller 2 Loosen the cover screw below the main scaleplate and remove the cover 3 Mark the wires to the external device motor or valve actuator and disconnect them from the terminal block 4 Remove the screw holding the terminal block br...

Страница 10: ...A 0 4 6 2 1 3 4 5 16 14 12 10 8 0 kPa OZS IN 2 DIFF IS ADDITIVE 2 6 7 M8547A BARE WIRES ENAMEL REMOVED TERMINAL BLOCK R W B POTENTIOMETER WIRES WIPER ARM BOLT POTENTIOMETER ACTIVE WINDING POTENTIOMETER BRACKET 1 1 2 2 THE POTENTIOMETER IN AN L91A IS MOUNTED AT A 45 DEGREE ANGLE INSTEAD OF HORIZONTALLY AN L91D HAS TWO POTENTIOMETERS TERMINALS ARE LABELED DIFF MAIN MIN B D F E C A 0 4 6 2 1 3 4 5 16...

Страница 11: ...L91A B D PROPORTIONING PRESSURETROL CONTROLLERS 11 60 2152 08 ...

Страница 12: ...ons Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 Honeywell Limited Honeywell Limitée 35 Dynamic Drive Toronto Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2009 Honeywell International Inc 60 2152 08 K K Rev 12 09 Printed in U S A ...

Отзывы: