L4064B, L4064R UNIVERSAL COMBINATION FAN AND LIMIT CONTROLLERS

69-0115—11

2

Do not exceed the following electrical ratings 
(amperes):

Table 1. Electrical Ranges

Pilot Duty: 2 A at 24 Vac; 0.25 A at 0.25 to 12 Vdc. 
Maximum Combined Connected Load: 2000 VA. 75 ºC 
(167 ºF) (min.) field wiring required. Wiring must 
conform to NEC Class 1 requirements.

Approval

— IP20  compliance
— Classified as TR/TW
— CSA certified file #095329
— UL listed file #MP3387
— DVGW certified ID-No:

CE-0085BM0320 for B type only

LOCATION

If this is a replacement installation, locate the L4064 
in the same location as the control being replaced. 
Sensing tube length should be same as old control. If 
this is a new installation, the element should be 
installed only by a trained, experienced service 
technician according to the furnace manufacturer’s 
instructions. The element must not touch any internal 
part of the furnace.

NOTE:

The electrical rating is at maximum switch 
temperature of 190 ºF (88 ºC). If plenum sur-
face temperature exceeds 190 ºF (88 ºC), 
heat insulating material or mounting bracket 
must be used.

MOUNTING

The devices may be mounted as follows:
  L4064B — Swivel mount
  L4064R — Swivel mount

Fig. 1. Surface mounting for L4064B requires a

13/16 in. (20.6 mm) hole.

Surface Mounting (Fig. 1)

L4064B—Hole in plenum should be just large enough 
to accommodate the 3/4 in.(19.1 mm) diameter 
element tube. A 13/16 in. (20.6 mm) diameter hole is 
recommended.

1.

Remove cover by removing screw, squeezing 
sides and pulling off. Insert element in plenum 
and mark location of mounting holes. Make sure 
the case is snug against the plenum before 
marking the mounting holes.

2.

Punch or drill holes for mounting screws.

3.

Place insulation between plenum and case 
if necessary.

4.

Fasten controller securely with mounting 
screws.

Swivel Mounting (Fig. 2)

The L4064B and L4064R may be swivel-mounted. The 
swivel bracket requires a 1-9/16 in. (39.7 mm) hole in
the plenum.

1.

Use bracket as a template to make the location 
of mounting holes in plenum. Drill or punch 
holes for mounting screws.

2.

Fasten the bracket in place with furnished 
screws. Start the screws but do not tighten.

3.

Insert element tube through bracket, straighten 
controller, and fasten. Tighten the mounting 
screws securely. It may be necessary to rotate 
the bracket to tighten all screws securely.

Fig. 2. Swivel mounting requires a 1-9/16 in. 

(40 mm) diameter mounting hole for element 

insertion.

120 Vac

240 Vac

FAN

LIMIT

FAN

LIMIT

Full Load

14

8

7

4

Locked 
Rotor

84

48

42

24

ADD HEAT

INSULATING

MATERIAL IF

NEEDED

FURNACE

PLENUM

M31163

M31164

FURNACE

PLENUM

REQUIRE 1-9/16 IN

[39.7mm] DIAMETER

HOLE IN PLENUM

32612A SWIVEL

BRACKET

Содержание L4064R

Страница 1: ...N OFF setting is reached If the call for heat continues until the temperature in the plenum rises to the LIMIT setting the bimetal element will mechanically break the limit contacts and de energize the heating control circuit INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to fol low them could damage the product or cause a hazardous condition 2 Check the rati...

Страница 2: ... 20 6 mm hole Surface Mounting Fig 1 L4064B Hole in plenum should be just large enough to accommodate the 3 4 in 19 1 mm diameter element tube A 13 16 in 20 6 mm diameter hole is recommended 1 Remove cover by removing screw squeezing sides and pulling off Insert element in plenum and mark location of mounting holes Make sure the case is snug against the plenum before marking the mounting holes 2 P...

Страница 3: ...Fig 5 For Standard wire Push in terminals Connect wires to the terminals as follows 1 Use Nos 14 16 or 18 solid wire or Nos 14 or 16 stranded wire depending on electrical require ment 2 Strip insulation from wires the distance shown by the strip gauge on the controller If wire insu lation is 4 64 in 2 mm thick strip additional 1 4 in 6 mm to ensure wire seats securely in push in connectors 3 Solid...

Страница 4: ...n is complete disconnect the fan motor circuit at the L4064 Turn on power and set thermostat to call for heat Burner should come on and limit controller should shut burner off when plenum temperature reaches the limit set point Turn off power reconnect the fan switch turn on power and again set thermostat to call for heat The fan should start when plenum temperature has reached fan on setting Fig ...

Отзывы: