PFU 780 · Edition 02.12l
38
Parameters
Restart following flame failure
Parameter 13 = 1:
Restart following flame failure.
06
05
07
08
08
t
t
SA2
t
FS2
1x
t
W2
t
SB
>2 s
26a
16c
18e
2c–4c
18a
14a
88
10e
26e
30a
28c
2e–4e
6a–6e
V1
1
V2
2
ϑ
1
ϑ
2
2
1
If the PFU detects a flame failure after a minimum op-
erating time of 2 s, valve V2 is closed and the operation
signalling contact is opened within time t
SB
.
The burner control unit now attempts to restart the
main burner once. If the burner does not function, a
fault lock-out occurs. The display blinks and shows the
cause of the fault.
In accordance with EN 746-2, a restart may be con-
ducted only if the safety of the installation is not im-
paired. Restart is recommended for burners which oc-
casionally display unstable behaviour during operation.
The precondition for a restart is that activation of the
restart allows the burner to restart as intended (in all
operating phases). In this case, it must be ensured that
the program sequence started by the PFU matches the
application.