Medium

Designed lifetime

Switching cycles

Time [years]

Gas

50,000

10

Air

250,000

10

You can find further explanations in the applicable 

rules and regulations and on the afecor website 
(www.afecor.org). This procedure applies to heating 
systems. For thermoprocessing equipment, observe 
local regulations.

Accessories

See Technical Information DG (D, GB, F) – 
www.docuthek.com

Logistics

Transport

Protect the unit from external forces (blows, shocks, 
vibration). On receipt of the product, check that the 
delivery is complete, see page 1 (Part designa-
tions). Report any transport damage immediately.

Storage

Store the product in a dry and clean place.
Storage temperature: see page 3 (Technical data). 
Storage time: 6 months before using for the first 
time. If stored for longer than this, the overall service 
life will be reduced by the corresponding amount of 
extra storage time.

Packaging

The packaging material is to be disposed of in ac-

cordance with local regulations.

Disposal

Components are to be disposed of separately in 
accordance with local regulations.

Certification

Declaration of conformity

We, the manufacturer, hereby declare that the prod-

uct DG with product ID No. CE-0085AP0467 com-
plies with the requirements of the listed Directives 
and Standards.
Directives: 2009/142/EC – GAD (valid until 20 April 

2018), 2014/35/EU – LVD

Regulation: (EU) 2016/426 – GAR (valid from 
21 April 2018)
Standards: EN 13611:2015+AC:2016, 
EN 1854:2010

The relevant product corresponds to the tested type 

sample. The production is subject to the surveillance 
procedure pursuant to Directive 2009/142/EC Annex II 
paragraph 3 (valid until 20 April 2018) and to Regula-
tion (EU) 2016/426 Annex III paragraph 3 (valid from 
21 April 2018).
Elster GmbH
Scan of the Declaration of conformity (D, GB) – see 
www.docuthek.com

SIL, PL

The pressure switches are suitable for single-channel 

systems (HFT = 0) up to SIL 2/PL d, and up to SIL 3/
PL e when two redundant pressure switches are 
installed in a double-channel architecture (HFT = 1), 
provided that the complete system complies with the 
requirements of EN 61508/ISO 13849. The safety 
function value which is actually achieved is derived 
by taking all components into account (sensor – logic 

– actuator). For this, the demand rate and structural 

measures to avoid/detect nonconformity are to be 
observed (e.g. redundancy, diversity, monitoring).

Characteristic values for SIL/PL: HFT = 0 (1 de-
vice), HFT = 1 (2 devices), SFF > 90, DC = 0, 
type A/category B, 1, 2, 3, 4, high demand mode, 
CCF > 65, ß ≥ 2.

PFH

D

 = 

λ

D

 = 

x n

op

1

MTTF

d

0.1

B

10d

 

U

I

B

10d

 value

24 V DC

10 mA

6,689,477

230 V AC

4 mA

24 V DC

70 mA

4,414,062

230 V AC

20 mA

230 V AC

2 A

974,800

RoHS compliant, Eurasian Customs Union, 

AGA approved

Directive on the restriction of the use of haz-

ardous substances (RoHS) in China

Scan of the Disclosure Table China RoHS2 – see 
certificates at www.docuthek.com

AGA

Содержание Krom Schroder DG B Series

Страница 1: ...chnical changes are prohibited Only use OEM spare parts Changes to edition 11 17 The following chapters have been changed Declaration of conformity Checking the usage Gas pressure switches DG for monitoring increasing and decreasing gas or air pressure Positive pressure Negative pressure DG B Gas air flue gas DG U Gas air flue gas Air flue gas This function is only guaranteed when used within the ...

Страница 2: ...tallation space Ensure unobstructed view of the hand wheel 1 Disconnect the system from the electrical power supply 2 Shut off the gas supply 3 Ensure that the pipeline is clean 2 1 3 4 1 and 2 Positive pressure Rp 3 and 4 Negative pressure Rp 1 8 Connect Seal Free Positive pres sure DG U 1 2 3 or 4 2 1 3 or 4 Negative pres sure DG U 3 4 1 or 2 4 3 1 or 2 Differential pres sure DG U 1 or 2 for hig...

Страница 3: ... with biogas A function check can be carried out in case of decreasing pressure control e g with the PIA After carrying out the maintenance work check for tightness see page 3 Tightness test Technical data Gas type natural gas town gas LPG gaseous flue gas biogas max 0 1 by vol H2S and air Max inlet pressure pmax withstand pressure see page 3 Adjustment Max test pressure for testing the entire sys...

Страница 4: ...eclare that the prod uct DG with product ID No CE 0085AP0467 com plies with the requirements of the listed Directives and Standards Directives 2009 142 EC GAD valid until 20 April 2018 2014 35 EU LVD Regulation EU 2016 426 GAR valid from 21 April 2018 Standards EN 13611 2015 AC 2016 EN 1854 2010 The relevant product corresponds to the tested type sample The production is subject to the surveillanc...

Отзывы: