Adjustment

 

The switching point is adjustable via hand wheel.

 1 

  Disconnect the system from the electrical power 

supply.

 2 

 Detach the housing cover, see page 3 (Tech-

nical data).

 3 

 Connect an ohmmeter.

NO

2

NC

1

COM

3

COM

3

NC

1

NO

2

0

1 cm = 1 mbar

 4 

 Set the switching point using the hand wheel.

 5 

 Connect a pressure gauge.

NO

2

NC

1

COM

3

COM

3

NC

1

NO

2

0

1 cm = 1 mbar

 6 

 Apply pressure. In doing so, monitor the ohm-

meter and the pressure gauge.

Type

Adjusting 

range* 

[mbar]

Switching 

 differential** 

[mbar]

Max. inlet 

pressure 

p

max

 [mbar]

DG 6

0.4 – 6

0.2 – 0.3

100

DG 10

1 – 10

0.25 – 0.4

500

DG 30

2.5 – 30

0.35 – 0.9

500

DG 50

2.5 – 50

0.8 – 1.5

500

DG 150 30 – 150

3 – 5

600

DG 400 50 – 400

5 – 15

600

DG 500 100 – 500

8 – 17

600

 Adjusting tolerance = ± 15% of the scale value.

**   Mean switching differential at min. and max. setting.

 

Deviation from the switching point during test-
ing pursuant to EN 1854 Gas and air pressure 
switches: ± 15%. For DG 6: EN 1854 Air pressure 
switches: ± 15%  or  ± 0.1 mbar.

 

If the DG does not trip at the desired switching 
point, correct the adjusting range using the hand 
wheel. Relieve the pressure and repeat the process.

Tightness test

 1 

 Shut off the downstream gas pipeline close to 

the valve.

 2 

 Open the valve and the gas supply.

 

Check all used ports for tightness.

N

2

 

900 mbar
max. 2 bar 
< 15 min 

3

4

Maintenance

In order to ensure smooth operation: check the tight-
ness and function of the DG every year, or every six 
months if operated with biogas.

 

A function check can be carried out in case of 

decreasing pressure control e.g. with the PIA.

 

After carrying out the maintenance work, check 

for tightness, see page 3 (Tightness test).

Technical data

Gas type: natural gas, town gas, LPG (gaseous), 
flue gas, biogas (max. 0.1 %-by-vol. H

2

S) and air.

Max. inlet pressure p

max

 = withstand pressure, 

see page 3 (Adjustment). Max. test pressure 
for testing the entire system: temporarily < 15 min-
utes 2 bar.
Switching capacity:

I (cos φ = 1) I (cos φ = 0,6)

DG 24 – 250 V AC 0.05 – 5 A

0.05 – 1 A

DG..G 5 – 250 V AC 0.01 – 5 A

0.01 – 1 A

5 – 48 V DC

0.01 – 1 A

Maximum medium and ambient temperatures:  

-20 to +80°C.

Long-term use in the upper ambient temperature range 
accelerates the ageing of the elastomer materials and 
reduces the service life (please contact manufacturer).
Storage temperature: -20 to +40°C.
Diaphragm pressure switch, silicone-free.
Diaphragm: NBR.
Housing: glass fibre reinforced PBT plastic with 
low gas release.
Lower housing section: AlSi 12.
Enclosure: IP 54 or IP 65. Safety class: 1.
Line diameter: 0.5 to 1.8 mm (AWG 24 to AWG 13).
Line entrance: M16 x 1.5, clamping range: diam-
eters of 4 to 10 mm.
Electrical connection type: screw terminals.
Max. tightening torque, see Technical Information 
bulletin DG (D, GB, F) – www.docuthek.com.
Weight: 270 to 320 g.
Safety information, see Safety manual DG 
(D, GB) – www.docuthek.com.

Designed lifetime

This information on the designed lifetime is based on 

using the product in accordance with these operat-
ing instructions. Once the designed lifetime has been 
reached, safety-relevant products must be replaced.
Designed lifetime (based on date of manufacture) in 
accordance with EN 13611, EN 1854 for pressure 
switches:

Содержание Krom Schroder DG B Series

Страница 1: ...chnical changes are prohibited Only use OEM spare parts Changes to edition 11 17 The following chapters have been changed Declaration of conformity Checking the usage Gas pressure switches DG for monitoring increasing and decreasing gas or air pressure Positive pressure Negative pressure DG B Gas air flue gas DG U Gas air flue gas Air flue gas This function is only guaranteed when used within the ...

Страница 2: ...tallation space Ensure unobstructed view of the hand wheel 1 Disconnect the system from the electrical power supply 2 Shut off the gas supply 3 Ensure that the pipeline is clean 2 1 3 4 1 and 2 Positive pressure Rp 3 and 4 Negative pressure Rp 1 8 Connect Seal Free Positive pres sure DG U 1 2 3 or 4 2 1 3 or 4 Negative pres sure DG U 3 4 1 or 2 4 3 1 or 2 Differential pres sure DG U 1 or 2 for hig...

Страница 3: ... with biogas A function check can be carried out in case of decreasing pressure control e g with the PIA After carrying out the maintenance work check for tightness see page 3 Tightness test Technical data Gas type natural gas town gas LPG gaseous flue gas biogas max 0 1 by vol H2S and air Max inlet pressure pmax withstand pressure see page 3 Adjustment Max test pressure for testing the entire sys...

Страница 4: ...eclare that the prod uct DG with product ID No CE 0085AP0467 com plies with the requirements of the listed Directives and Standards Directives 2009 142 EC GAD valid until 20 April 2018 2014 35 EU LVD Regulation EU 2016 426 GAR valid from 21 April 2018 Standards EN 13611 2015 AC 2016 EN 1854 2010 The relevant product corresponds to the tested type sample The production is subject to the surveillanc...

Отзывы: