MU5H-1419GE23 R0815
13
Honeywell GmbH
English
• Open the tapping point completely to ensure a sufficient
flow
3. Readjust by turning the screw if necessary
4. Repeat the above steps until the measured value is equal
to the value set under 8.3.2. (default 15°fH).
8.4. Programming - Advanced Installers
8.5. Basic settings
The basic settings such as changing water hardness and
regeneration time are described in detail in 8.3.
8.5.1. Unlocking the set mode
To unlock the set mode press following buttons one after
another .
8.5.2. Locking the set mode
To lock the set mode press following buttons one after
another .
8.5.3. Setting parameters
The KS20S softener can be programmed by defining the
following parameters:
• Operating mode
• Cycle times
• Capacity
• Brine tank refill type
• Regeneration start time
• Reserve type
• Service alarm
8.5.4. Set mode
1. Push and hold for 3 seconds both buttons
and
until the display shows "SOFTENING".
2. Push
to go to the next parameter.
8.5.5. Cycle times
The display shows FILL TIME.
1. Push
or
to set up the amount of salt in kg
for cycle 1 (see 8.6.4. Operation cycles).
2. Push
to go to the next parameter.
The display shows SOFTENING TIME
3. Push
or
to set up the number of minutes for
cycle 2 (see 8.6.4. Operation cycles).
4. Push
to go to the next parameter.
The display shows DRAW TIME
5. Push
or
to set up the parameters for
cycles 3, 4 and 5 (see 8.6.4. Operation cycles).
8.5.6. Capacity
The display shows SOFTENING CAPACITY.
• If hardness unit is f°H then capacity unit is m
3
.
6. Push
or
to set up the softener capacity.
7. Push
to go to the next parameter.
8.5.7. Brine tank refill
The display shows FILL.
You can select between "NORMAL" and "PROPORTIONAL"
brine tank refill.
8. Push
or
to change between the brine tank
refill types.
• NORMAL: the unit regenerates completely.
• PROPORTIONAL (default): corresponds with ratio of
used capacity on total capacity multiplied
by refill for a complete regeneration
of resin bed.
9. Push
to go to the parameter "Reserve type".
10. Push
to go to the next parameter.
8.5.8. Reserve calculator
The display shows RESERVE CALCULATOR
Caution!
Programming must be perfomed by
authorized personnel only.
Note!
To set the parameters the setting mode must be
unlocked!
Note!
Remember to lock the set mode after the setting
of the parameters.
Caution!
Do not change any settings in the FILTERING
mode. Any changes in the FILTERING mode will
prevent the device from functioning correctly.
Note!
In this manual, only the SOFTENING operating
mode is described.
Note!
This pa rameter is o nly available if con figured
as a 25 mm Pre-Fill Up-Flow brining softener.
Содержание KaltecSoft Evolution KS20S-15
Страница 2: ......
Страница 47: ...MU5H 1419GE23 R0815 45 Honeywell GmbH ...