HONEYWELL IDENTIPOINT™ INTELLIGENT SMARTCARD SYSTEM
23
95-7767
Power Wiring
IMPORTANT
Use a shielded power cable with a three-pin (or as
per local regulations) plug to draw mains power for
the power supply assembly. (The shielded wire is
required to meet FCC RF radiation limits.)
To route the power wiring
1.
Using proper conduits, route the input power cable from
the mains supply to the input block of the power supply.
2.
Route the +ve and -ve pairs of wires from the output
block of the power supply out of the power supply enclo-
sure via proper conduits.
3.
Connect the +ve and -ve of wires to IdentIPoint devices.
For readers, connect the +ve to the red and the -ve to
the black wires of the 9-pin Molex terminal respectively.
(See Fig.6 for details on Molex terminal wire colors.)
Tamper Protection
IMPORTANT
IdentIPoint readers are equipped with tamper protec-
tion features. They must be permanently mounted
before commissioning. Attempting to open a reader
case without putting it in maintenance mode will dis-
able the reader, and require recommissioning. For
details on how to deal with a tampered reader please
refer the EBI documentation set.
Table 2. Wire Sizes and Distances
EACH DOOR STRIKE REQUIRES A 14507020-001 DIODE
SUPPRESSION NETWORK. DOOR STRIKE MAY DRAW A
MAXIMUM CURRENT OF 2A; REGULATED 12/ 24 VDC.
DOOR STRIKE AND REX MUST BE UL LISTED. SEE
FIG.25 THROUGH FIG.28 FOR TYPICAL DIODE SUP-
PRESSION NETWORK WIRING.
DOOR CONTACTS MUST BE UL LISTED. MAXIMUM WIRE
LENGTH 500 FT (152 M). WIRE TYPE 18 AWG (0.8 SQ
MM), 50 OHM 60 mA MAXIMUM. DOOR CONTACTS ARE
ONLY INTENDED FOR MONITORING DOOR POSITION.
THEY ARE NOT INTENDED FOR CONNECTION TO A
BURGLAR ALARM PANEL
EXIT SWITCH: WIRING MUST BE COMPLETED WITHIN
THE PROTECTED AREA OR NOT READILY ACCESSIBLE
OUTSIDE THE PROTECTED AREA. THE EXIT SWITCH
MUST BE UL LISTED.
Connection
Wire Gauge
Maximum Distance
Minimum
number of
conductors
Shielding
Power Source to
Device (Reader
or IOM)
18 AWG
(0.8mm
2
) to 15
AWG (1.7mm
2
)
See reader/IOM power requirements
(section
Power Supply Recommendations
of
Assembly, Mounting and Installation
topic) and compensate for drop in voltage.
3
Unshielded
cable
recommended
Reader/IOM to
Digital Inputs
18 AWG
(0.8mm
2
)
100m
2 per i/p
Optional
Reader/IOM to
Digital Output or
Lock
18 AWG
(0.8mm
2
) to 15
AWG (1.7mm
2
)
100m subject to adequate power reaching
the output device or lock
2 per o/p
Required for
power cable
connected to
output device or
lock
Reader to IOM
(Power)
18 AWG
(0.8mm
2
) to 15
AWG (1.7mm
2
)
See IOM power requirements (section
Power Supply Recommendations
of
Assembly, Mounting and Installation
topic)
and compensate for drop in voltage.
2
Required
Reader to IOM
(RS485 comm.)
18 AWG
(0.8mm
2
)
500m 3
Recommended
Reader to IOM
(other than Power
and RS485
comm.)
18 AWG
(0.8mm
2
)
100m
2 per connection
type
Optional
IOM to IOM
(RS485 comm.)
18 AWG
(0.8mm
2
)
500m 3
Recommended
Ethernet
CAT5
100m
Standard as in
CAT5
Recommended