3
4 Voltage Output Selection Table
5 LED Diagnostics
Figure 2 HPS3 Diagram
Output
SW1
(on is up)
SW2
(on is up)
24 VDC
Off
On
12 VDC
Off
Off
6 VDC
On
Off
Red (DC) LED
Green (AC) LED
Status
ON
ON
Normal operation.
ON
OFF
Loss of AC. Operating on standby power (if equipped).
OFF
ON
No DC output. Short circuit or thermal overload present.
OFF
OFF
No DC output. Loss of AC. Battery discharged or not present.
NOTE: