Products
AC current draw
(Full load)
120VAC@50/60hz
AC current draw
(Full load)
240VAC 50/60Hz
Max output
per circuit
Number of
batteries required
for backup
HP1205UL-4
1.3Amps
650mA
2.5Amps
0
HP1205UL-8
1.3Amps
650mA
2.5Amps
1
HP1210UL-8
2.6Amps
1.3Amps
2.5Amps
2
HP1210UL-16
2.6Amps
1.3Amps
2.5Amps
2
Equipment is to be installed and serviced by authorized / trained
personnel only. Installation should conform to all local codes and in accordance
with the National Electrical Code.
branch circuit power before installing /
servicing equipment. Product is intended for indoor use only.
4. Installation Instructions:
1. Unpack product. Do not discard packaging material until installation is complete.
2. Pre-drill holes on the wall where enclosure is to be mounted. Choose a vertical surface (wall)
strong enough to support the full weight of the assembly. Select a mounting location in an area
without excessive moisture; for indoor installation only and in a secured area (Electrical Room).
3. Secure enclosure to the desired wall location with the
appropriate sized fasteners using the four mounting
holes in the cabinet.
4. Disconnect power to the branch circuit to which the
product will be connected.
5. Connect incoming AC power (120 V, 60 Hz):
– Hot (L1) (black) to terminal marked “L”.
– Neutral (L2) (white) to terminal marked “N”.
– Ground (Green) to terminal marked “G”.
6. Use the knockout in bottom of cabinet for 120 VAC
wiring. Route the 120VAC wiring at least 1/4" from (low
voltage) wiring.
7. Keep a 1/4" (0.635 cm) separation between power-
limited wiring and on-power-limited wiring. Use separate
knockouts for power limited wiring.
8. Connect CCTV cameras (or other external loads) to
appropriate terminals shown in Fig 1: Connect circuit #1
to terminals marked “VO1+” and “VO1–”. Connect circuit
#2 to terminals marked “VO2+” and “VO2–”. Continue to
connect the remaining circuits, carefully observing
polarity.
9. Power the branch circuit and observe red output LEDs
illuminated. Illuminated LEDs 1-4 or 1-8 mean that Dc power is present on outputs.
10.
To avoid potential damage, verify that output voltage and load current does not exceed output
limitations. (A single extinguished LED can mean an overload condition)
See troubleshooting
guide for more information
.
11.
For Battery backup
: If battery backup is required on selected models, using the provided battery
leads, connect the Lead Acid battery(s) 7AH 12V to the battery charger terminals while carefully
observing polarity. Set the output voltage on the trim pot shown in Fig. 1 to 13.8VDC for proper
charging. Battery(s) not supplied with the finished
power supply unit. We suggest to use
Power Sonic Battery part NO. PS1270, UL File NO.MH20845 or any Recognized Lead Acid
UL Battery of same capacity and type,7AH 12V.
12.
G N L
+ 1 - + 2 - + 3 - + 4 -
LED 1 LED 2 LED 3 LED 4
Connecting AC Power
Hot (L1) Connects to L
Neutral (L2) Connects to N
Eath Connects to G
+ 1 - + 2 - + 3 - + 4 -
+ -
VO4
+ -
VO3
+ -
VO2
VO1
+ -
LED 4 LED 3 LED 2 LED 1
Fig. 1
Voltage
Adjust
Upon completion of wiring, secure the cabinet door with screws supplied (or the included
lock on the HP1210UL-8 and the HP1210UL-16 models) to prevent access by unauthorized personal.
Remove