background image

HM750A1000

33-00289—01

10

Mounting to the Supply Duct

The HM750 can also be mounted directly onto the supply 
duct. In this case, the steam guide must be removed and 
replaced with the steam nozzle and baffle as follows:

REMOVE THE STEAM GUIDE

CAUTION

Do not remove the cover when the humidifier 
powered.

1.

Remove the humidifier front cover.

2.

Remove the cylinder plugs and high water sensor 
plug from the cylinder pins by pulling vertically.

3.

Loosen the hose clamp furthest from the cylinder 
steam outlet  (the one attached to the plastic steam 
guide). Remove the cylinder with the short steam 
hose still attached. See Fig. 15.

4.

Remove the hose adapter by pressing on the release 
tab toward the back of the humidifier and sliding the 
hose adapter down.

Fig. 15. Changing to duct mount configuration.

PREPARE THE STEAM NOZZLE

1.

Locate the supplied steam nozzle and baffle.

2.

Insert the baffle into the duct-mount nozzle.

NOTE:

There is a keying feature on the baffle that 
ensures proper orientation of the baffle in the 
nozzle. 

Fig. 16. Insert baffle into the duct-mount nozzle.

Key ensures proper alignment.

INSTALL THE STEAM NOZZLE

1.

Install the nozzle with baffle directly onto the 
humidifier at the location where the hose adapter 
was removed. It clicks into place.

2.

Insert cylinder base into drain valve. Press down on 
the cylinder to ensure it is properly seated in the 
drain valve, otherwise it could leak

3.

Rotate the cylinder back in place while guiding the 
short steam hose attached to the cylinder onto the 
duct mount nozzle.

4.

Secure the steam hose to the duct mount nozzle with 
the hose clamp. Do NOT overtighten, or the duct 
mount nozzle could be damaged.

5.

Reconnect the cylinder plugs and high water sensor 
plug to the cylinder pins.

MOUNT HUMIDIFIER ON DUCT

1.

Using the duct mount template supplied with the 
humidifier, locate the template on the side of the 
duct where the humidifier will not interfere with the 
operation or maintenance of the furnace.

2.

Following the template, drill a 1-3/4” hole in the 
duct to insert the duct mount nozzle.

3.

Insert the top screw until 1/4 in. (6 mm) is exposed. 
Hang the humidifier via its keyhole on the screw 
head (see Fig. 17).

NOTE:

The donut-shaped foam gasket must be installed 
between the humidifier and the duct.

4.

After making sure the humidifier is level, secure it to 
the duct using two screws at the duct-mount 
locations (Fig. 12), and then replace the cover

Fig. 17. Duct mount. Install foam gasket between 

humidifier and air supply duct.

M37218

2.

 TILT OUT TO 

    REMOVE CYLINDER

1.

 REMOVE WIRE PLUGS

    LOOSEN HOSE CLAMP

4.

 SLIDE DOWN

 HOSE 

GUIDE

WARNIN

G

Electri

c Shock 

Hazard

Can cau

se seve

re injur

y

or dea

th.

A sepa

rate g

round w

ire

must b

e used.

AVERTIS

SEMENT

Fire Haza

rd

Can cau

se seve

re injur

y,

death, 

or sub

stantia

l

property

 dama

ge.

Replace o

nly with same

 type

of 1.0 amp f

ast-acti

ng fuse.

32332376-001

 Rev. A

Risqu

e de choc 

électrique

Peut ca

user 

des blessures

graves ou l

a mort.

Un fil de m

ise à la ter

re

séparé e

st néce

ssaire.

Risqu

e d’incen

die

Peut caus

er des 

blessures

graves, l

a mort ou

 des

dégâts m

atériels impo

rtants.

Remp

lacer s

euleme

nt avec

le même

 type d

e fusible à

action r

apide d

e 1.0 am

p.

3.

 PRESS ON 

    RELEASE TAB

M37197

AIR FLOW

FOAM
GASKET

AIR DUCT

MOUNTING
SCREWS

Содержание HM750

Страница 1: ...ons 33 00289 this document Annual Operation and Maintenance Reminder Tools Needed Flat head screwdriver Phillips screwdriver Wrench Copper pipe optional Level Hole saw Humidifier Configuration The HM750 is configured at the factory to operate under most conditions without the need to change its configuration NOTE Because the humidifier is factory configured for optimal performance Honeywell strong...

Страница 2: ...the steam outlet Steam lines must be installed so that no restriction can produce backpressure in the humidifier Do not mount outdoors without protection against rain snow condensation or equivalent CAUTION Water quality The Honeywell HM750 requires a cold water connection from your home s main water supply between 15 100 PSIG A throttle valve may be necessary and a water shut off valve is recomme...

Страница 3: ...nerals in the water will adhere to the cylinder electrodes The humidifier will automatically fill to a higher water level to maintain full capacity during the life of the cylinder Eventually because of scale formation it will no longer be possible for the humidifier to reach its full capacity The HM750 software monitors this condition and when detected will stop operating and the Cylinder LED will...

Страница 4: ...rements Table 3 AHRI Recommended Humidity in US gallons per day Table 4 Steam humidifier s necessary for application a a In the table above 11 GPD indicates a steam humidifier configured to run on 120 V and 22 GPD indicates a steam humidifier configured to run on 240 V Construction Type 8 000 ft3 12 000 ft3 16 000 ft3 20 000 ft3 24 000 ft3 32 000 ft3 40 000 ft3 Tight 3 3 5 0 6 7 8 3 10 0 13 4 16 7...

Страница 5: ...TIONAL OFF ON HOT HOT GROUND OFF ON 120 VAC 4 102 1 25 1 25 4 102 1 25 IF WIRED BEFORE MOUNTING 36 INCHES 914 FOR WIRING ACCESSIBILITY 240VAC 120VAC HUMIDIPRO H6062 AIR PROVING OR JUMPER 24VAC COM HUM HUM AP AP Air Proving Humidistat 1 1 THERMOSTAT OR HUMIDISTAT 3 4 19 OD 1 4 LDPE OR COPPER WATER LINE ALWAYS INSTALL A WATER SHUT OFF VALVE USE 1 2 IN OD COPPER TO WITHIN 4 FT 1 2 M OF HUMIDIFIER AIR...

Страница 6: ...t will be reduced as a result of heat loss through the steam line When possible mount the HM750 humidifier at a height convenient for servicing NOTE Do not mount on surfaces above 176 F 80 C where freezing can occur vibrating surface or floor Fig 4 Distributor nozzle installed vertically in a horizontal duct Remote mount Steam Nozzle Location Whether the humidifier is being installed directly on t...

Страница 7: ...n the supply side of ductwork As shipped the HM750 is configured with a steam guide for remote mounting The steam outlet points upwards and is only used when the humidifier is installed remote to the air supply duct The steam distributor nozzle should be installed as close as possible to the humidifier to a maximum of 15 ft 4 6 m The HM750 is supplied with a 5 ft steam hose A 15 ft hose is availab...

Страница 8: ...t Cover CONNECT STEAM HOSE TO CYLINDER M37204 TO DRAIN OBSTRUCTION 12 305 MINIMUM RADIUS SUPPORT BRACKETS USE FULL SIZE CONDENSATE TEE AT LOW POINT SLOPE LINES UP TO T AND IMMEDIATELY AFTER IT HOSE WILL SOFTEN OVER TIME PROPER SUPPORT IS NECESSARY 1 4 102 MINIMUM 12 305 MINIMUM 1 HM750 Status Service Power Idle Filling Humidifying Draining Cylinder Fault Drain Fault Codes In Front Cover 12 305 MIN...

Страница 9: ...ier see Fig 13 The steam hose should maintain an inclination of at least 4 inches 10 cm of rise for every 12 inches 30 cm of run CAUTION Do not remove the cover when the humidifier powered 1 Remove the humidifier cover and pull out the cylinder Insert the top screw until 1 4 in 6 mm is exposed Hang the humidifier via its keyhole on the screw head see Fig 12 2 After making sure the humidifier is le...

Страница 10: ...the duct mount nozzle 4 Secure the steam hose to the duct mount nozzle with the hose clamp Do NOT overtighten or the duct mount nozzle could be damaged 5 Reconnect the cylinder plugs and high water sensor plug to the cylinder pins MOUNT HUMIDIFIER ON DUCT 1 Using the duct mount template supplied with the humidifier locate the template on the side of the duct where the humidifier will not interfere...

Страница 11: ...vide free and easy draining A restricted drain can cause cylinder water to over concentrate and result in poor operation Drain line must be continuously sloped down from unit If a drain is not located near the humidifier use a condensate pump rated for hot drain water Connecting the Water Supply Line Connect water supply line Copper or LDPE supplied with equipment to the supply connection Fig 18 T...

Страница 12: ...5 amp circuit breaker All wiring must be done per governing electrical codes Failure to do so will void the product warranty The use of electric cord plugs can cause overheating and result in risk of damage to property and or personal injury Wiring Procedure 1 Install a disconnect switch between the humidifier and the circuit breaker as shown in Fig 21 and Fig 22 optional 2 Route the power supply ...

Страница 13: ...e is a call for humidity Fig 23 Wiring the steam humidifier with a digital thermostat Fan Interlock Wiring with HumidiPRO When distributing steam into a duct there could be a call for humidity when there is no air flow The HM750 with HumidiPRO control or some other thermostat can be used to enable a fan on a call for humidity If using another thermostat consult that control s manual for wiring ins...

Страница 14: ... HM750 only these two wires are necessary to control humidity Be sure to configure the control to force fan on with a call for humidity or run on a heat cycle if the fan enable wiring is not used HVAC THERMOSTAT R C U U S S G Y W R Rc G Y W R C M37198 OUTDOOR SENSOR NOTE SPDT RELAY IS NECESSARY TO PREVENT ENERGIZING THE Y TERMINAL IF THE THERMOSTAT DOES NOT ISOLATE Y AND G SPDT RELAY COM NC NO AIR...

Страница 15: ...f applicable the high limit humidistat This will enable a call for humidity 6 If the fan enable relay on the control board is used the green LED will continue to flash until the air proving closes Once the air closes the flashing green LED will become solid and the humidifier will start steam production 7 When the external humidistat calls for humidity and the air proving terminals are closed the ...

Страница 16: ... Excess Current fault 2 flashes Fill Drain fault 3 flashes Insufficient Current fault 4 flashes PCB fault 5 flashes Wrong Voltage Selector fault See the Troubleshooting section for more information MAIN BUTTON Power Drain When primary power has been wired to the humidifier the Power Drain button must be pressed in order to enable steam generation When the user so decides the humidifier may be turn...

Страница 17: ...midifier Fill cup Provides an air gap for backflow prevention Fill valve Controls flow of water into humidifier High water sensor Used to detect maximum water level in cylinder Power Drain button Used to turn the humidifier on or off Note that before the humidifier turns off the water in the cylinder is drained CAUTION The unit will still be powered internally even after being shut down Steam cyli...

Страница 18: ...ric current leak is detected In all cases proper cleaning of the drain valve is recommended HOSE CONNECTIONS Inspect annually clean as necessary NOZZLE DUCT OR REMOTE Inspect annually clean as necessary Extended Shutdown Should it be required to disconnect power to the humidifier for a period of extended shut down the following procedure shall be followed 1 Press the Power Drain button 2 Wait unti...

Страница 19: ...nd the cylinder LED will be on constantly no flashing At this point the cylinder must be replaced The steam cylinder is disposable and must be replaced at end of cylinder life Cylinder life is dependent on water supply conditions and humidifier use Always clean the drain valve before installing a new cylinder Scale from the spent cylinder may have fallen into the drain valve and could prevent its ...

Страница 20: ...nder plugs from the cylinder pins by pulling vertically 6 Using a flat screwdriver or 5 16 in nut driver loosen the hose clamp closest to the cylinder 7 Pull the cylinder away from the steam hose to disengage When free of steam hose lift the cylinder out 8 Some water may remain in the cylinder even after fully draining Have a cloth available to absorb any water Fig 29 Removing the cylinder IMPORTA...

Страница 21: ...he core 6 Using an adjustable wrench unscrew the core counterclockwise from the drain valve body 7 Carefully remove the core assembly this includes the plunger and return spring from the plastic drain valve body The plunger seal rubber stop can be cleaned using a plastic brush tooth brush or damp cloth Do NOT use a metal brush or chemical cleaning agents as this could damage the part Fig 30 Removi...

Страница 22: ...d personnel To protect the user and the control board the control board is mounted in a red electrical compartment housing 1 Disconnect main power at the external disconnect 2 Using a flat screwdriver turn the lock on the humidifier s front cover 90 counterclockwise to release Rotate the base of the cover outwards 6 inches then lift upwards to remove 3 Use a flat screwdriver to loosen the retainin...

Страница 23: ... the wiring to the solenoid See Fig 32 6 Remove quick connect fitting from inlet valve 7 Grip the inlet valve and pull forward as far as possible 8 Inside the humidifier bend the hose attached to the inlet valve up as shown in Fig 33 9 Using pliers move the clamp up the hose away from the valve to release its hold Slide the hose off the valve Some remaining water in the hose will spill out Have a ...

Страница 24: ...e located beside transformer Incorrect voltage Check voltage against specification label and correct Step down transformer not outputting 24 VAC Replace the circuit board Incorrect primary power jumper Check that the on board voltage selection jumper is installed correctly If 240 VAC power was supplied to a unit where the voltage selection jumper was set to 120 VAC the circuit board will need to b...

Страница 25: ...rmal operation None Cylinder solid Cylinder end of life Normal operation Replace cylinder Fault 1 flash Excess Current Current has exceeded 130 of max Drain blocked water over concentration Clean the drain line Drain solenoid not energized water over concentrated Check and correct wiring to drain valve Filling too fast wrong fill valve Fill valve may be defective replace if necessary Water supply ...

Страница 26: ...CB Error The control board detects current draw when the humidifier is in standby mode Replace circuit board Fault 5 flashes Wrong Voltage Selection VOLTAGE SELECTION jumper on control board is incorrectly set If 240VAC is supplied to the humidifier but the VOLTAGE SELECTION jumper is set to 120VAC the control board will fail and need to be replaced If 120VAC supplied to the humidifier but the VOL...

Страница 27: ...TAT AIR PROVING SW GT RF GF IDLE LED FILLING LED HUMIDIFYING LED DRAINING LED CYLINDER LED FAULT LED ON OFF DRAIN FAULT RESET BUTTON BLACK BLUE RED YELLOW FILL VALVE DRAIN VALVE FAULT CODES NUMBER OF FLASHES INDICATES FAULTS TO CLEAR FAULTS PRESS AND HOLD POWER BUTTON FOR FIVE SECONDS 1 EXCESSIVE CURRENT 2 FILL DRAIN ERROR 3 INSUFFICIENT CURRENT 4 PCB ERROR 3 WRONG VOLTAGE SELECTION FLASHING IDLE ...

Страница 28: ...at the defect was caused by damage which occurred while the product was in the possession of a consumer Honeywell s sole responsibility shall be to repair or replace the product within the terms stated above HONEYWELL SHALL NOT BE LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING DIRECTLY OR INDIRECTLY FROM ANY BREACH OF ANY WARRANTY EXPRESS OR I...

Отзывы: