HE360 HUMIDIFIER AND INSTALLATION KIT

69-1646EF—01

2

• Select a location that cannot damage the air 

conditioner A-coil during installation.

• Do not locate the humidifier on the furnace body.
• Allow adequate clearance in front of and above the 

humidifier so you can easily remove the cover to 
perform routine maintenance. 
— Mount the humidifier at least 3 in. (78 mm) above 

the furnace body to allow adequate space for the 
solenoid valve and drain line.

— Mount the humidifier in a conditioned space to 

prevent freezing.

Fig. 1. Typical humidifier installation locations.

Selecting Water Supply Location

• Use either hard or soft water in the humidifier and 

either hot or cold water. The water flow rate, with the 
humidifier running, is 3.5 gal/hr (13 liters/hr) to flush 
the pad and provide moisture for evaporation. 

• Make sure that the 20 ft (6.2m) of feed water tubing 

provided is adequate to connect the water supply 
(saddle valve) with the humidifier solenoid valve.

Locating Closest Floor Drain 

• Select location with access to a floor drain to provide 

drainage for air conditioner condensation and 
humidifier drainage.

• If you do not have a drain available, we recommend 

that you install the Honeywell Whole House Drum or 
Disk Humidifier. Make sure that the 10 ft (3.1m) of 
drain tubing is adequate to reach from the humidifier 
drain connection to the floor drain. 

Selecting Location for Sail Switch

• Select a location for the sail switch in the cold air 

return duct where the sail is in the direct path of an 
unrestricted air stream.
— Sail switch detects when furnace fan is operating.

• Select a location where the air duct is at least 12 in. 

(305 mm) deep and 8 in. (203 mm) wide to allow 
operation of the sail without affecting the smooth flow 
of air in the duct. 
— Airflow at the location can be vertical (up or 

down) or horizontal.

IMPORTANT

Mounting the S688 in warm air supply duct can 
reduce the sail life.

• Mount the switch at least 6 in. (152 mm) upstream 

from an elbow or junction, and at least 15 in. 
(381 mm) downstream from an elbow or junction. 

• Locate the switch on the opposite side of the duct 

from the air entrance. (See Fig. 1-3 in S688 
Installation Instructions.) 

Selecting Location for Humidistat

• Select a location for the humidistat on the return 

plenum or on the wall in the living space. 
— Mounting on the return plenum is the easiest 

installation for the control wiring circuit.

For return duct mounting, the humidistat should be 
mounted upstream from the humidifier or bypass so that 
it is properly sensing the relative humidity of the living 
space. Locate the control at least 8 in. (203 mm) 
upstream from the humidifier in the return air duct. (See 
Fig 2.)

Fig. 2. Selecting duct location for humidistat.

Locating Closest 120V Electrical Outlet

• Select location with access to an outlet. If not 

available, contact an electrician to have one installed.

• Make sure that the humidifier cord is adequate to 

reach from the humidifier to the outlet.

• Make sure that the 20 ft (6.2m) of thermostat wire is 

adequate to reach from the humidifier solenoid, to the 
sail switch, to the humidistat. 

Installing the Humidifier

WARNING

Hazardous Voltage 
Can cause personal injury or equipment 
damage.

Do not cut or drill into any air conditioning or 
electrical accessory.

CAUTION

Sharp Edges Installation Hazard.   
Can cause personal injury.

Wear gloves and safety glasses.

M12808B

HORIZONT

AL

DOWN

FLO

LOWBOY

RETURN

RETURN

RETURN

HIGHBOY

RETURN

ALTERNATE LOCATION 

RETURN  

AIR 

RETURN 

AIR 

6 in. (152 mm)  

MINIMUM 

15 in. (381 mm)  

MINIMUM 

BEST  

LOCATION 

RETURN AIR DUCT 

M12831A

69-1646E-01_A.fm  Page 2  Tuesday, June 9, 2009  1:13 PM

Содержание H8908

Страница 1: ... the installation Required Accessories Included Required Tools Tools required for installation include Tin snip Screwdriver Adjustable or open end wrench Drill punch or awl Level Determining Best Location for Humidifier CAUTION Temperature and Static Pressure Hazard Can cause property or equipment damage Locate humidifier where ambient temperature is between 32 F 0 C and 160 F 71 C Do not install ...

Страница 2: ...ail without affecting the smooth flow of air in the duct Airflow at the location can be vertical up or down or horizontal IMPORTANT Mounting the S688 in warm air supply duct can reduce the sail life Mount the switch at least 6 in 152 mm upstream from an elbow or junction and at least 15 in 381 mm downstream from an elbow or junction Locate the switch on the opposite side of the duct from the air e...

Страница 3: ...ing humidifier on duct 11 Reinstall the humidifier pad assembly in the humid ifier housing IMPORTANT Be sure to reconnect the water feed tube and ensure that the tube is not pinched or kinked 12 Hinge the cover in place and secure with the thumbscrew located at the bottom of the cover Connecting the Plumbing Use hot or cold water and either hard or softened water in the humidifier 1 Shut off the w...

Страница 4: ...tube to the humid ifier drain fitting and run to the floor drain see Fig 8 a Slide the drain clamp over the tubing b Push the tubing over the drain nipple on the humidifier c Hand tighten the clamp around the tubing to secure the humidifier drain d Fasten the drain tubing can use duct tape along the route to prevent movement and ensure downward slope for correct drainage NOTE Cut tubing to correct...

Страница 5: ... Off position the sail should point into the direction of airflow as shown in Fig 11 Fig 11 Inserting sail switch in direction of airflow 6 Secure the switch by using the sheet metal screws provided 7 After wiring snap on the cover Installing the Humidistat Installing on Mounting Duct 1 Apply the template to the duct location chosen for the humidistat Make sure the template is level before drillin...

Страница 6: ... white con ductors to the Com and NO sail switch terminals NC terminal is not used TESTING HUMIDIFIER OPERATION Checklist q Humidifier is level q Control wiring was reviewed using circuit diagram q Humidifier is plugged in q Feed line has no kinks q Drain line slopes continuously down and ends at floor drain q Water hose inside humidifier is connected to PerfectFlow water distribution tray After i...

Страница 7: ...t can accumulate moisture on your windows NOTE If these activities persist for more than a few hours set the humidity control to the lowest set ting to turn off the humidifier If the condition does not improve ventilate your home to remove the moisture MAINTAINING YOUR HUMIDIFIER A regular maintenance program prolongs the life of your humidifier and makes your home more comfortable The frequency o...

Страница 8: ... the water feed tube is placed in the guide slots 15 Replace the humidifier cover 16 Verify the humidifier operation by following the steps in the Checking Your Humidifier for Correct Operation section CHECKING YOUR HUMIDIFIER FOR CORRECT OPERATION After winter startup or servicing use the following steps to check your humidifier operation 1 Turn on the humidifier power and water supply 2 Turn the...

Страница 9: ...Verify plumbing connections Check for kinks Saddle valve Verify that needle pierces water line and then backs out needle to open valve Humidifier Remove cover and verify that water flows into distribution tray Drain tubing Verify no obstructions Low humidity Furnace blower not operating Reset circuit breaker or check for blown fuse Check that the furnace power is on Check all external wiring conne...

Страница 10: ...WELL SHALL NOT BE LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING DIRECTLY OR INDIRECTLY FROM ANY BREACH OF ANY WARRANTY EXPRESS OR IMPLIED OR ANY OTHER FAILURE OF THIS PRODUCT Some states do not allow the exclusion or limitation of incidental or consequential damages so this limitation may not apply to you THIS WARRANTY IS THE ONLY EXPRESS WAR...

Страница 11: ...HE360 HUMIDIFIER AND INSTALLATION KIT 11 69 1646EF 01 69 1646E 01_A fm Page 11 Tuesday June 9 2009 1 13 PM ...

Страница 12: ... U S A on recycled paper containing at least 10 post consumer paper fibers Automation and Control Solutions Honeywell Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 69 1646E 01_A fm Page 12 Tuesday June 9 2009 1 13 PM ...

Страница 13: ...HE360 et un humidistat H8908 de Honeywell ainsi que tous les accessoires nécessaires à l installation INSTALLATION Avant d installer ce produit Il est important d identifier tous les accessoires nécessaires fournis énumérés au Tableau 1 et d avoir sous la main les bons outils Accessoires nécessaires fournis Tableau 1 Accessoires nécessaires Outils nécessaires Les outils nécessaires à l installatio...

Страница 14: ...ficateur S il n y a pas de siphon à proximité il est préférable d installer l humidificateur central à tambour ou à disque de Honeywell S assurer que le tuyau de vidange de 3 1 m 10 pi est suffisamment long et permet de raccorder le tuyau de vidange de l humidificateur au siphon de sol Choix de l emplacement de l interrupteur à ailette Choisir un endroit dans la gaine de reprise d air froid où l i...

Страница 15: ...igneusement une ouverture rectangulaire 6 Démonter l humidificateur enlever le couvercle et retirer l ensemble écran évaporateur Voir la Fig 3 Fig 3 Démontage de l humidificateur 7 Placer les pinces de fixation comme l indique la Fig 4 Fig 4 Position des pinces de fixation 8 S assurer que le boîtier de l humidificateur est de niveau puis le placer de manière que les attaches de plastique soient su...

Страница 16: ...rémité du tuyau c Glisser l anneau de compression en plastique sur le tuyau Mettre de côté l anneau de com pression en cuivre fourni avec le robinet REMARQUE Pour empêcher les fuites avec des tuyaux en plastique utiliser des anneaux en plastique Delrin N utiliser des anneaux en cuivre qu avec des tuyaux en cuivre d Insérer le tuyau dans le raccord de l électro vanne et serrer l écrou de compressio...

Страница 17: ...p Enlever le support attaché au support marqué Down Courant d air horizontal Enlever les deux ressorts 1 Placer le gabarit fourni avec l interrupteur à ailette à l endroit choisi REMARQUE S assurer que la flèche indiquant le sens de la circulation de l air pointe dans la bonne direction a Dans le cas d un montage horizontal placer le long côté horizontalement à l aide d un niveau b Dans le cas d u...

Страница 18: ...ISE EN GARDE Risque de choc électrique Peut causer des blessures ou des dommages matériels Couper l alimentation électrique avant de faire l installation ou l entretien IMPORTANT Tout le câblage doit être conforme aux codes et règlements locaux Câbler l électrovanne de l humidificateur l interrupteur à ailette l humidistat et le transformateur Voir la Fig 13 Fig 13 Câblage des appareils 1 Passer l...

Страница 19: ...l appareil de chauffage passe sur l écran évaporateur de l humidificateur et capte l air humide pour le faire circuler dans la maison L air humidifié est plus chaud et il assure un meilleur confort Le point de consigne du thermostat peut donc être abaissé ce qui permet de diminuer les coûts de chauffage Avec un humidificateur la maison devient confortable et éconergétique Réglage de l humidificate...

Страница 20: ...e tuyau de vidange avec de l eau sous pression eau du robinet pour le nettoyer 11 Replacer le tuyau de vidange sur le raccord de vidange 12 Replacer le gicleur sur le plateau 13 S assurer que la partie marquée de l écran évapo rateur est orientée vers le haut Remettre le pla teau sur le cadre 14 Mettre l ensemble écran évaporateur d humidifica teur dans le boîtier de l humidificateur en appuyant j...

Страница 21: ...ectrovanne Tuyauterie Vérifier les raccords des tuyaux Vérifier si les tuyaux sont pincés Robinet vanne à étrier Vérifier si le pointeau perce la ligne d eau et revient en position pour ouvrir le robinet vanne Humidificateur Enlever le couvercle et vérifier si l eau s écoule dans le plateau de distribution Tuyau de vidange Vérifier s il y a blocage Faible humidité Le ventilateur de l appareil de c...

Страница 22: ...placer le produit conformément aux modalités susmentionnées HONEYWELL N ASSUME AUCUNE RESPONSABILITÉ POUR QUELQUE DOMMAGE INDIRECT QUE CE SOIT RÉSULTANT D UNE VIOLATION QUELCONQUE D UNE GARANTIE EXPRESSE OU TACITE APPLICABLE AU PRÉSENT PRODUIT Certains territoires et provinces ne permettent pas l exclusion ou la restriction des dommages indirects et par conséquent la présente restriction peut ne p...

Страница 23: ...HUMIDIFICATEURS HE360 ET TROUSSE D INSTALLATION 11 69 1646EF 01 69 1646F 01_A fm Page 11 Wednesday June 10 2009 2 22 PM ...

Страница 24: ...09 www honeywell com yourhome HUMIDIFICATEURS HE360 ET TROUSSE D INSTALLATION Solutions de régulation et d automatisation Honeywell Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 69 1646F 01_A fm Page 12 Wednesday June 10 2009 2 22 PM ...

Отзывы: