H7625A, H7635A HUMIDITY/TEMPERATURE SENSORS

5

62-0208—3

APPENDIX

RH Test and Configuration DIP Switch Settings (Table 4)

IMPORTANT

• Only adjust these switches for troubleshooting or
• recalibrating the sensor. (Adjustment is not 

normally necessary.)

• For normal operation, always keep DIP switch 3 

in the ON position. When DIP switch 3 is off, the 
RH transmitter cannot read the sensor. This 
inability-to-read forces the output to never 
change.

Table 4. Test and Calibration Settings (6-Switch Block).

0% RH Output (for Testing Only)

Transmitter always outputs a signal of 4 mA or 0 Vdc. The 
sensor does not affect the transmitter output.

50% RH Output (for Testing Only)

Transmitter always outputs a signal of 12 mA, 2.5 VDC, or 
5 VDC. The sensor does not affect the transmitter output.

100% RH Output

Transmitter always outputs a signal of 20 mA, 5 VDC, or 
10 VDC. The sensor does not affect the transmitter 
output. Sensor doesn’t affect the transmitter output.

Normal Operating Condition

DIP switch 3 must be set in the On position for normal 
operation. All other DIP switches must be set Off.

Setting

6

5

4

3

2

1

Normal Operation (Default)

— — — On — —

0%  RH  Output

On — — — — —

50%  RH  Output

— On — — — —

100% RH Output

— — On — — —

Increment RH Output

— — — — On —

Decrement  RH  Output

— — — — — On

Reset to Original Calibration

— — — — On On

Содержание H7625A

Страница 1: ...ician 4 After installation is complete check out product operation as provided in these instructions CAUTION Electrical Shock or Equipment Damage Hazard Can shock individuals or short equipment circuitry Disconnect power supply before installation CAUTION Equipment Damage Hazard Improper wiring can damage the sensor beyond repair Follow the wiring instructions carefully Location Install the device...

Страница 2: ...g shielded cable ground the shield only at the controller end see Fig 3 Grounding both ends can cause a ground loop NOTE See Table 2 for terminal designations Table 2 Terminal Designations Fig 3 Typical wiring diagram for transducer with two wire mA output with external DC power supply Controller Required Sensor Output Setting 4 Switch Block Settings Blueand White Output Switch LONSPEC Setting 4 3...

Страница 3: ...ISCHARGE AIR SENSOR OUTDOOR AIR SENSOR MOTION SENSOR HUMIDITY SENSOR M OS OS AS AS M HC HP HS Gnd Vin Vo 1 4 L1 HOT L2 COMPRESSOR CONTACTOR 1 COMPRESSOR CONTACTOR 2 HEAT RELAY 1 1 2 3 4 5 6 7 8 9 FAN RELAY ECONOMIZER HEAT RELAY 2 COMPRESSOR CONTACTOR 3 COMPRESSOR CONTACTOR 4 E GND OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 OUT 8 DI 1 DI 2 DI 3 DI 4 GND GND 24 VAC COM 24 VAC COM 24 VAC 24 VAC 24 VAC...

Страница 4: ...nverting Output Signal to Percent RH 4 to 20mA Signal Example 12 mA output signal 12 4 0 16 50 RH 0 to 10 Vdc Signal Example 8 VDC transmitter signal output 8 Vdc 0 10 80 RH Table 3 Troubleshooting signal in mA 4 0 16 percent RH Problem Items to Check No reading Verify correct supply voltage at the power terminal blocks Verify correct wiring configuration and DIP switch settings Verify that termin...

Страница 5: ...mitter always outputs a signal of 4 mA or 0 Vdc The sensor does not affect the transmitter output 50 RH Output for Testing Only Transmitter always outputs a signal of 12 mA 2 5 VDC or 5 VDC The sensor does not affect the transmitter output 100 RH Output Transmitter always outputs a signal of 20 mA 5 VDC or 10 VDC The sensor does not affect the transmitter output Sensor doesn t affect the transmitt...

Страница 6: ...that if your humidity has drifted 1 lower over a certain time period you will be able to toggle the Increment RH Output switch 2 times in order to slide the whole curve upward 1 Decrement RH Output This DIP switch allows calibration in the same way as the Increment RH The difference is that each toggle results in a decrease of 0 5 RH Using Calibration Trim Potentiometers IMPORTANT Due to the sensi...

Страница 7: ...H7625A H7635A HUMIDITY TEMPERATURE SENSORS 7 62 0208 3 ...

Страница 8: ...national Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2005 Honeywell International Inc 62 0208 3 B B Rev 01 05 LonSpec is a trademark of Echelon Corporation ...

Отзывы: