GATEWAY (GW-1000-WE/GW-1000-NWE)
® U.S. Registered Trademark
© 2020 Honeywell International Inc.
31-00424 | Rev.10-20
Honeywell Building Solutions
Honeywell
715 Peachtree Street NE
Atlanta, GA 30308
customer.honeywell.com
buildingcontrols.honeywell.com
Professional Installation
•
This device must be professionally installed, this
should be noted on grantee.
•
To maintain compliance, only the antenna types that
have been tested shall be used, which listed in “Remote
Antenna Part Numbers” on page 6. This device requires
a significant technology engineering expertise towards
understanding of the tools and relevant technology, not
readily available to average consumer. Only a person
professionally trained in the technology is competent.
•
This device is not directly marketed or sold to general
public.
Safety Information as per EN60730-1
The GW-1000-WE/GW-1000-NWE Gateway is intended
for residential, commercial, and light-industrial
environments.
The GW-1000-WE/GW-1000-NWE Gateway is an
independently mounted electronic control system with
fixed wiring.
The GW-1000-WE/GW-1000-NWE is suitable for
mounting in fuse boxes conforming with standard
DIN43880, and having a slot height of max. 45 mm.
It is suitable for panel rail mounting on 35 mm standard
panel rail (both horizontal and vertical rail mounting
possible).
The GW-1000-WE/GW-1000-NWE is used for the purpose
of building HVAC control and is suitable for use only in
non-safety controls for installation on or in appliances.
Table 12. Safety Information as per EN60730-1
Electric Shock
Protection
PELV
Pollution Degree
Pollution Degree 2, suitable for use
in industrial environments.
Installation
Class 3
Overvoltage
Category
24 V-powered controls: Category I
Rated Impulse
Voltage
330 Vac for Category I (SELV)
Automatic
Action
Type1.Y
Software Class
Class A
Enclosure
IP20 according to EN-60529
Ball-pressure
Test
Temperature
>75 °C for all housing and plastic
parts
>125 °C in the case of devices
applied with voltage-carrying parts,
connectors, and terminals.
Electromagnetic
Interference
Tested at 230 Vac, with the
modules in normal condition.
System
Transformer
Europe: safety isolating
transformers according to
IEC61558-2-6
U.S.A. and Canada: NEC Class-2
transformers
WEEE
WEEE Directive 2012/19/EC Waste
Electrical and Electronic Equipment
Directive
• At the end of the product life,
dispose of the packaging and
product in an appropriate recycling
center.
• Do not dispose of the device with
the usual domestic refuse.
• Do not burn the device.
Table 12. Safety Information as per EN60730-1