GSMX Installation and Setup Guide
– 17 –
PROMPTS
ENTRY
OPTIONS
DESCRIPTION
18
Supervi-
sion
(24
Hours)_
•
30 Day
•
24 Hour
•
None
The AlarmNet network must hear
at least one supervisory message
from the module during this
supervision period; otherwise,
AlarmNet notifies the central
station that a communication
failure has occurred. (If the
supervision period is changed
after registration, you must re-
register the module.)
Press the [space] key to scroll
through choices.
UL NOTE:
Must be 24 hour.
19
Old Alarm
Time
(10
Minutes)_
•
10
Minutes
•
15
Minutes
•
30
Minutes
•
1 Hour
•
2 Hours
•
4 Hours
•
8 Hours
•
12 Hours
•
24 Hours
The old alarm time sets how long
an undeliverable alarm is retried
for delivery to the central station.
If the message is not validated, it
is retried until the old alarm time
is reached or the message is
validated.
Press the [space] key to scroll
through choices.
UL NOTE:
Must be 10 minutes.
20
GSM Flt
Time
(00 mins)_
[01-99]
[00] = not
used
In the event the module detects a
communication path failure,
enter the time delay (in minutes)
before the module notifies the
control panel with a trouble
message. The control panel can
then notify the central station.
UL NOTE:
Must be one (01)
minute.