FIGURE 5. TYPICAL WIRING FOR SPEAKER SUPERVISION AND SWITCHING, NFPA STYLE Y:

(+)

(–)

(+)

(–)

(+)

(–)

(–)

(+)

(–)

(+)

(+)

(–)

AUDIO CIRCUIT

DO NOT LOOP WIRE AROUND TERMINALS 10 & 

11. BREAK WIRE TO ENSURE

SUPERVISION OF CONNECTIONS.

SIGNAL LINE CIRCUIT (SLC)

32 VDC MAX.

TWISTED PAIR

IS RECOMMENDED

ALL WIRING SHOWN IS SUPERVISED 

AND POWER LIMITED

WIRES MUST BE SUPERVISED PER NFPA

CONNECT MODULES TO LISTED 

COMPATIBLE  CONTROL PANELS ONLY

FROM 

PANEL OR 

PREVIOUS 

DEVICE

CONTROL 

MODULE

47K EOL

RESISTOR

ELR-47K

SPEAKERS MUST BE LISTED 

FOR FIRE PROTECTION. 

TO NEXT 

DEVICE

MODULE POLARITIES ARE 

SHOWN IN ALARM

TO NEXT CONTROL MODULE 

LAST MODULE MUST RETURN 

WIRES FOR SUPERVISION

SUPERVISION

AUDIO CIRCUIT WIRING MUST BE TWISTED PAIR AS A MINIMUM.

SEE INSTALLATION MANUAL FOR DETAILED INFORMATION.

AUDIO AMPLIFIER, 70.7 Vrms MAX.

USE ONLY MODELS AM-50, AM-50-70, AA100 

OR AA-120. AMPLIFIER MUST PROVIDE 

WIRING SUPERVISION PER NFPA.

*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.

C1016-01

FIGURE 6. TYPICAL FAULT TOLERANT WIRING FOR SPEAKER SUPERVISION AND SWITCHING, NFPA STYLE Z:

(+)

(–)

(+)

(–)

(+)

(–)

(+)

(–)

(–)

(+)

(–)

(+)

ALL WIRING SHOWN IS SUPERVISED 

AND POWER LIMITED

TO NEXT 

DEVICE

SIGNAL LINE CIRCUIT (SLC)

32 VDC MAX.

TWISTED PAIR

IS RECOMMENDED

WIRES MUST BE SUPERVISED PER NFPA

CONNECT MODULES TO LISTED 

COMPATIBLE CONTROL PANELS ONLY

FROM 

PANEL OR 

PREVIOUS 

DEVICE

CONTROL 

MODULE

SPEAKERS MUST BE LISTED 

FOR FIRE PROTECTION. 

47K EOL RESISTOR

IS INTERNAL AT 

TERMINALS 8 & 9

MODULE POLARITIES ARE 

SHOWN IN ALARM

TO NEXT CONTROL MODULE 

LAST MODULE MUST RETURN 

WIRES FOR SUPERVISION

SUPERVISION

AUDIO CIRCUIT WIRING MUST BE TWISTED PAIR AS A MINIMUM.

SEE YOUR PANEL’S SLC WIRING DOCUMENTATION FOR DETAILS.

AUDIO AMPLIFIER, 70.7 Vrms MAX.

USE ONLY MODELS AM-50, AM-50-70, AA100 

OR AA-120. AMPLIFIER MUST PROVIDE 

WIRING SUPERVISION PER NFPA.

AUDIO CIRCUIT

DO NOT LOOP WIRE AROUND TERMINALS 10 & 11. BREAK WIRE TO 

ENSURE SUPERVISION OF CONNECTIONS.

BYPASS CAPACITORS: 100µ

A2143-20 NONPOLARIZED

<10µA LEAKAGE

*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.

C1024-02

WARNING

All relay switch contacts are shipped in the standby state (open) state, but may have transferred to the activated (closed) state during shipping. To ensure that 
the switch contacts are in their correct state, modules must be made to communicate with the panel before connecting circuits controlled by the module.

  4 

I56-3550-008 

  