FIGURE 3. TYPICAL NOTIFICATION APPLIANCE CIRCUIT CONFIGURATION, NFPA STYLE Y:

(+)

(+)

(+)

(+)

(+)

(+)

47K EOL

RESISTOR

ELR-47K

UL LISTED EOL 

RELAY SHOWN 

ENERGIZED

24 VDC COIL 

EOLR-1

24 VDC CIRCUIT

DO NOT LOOP WIRE ON TERMINALS 10 & 11. BREAK WIRE 

RUN TO PROVIDE SUPERVISION OF CONNECTIONS.

TO NEXT CONTROL MODULE OR 

END-OF-LINE RELAY. ONE RELAY 

REQUIRED FOR EACH CIRCUIT. SOME 

CONTROL PANELS HAVE RELAY BUILT 

IN AND DO NOT REQUIRE EXTERNAL 

WIRING. REFER TO PANEL MANUAL.

24 VDC POWER SUPPLY

ISOLATED, REGULATED, POWER 

LIMITED PER NFPA 70. LISTED 

FOR FIRE PROTECTION WITH 

BATTERY BACKUP.

MODULE POLARITIES 

ARE SHOWN IN ALARM

CONNECT MODULES TO LISTED COMPATIBLE

CONTROL PANELS ONLY

SIGNAL LINE CIRCUIT (SLC)

32 VDC MAX.

TWISTED PAIR

IS RECOMMENDED

ALL WIRING SHOWN IS SUPERVISED 

AND POWER LIMITED

CONTROL 

MODULE

FROM 

PANEL OR 

PREVIOUS 

DEVICE

TO NEXT 

DEVICE

*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.

(–)

(–)

(–)

(–)

(–)

(–)

C1017-00

FIGURE 4. TYPICAL FAULT TOLERANT NOTIFICATION APPLIANCE CIRCUIT CONFIGURATION, NFPA STYLE Z:

(+)

(–)

(+)

(–)

(+)

(–)

(–)

(+)

(–)

(+)

(+)

(–)

ALL WIRING SHOWN IS 

SUPERVISED AND POWER LIMITED

MODULE POLARITIES 

ARE SHOWN IN ALARM

EOL 

RESISTOR IS 

INTERNAL AT 

TERMINALS

8 & 9 

UL LISTED EOL 

RELAY SHOWN 

ENERGIZED

24 VDC COIL 

EOLR-1

TO NEXT CONTROL MODULE OR 

END-OF-LINE RELAY. ONE RELAY 

REQUIRED FOR EACH CIRCUIT. SOME 

CONTROL PANELS HAVE RELAY BUILT 

IN AND DO NOT REQUIRE EXTERNAL 

WIRING. REFER TO PANEL MANUAL.

CONTROL 

MODULE

TO NEXT 

DEVICE

SIGNAL LINE CIRCUIT (SLC)

32 VDC MAX.

TWISTED PAIR

IS RECOMMENDED

CONNECT MODULES TO 

LISTED COMPATIBLE

CONTROL PANELS ONLY

FROM 

PANEL OR 

PREVIOUS 

DEVICE

24 VDC CIRCUIT

DO NOT LOOP WIRE ON TERMINALS 10 & 11. BREAK WIRE 

RUN TO PROVIDE SUPERVISION OF CONNECTIONS.

24 VDC POWER SUPPLY

ISOLATED, REGULATED, 

POWER LIMITED PER 

NFPA 70. LISTED FOR 

FIRE PROTECTION WITH 

BATTERY BACKUP.

*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.

C1018-00

  

I56-3550-008 

 

 06/19/2018