Test Lamps
Some manufacturers claim that their detectors do not need remote testing with an
external test lamp because it tests itself. Even though Honeywell Analytics detectors
also perform “through-the-window” self-testing, Honeywell Analytics, in compliance
with NFPA 72 codes, has developed portable test lamps for end-to-end remote
testing.
Internal detector testing and window cleanliness testing cannot ensure that a
detector is aimed properly, that its view of the threat area has not been blocked, or
that its alarming circuitry and outputs (i.e., relays, 4-to-20 mA, open collectors, etc.)
are operating properly. Remote test lamps can perform these functions.
Use test lamp model TL-1055 in non-hazardous locations only. For hazardous
locations, use model TL-2055 as described below.
WARNING
!
Test lamp TL-1055
Model TL-1055 is a general purpose NEMA 1 handheld rechargeable test lamp
designed for testing FSX detectors in non-hazardous locations only. The test lamp
(see
) is supplied with a universal charger (110 VAC and 220 VAC).
Figure 3. TL-1055 handheld test lamp (NEMA 1)
In normal operation, an FS20X detector will alarm to a fully charged TL-1055 test
lamp at a distance of 1 to 25 feet. This complies with NFPA 72 codes.