FocusPRO
TM
TH5110 / TH50
System test
System status
Shaded areas below apply only to
TH5220D
.
Press
s
/
t
to turn system on/off.
Press NEXT to advance to next test.
Press DONE to terminate system test.
Test number
System status
10
0
To begin, press and hold the
s
and
t
buttons until the display changes
Installer setup
Setup function
Settings & options (factory default in bold)
Shaded areas below apply only to
TH5220D
.
CAUTION:
Compressor protection is bypassed during testing. To prevent equipment
damage, avoid cycling the compressor quickly
!
10
Heating system
0
Heat and fan turn off.
1
Stage 1 heat turns on. Fan turns on if Setup Function 1 is set to 1
or 5 OR Setup Function 3 is set to 1 **See page 6
2
Stage 2 heat turns on
20
Emergency heating
system
0
Heat and fan turn off
1
Heat and fan turn on
2
Stage 2 heat turns on (auxiliary heat)
30
Cooling system
0
Compressor and fan turn off
1
Compressor and fan turn on
2
Stage 2 compressor turns on
40
Fan system
0
Fan turns off
1
Fan turns on
9
Stage 1 compressor
cycle rate (CPH)
3
Recommended for most compressors
[Other cycle rate options: 1, 2, 4, 5 or 6 CPH]
10
Stage 2 compressor
cycle rate (CPH)
3
Recommended for most compressors
[Other cycle rate options: 1, 2, 4, 5 or 6 CPH]
12
Manual/Auto
changeover
0
Manual changeover (Heat/Cool/Off)
1
Auto changeover (Heat/Cool/Auto/Off)
2
Auto changeover only (Auto)
14
Temperature
display
0
Fahrenheit
1
Celsius
15
Compressor
protection
5
Five-minute compressor off time
[Other options: 0, 1, 2, 3 or 4-minute off time]
26
Auxiliary heat control
0
Comfort **See page 8
1
Economy
27
Heat temperature
range stops
90 Max. heat temperature setting is 90 °F (32 °C)
[Other options: 40 °F to 89 °F (4.5 °C to 31.5 °C)]
28
Cool temperature
range stops
50 Min. cool temperature setting is 50 °F (10 °C)
[Other options: 51 °F to 99 °F (10.5 °C to 37 °C)]
Installer system test
OBSOLETE