background image

FocusPRO

TM 

TH5110 / TH50 

System test 

System status

Shaded areas below apply only to

 TH5220D

.

Press 

to turn system on/off. 

Press NEXT to advance to next test. 

Press DONE to terminate system test.

Test number

System status

10

0

To begin, press and hold the 

and 

 

buttons until the display changes

Installer setup

Setup function 

Settings & options (factory default in bold)

Shaded areas below apply only to

 TH5220D

.

CAUTION: 

Compressor protection is bypassed during testing. To prevent equipment 

damage, avoid cycling the compressor quickly

!

 

10

  Heating system

Heat and fan turn off.

Stage 1 heat turns on. Fan turns on if Setup Function 1 is set to 1 

or 5 OR Setup Function 3 is set to 1 **See page 6 

Stage 2 heat turns on

 

20

  Emergency heating  

system

Heat and fan turn off

Heat and fan turn on

Stage 2 heat turns on (auxiliary heat)

 

30

  Cooling system

Compressor and fan turn off

Compressor and fan turn on

Stage 2 compressor turns on

 

40

  Fan system

Fan turns off

Fan turns on

 

9

  Stage 1 compressor 

cycle rate (CPH)

Recommended for most compressors 

[Other cycle rate options: 1, 2, 4, 5 or 6 CPH]

 

10

  Stage 2 compressor 

cycle rate (CPH)

Recommended for most compressors 

[Other cycle rate options: 1, 2, 4, 5 or 6 CPH]

 

12

  Manual/Auto 

changeover

Manual changeover (Heat/Cool/Off)

Auto changeover (Heat/Cool/Auto/Off)

Auto changeover only (Auto) 

 

14

  Temperature 

display

Fahrenheit

Celsius

 

15

  Compressor 

protection

Five-minute compressor off time 

[Other options: 0, 1, 2, 3 or 4-minute off time]

 

26

  Auxiliary heat control

Comfort **See page 8

Economy

 

27

  Heat temperature  

range stops

90  Max. heat temperature setting is 90 °F (32 °C) 

[Other options: 40 °F to 89 °F (4.5 °C to 31.5 °C)]

 

28

  Cool temperature  

range stops

50  Min. cool temperature setting is 50 °F (10 °C) 

[Other options: 51 °F to 99 °F (10.5 °C to 37 °C)]

Installer system test

OBSOLETE

Содержание FocusPRO TH5110D

Страница 1: ...sistance with this product please visit http yourhome honeywell com or call Honeywell Customer Care toll free at 1 800 468 1502 69 1922EF This manual covers the following models TH5110D For 1 Heat 1 Cool systems TH5220D For up to 2 Heat 2 Cool systems Remove battery holder to find model number System Types Gas oil or electric heat with air conditioning Warm air hot water high efficiency furnaces h...

Страница 2: ...ipment damage Disconnect power before beginning installation MERCURY NOTICE If this product is replacing a control that contains mercury in a sealed tube do not place the old control in the trash Contact your local waste management authority for instructions regarding recycling and proper disposal Pull here to remove wallplate from new thermostat Remove battery holder It s easier to grasp the wall...

Страница 3: ...r systems use common wire from cooling transformer Heat Pump Terminals Rc 24VAC power from cooling transformer R 24VAC power from heating transformer O B Changeover valve Y Compressor contactor G Fan relay Aux Auxiliary heat relay E Emergency heat relay L Sends output when set to Em Heat C 24VAC common Wiring Terminal designations Shaded areas below apply only to TH5220D TH5110D Rc Y W G R C TH511...

Страница 4: ...y Heat only System with Fan Rc Power 1 R R Rc joined by jumper C 24VAC common 3 W Heat relay G Fan relay Cool only System Rc Power 1 R R Rc joined by jumper Y Compressor contactor C 24VAC common 3 G Fan relay 2H 2C System 1 transformer 6 Rc Power 1 R R Rc joined by jumper Y Compressor contactor stage 1 C 24VAC common 3 W Heat relay stage 1 G Fan relay W2 Heat relay stage 2 Y2 Compressor contactor ...

Страница 5: ...Pump System Rc Power 1 R R Rc joined by jumper Y Compressor contactor C 24VAC common 3 O B Changeover valve 7 G Fan relay 2H 1C Heat Pump System 8 Rc Power 1 R R Rc joined by jumper Y Compressor contactor C 24VAC common 3 O B Changeover valve 7 G Fan relay Aux Auxiliary heat relay 10 E Emergency heat relay 10 L Sends output when set to Em Heat 9 See notes on page 4 Rc Y G R C Rc Y G Aux E L R C Rc...

Страница 6: ...aux heat 6 2 heat 2 cool conventional 7 2 heat 1 cool conventional 8 1 heat 2 cool conventional 2 Changeover valve O B terminal 0 Changeover valve O B terminal energized in cooling 1 Changeover valve O B terminal energized in heating 3 Fan control heating 0 Gas or oil furnace equipment controls fan in heating 1 Electric furnace thermostat controls fan in heating 5 Stage 1 heat cycle rate CPH cycle...

Страница 7: ...rns on auxiliary heat 30 Cooling system 0 Compressor and fan turn off 1 Compressor and fan turn on 2 Stage 2 compressor turns on 40 Fan system 0 Fan turns off 1 Fan turns on 9 Stage 1 compressor cycle rate CPH 3 Recommended for most compressors Other cycle rate options 1 2 4 5 or 6 CPH 10 Stage 2 compressor cycle rate CPH 3 Recommended for most compressors Other cycle rate options 1 2 4 5 or 6 CPH...

Страница 8: ...ries replacement parts Please contact your distributor to order replacement parts Part Description Part Number Use With Battery holder 50000951 001 TH5110D Battery holder 50007072 001 TH5220D Cover plate assembly 50001137 001 TH5110D Cover plate assembly 50002883 001 TH5220D TH5110D 12 pack of small cover plates 50007297 001 TH5110D 12 pack of medium cover plates 50007298 001 TH5220D TH5110D Use t...

Страница 9: ...s frais au Centre de service à la clientèle de Honeywell au 1 800 468 1502 69 1922EF Ce guide couvre les modèles suivants TH5110D Pour 1 système de chauffage et 1 système de climatisation TH5220D Pour 2 systèmes de chauffage et 2 systèmes de climatisation Enlever le porte pile pour trouver le numéro de modèle Types de système Chauffage au gaz naturel au mazout ou à l électricité avec climatiseur F...

Страница 10: ...t de commencer l installation REMARQUE À PROPOS DU MERCURE Si ce produit sert à remplacer une commande qui contient du mercure dans un tube scellé ne pas jeter la vieille commande aux ordures Consulter l administration locale de gestion des déchets pour connaître les instructions relatives au recyclage et à l élimination Tirer ici pour enlever la plaque murale du thermostat neuf Retirer le porte p...

Страница 11: ...2 transformateurs utiliser le neutre pour le transformateur de climatisation Bornes de thermopompe Rc Alimentation de 24 V CA pour le transformateur de climatisation R Alimentation de 24 V CA pour le transformateur de chauffage O B Robinet de substitution Y Contacteur de compresseur G Relais de la soufflante Aux Relais auxiliaire de chauffage E Relais de chauffage d urgence L Envoie le signal de s...

Страница 12: ...limatisation 1 2 R Alimentation transformateur de chauffage 1 2 Y Contacteur de compresseur C Neutre 24 V CA 3 4 W Relais de chauffage G Relais de la soufflante Système de chauffage seulement avec soufflante Rc Alimentation 1 R R Rc reliés par le cavalier C Neutre 24 V CA 3 W Relais de chauffage G Relais de la soufflante Système de climatisation seulement Rc Alimentation 1 R R Rc reliés par le cav...

Страница 13: ...1C Rc Alimentation 1 R R Rc reliés par le cavalier Y Contacteur de compresseur C Neutre 24 V CA 3 O B Robinet de substitution 7 G Relais de la soufflante Système de thermopompe 2C 1C 8 Rc Alimentation 1 R R Rc reliés par le cavalier Y Contacteur de compresseur C Neutre 24 V CA 3 O B Robinet de substitution 7 G Relais de la soufflante Aux Relais auxiliaire de chauffage 10 E Relais de chauffage d ur...

Страница 14: ... 2 cool conventional 7 Traditionnel 2 chauffage 1 climatisation 2 heat 1 cool conventional 8 Traditionnel 1 chauffage 2 climatisations 1 heat 2 cool conventional 2 Robinet de substitution Borne O B 0 Robinet de substitution Changeover valve borne O B activée lors de la climatisation 1 Robinet de substitution Changeover valve borne O B activée lors du chauffage 3 Commande de soufflante chauffage 0 ...

Страница 15: ...u chauffage de stade 2 chauffage auxiliaire 30 Système de climatisation 0 Arrêter le chauffage et la soufflante 1 Mise en fonction du compresseur et de la soufflante 2 Activation du compresseur de stade 2 40 Système de soufflante 0 Désactivation de la soufflante 1 Activation de la soufflante 9 Rythme de cycle de compresseur de stade 1 CPH 3 Recommandé pour la plupart des compresseurs Autres option...

Страница 16: ...es de rechange Prière de communiquer avec le distributeur pour commander des pièces de remplacement Description des pièces N de pièce Pour Porte pile 50000951 001 TH5110D Porte pile 50007072 001 TH5220D Assemblage de couvercle 50001137 001 TH5110D Assemblage de couvercle 50002883 001 TH5220D TH5110D Paquet de 12 petites plaques de couvercle 50007297 001 TH5110D Paquet de 12 plaques de couvercle 50...

Отзывы: