Honeywell Fire-Lite ECC-RPU Скачать руководство пользователя страница 3

ECC-RPU Installation Document —

 P/N LS10030-000FL-E:B  8/9/2013

3

4 LED Indicators

OK to Page  

A green LED that turns on steady to 

instruct the operator that he/she may start paging.

Mic Trouble  

A yellow LED that turns on steady to 

indicate a microphone wiring fault.

Power  

A green LED that turns on steady when DC 

power is present.

Data Bus Fault  

A yellow LED turns on steady when 

the main console and RPU cannot communicate.

Audio Riser Fault  

A yellow LED that turns on steady 

when the audio riser wiring is open or short-circuited.

Board Fault  

A yellow LED that turns on steady when a 

critical issue has been detected with the board.  There are 
no serviceable parts. Contact service personnel to replace 
the unit.

5 Slide-in Label

Carefully cut along the outside of the label. Identify 
keypad buttons as desired and slide the label upwards 
through the slot at the bottom of the keypad.

+-

B
A
B

A

B
A

B

A

+

-

+

-

+

-

+

-

+

-

1
2
3
4

5

1
2
3

4
5

1

2
3

4
5

ECC main 

control board

RPU board

TB24

TB12

TB22

external operator interface 

power - 24VDC

external 

data bus

external 

audio 

riser

Figure 6  Remote Page Unit Wiring