One Fire-Lite Place
Northford, CT 06472-1653 USA
203-484-7161 • FAX 203-484-7118
www.firelite.com  

ECC-RPU Remote Page Unit 

Product Installation Document

PN LS10030-000FL-E:B   8/9/2013   13-696

1 Overview

The ECC-RPU is an optional Remote Page Unit 
compatible with the ECC-50/100 Emergency Command 
Center. The ECC-RPU provides 8 message select buttons.  
The 9th button can be used to activate an MMF-300 
monitor module mounted inside the cabinet.  The RPU 
requires an external data bus connection, an external audio 
riser connection, and an external operator interface power 
connection (24 volts DC) from the ECC-50/100 main 
console. ALL CALL paging can be broadcast over the 
speaker circuits by depressing the microphone's push-to-
talk switch.  Refer to the ECC-50/100  Manual, LS10001-
000FL-E, for more information.     

NOTE:

Installation and wiring of this device must be 

done in accordance with NFPA 72 and local ordinances.

2 Installation

2.1  Removing the Dress Panel

1. Open the door and lift the door off the pin hinges.
2. Loosen the screw securing the dress panel to the 

backbox.

3. Open dress panel and disconnect the ground wire 

from the back.

4. Lift up dress panel and pull out lower pivot flange. 

Slide the upper pivot flange down to completely 
remove the dress panel from cabinet.  Store in a safe 
location.

 

2.2  Mounting the Backbox

1. Mark and predrill holes for the top two backbox 

keyhole mounting bolts using the dimensions shown.

2. Install two upper fasteners in the wall with the screw 

heads protruding.

3. Using the upper 'keyholes', mount the backbox over 

the two screws.

4. Mark and drill the lower two holes.
5. Install the remaining fasteners and tighten all 

fasteners to complete backbox mounting.

6. Carefully reinstall the dress panel by reversing the 

steps in Section 2.1.  Remember to reattach the 
ground cable.

7. Reinstall door.

A trim ring, TR-6-R, is available for semi-flush mount 
installations.

Figure 1  ECC-RPU

 screw 

location

Figure 2  Removing the Dress Panel

1. lift up

2. pull out

3. slide down

keyholes

10.0” (25.4cm) O.C.

lower mounting holes

Figure 3  Backbox Mounting