BEFORE INSTALLING

This information is included as a quick reference installation guide. Refer to 

the  appropriate  Fire•Lite  control  panel  installation  manual  for  detailed  sys

-

tem information. If the modules will be installed in an existing operational 

system, inform the operator and local authority that the system will be tempo

-

rarily out of service. Disconnect the power to the control panel before install

-

ing  the  modules.  This  system  contains  static  sensitive  components.  Always 
ground yourself with a proper wrist strap before handling any circuits so that 
static charges are removed from the body. The module housing should also 

be grounded.

F200-22-00 

I56-1900-005 

SPECIFICATIONS

Normal Operating Voltage: 

15-32 VDC

Stand-By Current: 

2 mA

Alarm Current: 

40 mA (assumes all six LEDs solid on)

Temperature Range: 

32°F to 120°F (0°C to 49°C)

Humidity: 

10 to 93% Non-condensing

Dimensions: 

6.8˝H x 5.8˝W x 1.25˝D

Accessories: 

CH-6 Chassis; BB-6 Cabinet; BB-2 Cabinet

Wire Gauge: 

12-18 AWG

Maximum IDC Wiring Resistance: 

25 Ohms

External Power Supply Voltage: 

Regulated 24VDC

Ripple Voltage: 

0.1 volts RMS maximum

IDC (supervised and power limited)
     DC Voltage: 

18-28 volts power limited

     Frequency: 

DC

     Current: 

90mA per circuit

MMF-302-6 Six Zone Interface Module 

  DET.  

 

          DETECTOR  

 MODEL 

COMP. ID 

MANUFACTURER 

BASE MODEL 

MAX DET.

  1151 

SYSTEM SENSOR 

B110LP,B401 

20

  1451 

SYSTEM SENSOR 

B401, B401B 

20

 1451DH 

SYSTEM SENSOR 

DH400 

20

  2151 

SYSTEM SENSOR 

B110LP, B401 

20

  2451 

SYSTEM SENSOR 

DH400, B401B,B401 

20

 2451TH 

SYSTEM SENSOR 

B401, B401B 

20

  5451 

SYSTEM SENSOR 

B401 

20

  1100 

SYSTEM SENSOR 

N/A 

20

  1400 

SYSTEM SENSOR 

N/A 

20

**  2100AT 

SYSTEM SENSOR 

N/A 

20

  2100B 

SYSTEM SENSOR 

N/A 

20

  2100D 

SYSTEM SENSOR 

N/A 

20

  2100S 

SYSTEM SENSOR 

N/A 

20

 2100TB 

SYSTEM SENSOR 

N/A 

20

 2100TD 

SYSTEM SENSOR 

N/A 

20

 2100TS 

SYSTEM SENSOR 

N/A 

20

  2300B 

SYSTEM SENSOR 

N/A 

20

 2300TB 

SYSTEM SENSOR 

N/A 

20

  2400 

SYSTEM SENSOR 

N/A 

20

 2400TH 

SYSTEM SENSOR 

N/A 

20

* 2W-B 

SYSTEM SENSOR 

N/A 

20

* 2W-TB 

SYSTEM SENSOR 

N/A 

20

 DH100LP 

SYSTEM SENSOR 

N/A 

20

* Class B, Style B Only
** No Accessory will be supported by 2100AT

COMPATIBLE TwO-wIRE SySTEM SENSOR SMOkE DETECTORS FOR uSE wITh MMF-302-6 wITh ZONE A IDENTIFIER

GENERAL DESCRIPTION

The MMF-302-6 Six Zone Interface Module is intended for use in an intelli-

gent alarm system. Each module provides an interface between the intelligent 
alarm system and a conventional alarm system loop. A common SLC input is 
used for all modules, and the initiating device loops share a common super

-

visory supply and ground. Otherwise, each monitor operates independently 
from the others. Each module has its own unique address.

A pair of rotary code switches is used to set the address of the first module 
from 01 to 154. The remaining modules are automatically assigned to the next 
five higher addresses. Provisions are included for disabling a maximum of two 
unused  modules  to  release  the  addresses  to  be  used  elsewhere.  Each  mod

-

ule also has panel controlled bicolor LED indicators. The panel can cause the 
LEDs to blink, latch on, or latch off.

I56-1900-00

5

INSTALLATION AND MAINTENANCE INSTRuCTIONS

One FireLite Place

Northford, CT 06472

Phone: 203.484.7161 

NOTICE: This manual should be left with the owner/user of the equipment.

firealarmresources.com

Содержание Fire-Lite Alarms MMF-302-6

Страница 1: ...451 A SYSTEM SENSOR B401 20 1100 A SYSTEM SENSOR N A 20 1400 A SYSTEM SENSOR N A 20 2100AT A SYSTEM SENSOR N A 20 2100B A SYSTEM SENSOR N A 20 2100D A SYSTEM SENSOR N A 20 2100S A SYSTEM SENSOR N A 20 2100TB A SYSTEM SENSOR N A 20 2100TD A SYSTEM SENSOR N A 20 2100TS A SYSTEM SENSOR N A 20 2300B A SYSTEM SENSOR N A 20 2300TB A SYSTEM SENSOR N A 20 2400 A SYSTEM SENSOR N A 20 2400TH A SYSTEM SENSOR...

Страница 2: ...The BB 2 cabinet houses one or two MMF 302 6 modules on the internal chas sis that is part of the cabinet Refer to cabinet installation documents for dimensions C0235 00 INSTALLATION STEPS 1 Cabinet Mounting In a clean dry area mount the backbox using the four holes provided in the back surface of the cabinet Figure 3 2 Chassis Installation The CH 6 chassis is mounted in the BB 6 cabinet It is att...

Страница 3: ... All external power supplies and detectors must be UL listed for fire protection signaling applications PROGRAMMING The MMF 302 6 module operates with the following Fire Alarm Control Pan els MS 9200 MS 9600 The modules are programmed as devices in each system according to the pro gramming instructions in the appropriate FACP manual F200 22 00 3 I56 1900 005 The steps in Figures 6a and 6b describe...

Страница 4: ...ove the two shunts from the A B select positions 2 To use a common power supply between multiple MMF 302 6 modules connect a long power supply jumper from T5 or T6 to T5 or T6 on the adjacent MMF 302 6 module 0 1 2 3 4 5 6 7 8 9 BASE ADDRESS TO NEXT DEVICE STATUS INDICATORS IN OUT 0 1 2 3 4 5 IDC ADDRESS IDC ADDRESS IDC ADDRESS SLC FROM PANEL OR PREVIOUS DEVICE CONNECT MODULES TO LISTED COMPATIBLE...

Страница 5: ...his equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential in stallation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harm...

Отзывы: