Honeywell Fire-Lite Alarms D350RPL Скачать руководство пользователя страница 3

[3] Secure The Detector Housing To The Duct

Slide the foam gaskets over the tube bushings as shown in Figure 3. Use the two 1

1

4

˝ long sheet metal screws to screw the detector 

housing to the duct. 

CAUTION:

 Do not overtighten the screws.

Figure 3. Installation of foam gaskets
over sampling tube bushings:

SCREW HOLES FOR

ATTACHING HOUSING

TO DUCT WORK.

[4] Sampling Tube Installation for Ducts Greater Than 1

1

2

 Feet (0.46m) Wide

The sampling tube is identified by a series of air inlet holes on the tube. A plastic tube is included for ducts up to 1

1

2

 feet (0.46m) 

wide. All other lengths must be purchased separately. Order the correct length, as specified in Table 1, for width of the duct where it 
will be installed. It is recommended that the sampling tube length extend at least 

2

/

3

 across the duct width for optimal performance. 

The exhaust tube is molded onto the base of the duct housing, and the A2440-00 Exhaust Tube Extension is available as an accessory 
in those cases where the molded exhaust port does not extend at least 2 inches (50mm) into the duct. 
The  sampling  tube  is  always  installed  with  the  air  inlet  holes 
facing  into  the  air  flow.  To  assist  proper  installation,  the  tube’s 
mounting  flange  is  marked  with  an  arrow.  Make  sure  the  sam-
pling tube is mounted so that the arrow points into the air flow 
(see Figure 4). Figure 5 shows the various combinations of tube 
mounting  configurations  with  respect  to  air  flow.  Mounting  the 
detector housing in a vertical orientation is acceptable, provided 
that a metal sampling tube is used and the air flows directly into 
the sampling tube holes as indicated in Figure 4.

[4.1] Installation For Ducts Greater Than 1

1

2

 Feet 

(0.46m) But Less Than 8 Feet (2.4m) Wide

1.  If the tube is longer than the width of the air duct, drill a 

3

4

˝ 

(19mm) hole in the duct opposite the hole already cut for the 
sampling  tube.  Make  sure  the  hole  is  1˝  to  2˝  (25  to  50mm) 
below  the  sampling  hole  on  the  opposite  side  of  the  duct  to 
allow moisture drainage away from the detector. If the tube is 
shorter than the width of the air duct, install the end cap into 
the sampling tube as shown in Figure 4. Sampling tubes over 
3 ft. (0.91m) long must be supported at the end opposite the 
duct smoke detector.

2.  Slide the tube into the housing bushing that meets the air flow 

first.  Position  the  tube  so  that  the  arrow  points  into  the  air 
flow, as shown in Figure 4. 

3.  Secure the tube flange to the housing bushing with two #6 self-

tapping screws.

4.  For  tubes  longer  than  the  width  of  the  air  duct,  the  tube 

should extend out of the opposite side of the duct. If there are 
more than 2 holes in the section of the tube extending out of 
the  duct,  select  a  different  length  using  Table  1.  Otherwise, 
trim the end of the tube protruding through the duct so that 1˝ 
to 2˝ (25 to 50mm) of the tube extend outside the duct. Plug 
this  end  with  the  end  cap  and  tape  closed  any  holes  in  the 
protruding section of the tube. Be sure to seal the duct where 
the tube protrudes.

NOTE:

 The sampling tube end cap is critical to the proper opera-

tion of the duct smoke detectors. The end cap is needed to create 
the proper air flow to the sensor of the duct smoke detector.

F300-28-00 

I56-1974-006R

*Must extend a minimum of 

2

3

 the duct width

H0107-00

Outside Duct Width

Sampling Tube Recommended*

1 to 2 ft. (0.3 to 0.6 m)

ST-1.5

2 to 4 ft. (0.6 to 1.2 m)

ST-3

4 to 8 ft. (1.2 to 2.4 m)

ST-5

8 to 12 ft. (2.4 to 3.7 m)

ST-10

Table 1. Sampling tubes recommended for different 
Duct Widths:

H0108-02

Figure 5. Tube mounting configurations with varying 
air flow direction:

AIR FLOW

DIRECTION

DETECTOR

HOUSING

DOTS INDICATE POSITION OF SAMPLING TUBE HOLES

AIR FLOW

DIRECTION

DETECTOR

HOUSING

SAMPLING

TUBE

EXHAUST

TUBE

AIR FLOW

DIRECTION

EXHAUST

TUBE

SAMPLING

TUBE

SAMPLING

TUBE

EXHAUST

TUBE

DETECTOR

HOUSING

AIR FLOW

DIRECTION

DETECTOR

HOUSING

A.

B.

C.

D.

HORIZONTAL MOUNTING OF HOUSING

VERTICAL MOUNTING OF HOUSING

NOTE: ONLY METAL SAMPLING TUBES CAN BE INSTALLED IN ORIENTATIONS C AND D.

NOTE:

 Only metal sampling tubes can be installed 

in orientations C and D.

H0109-01

SAMPLING

TUBE

END CAP

AIR HOLES

ARROW

MUST FACE

INTO AIR FLOW

AIR FLOW DIRECTION

FLANGE

Figure 4. Air duct detector sampling tube:

Содержание Fire-Lite Alarms D350RPL

Страница 1: ...m control panel to provide a local alarm indication There is also a remote alarm output for use with auxiliary devices The D350RPL has remote test capability with the RTS451 RTS451KEY Remote Test Station The D350RPL incorporates a cover tamper feature When the cover is removed for more than 20 minutes the unit loses communication at the panel a trouble is indicated at the panel and the alarm relay...

Страница 2: ...but less than 8 feet 2 4m wide 3 Step 4 2 Installation for ducts more than 8 feet 2 4m wide 4 Step 5 Install the filters 4 Step 6 Field wiring 4 Step 7 Perform detector check 5 Step 8 Install the cover 5 Step 9 Detector Maintenance and Test Procedures 5 1 Verify Duct Air Flow Direction And Velocity The D350RPL duct smoke detector is designed to be used in air handling systems having air velocities...

Страница 3: ...rom the detector If the tube is shorter than the width of the air duct install the end cap into the sampling tube as shown in Figure 4 Sampling tubes over 3 ft 0 91m long must be supported at the end opposite the duct smoke detector 2 Slide the tube into the housing bushing that meets the air flow first Position the tube so that the arrow points into the air flow as shown in Figure 4 3 Secure the ...

Страница 4: ...4 25 to 32mm hole where the flange will be used 5 Install The Filters To install the sampling tube filters simply push the filters into the sampling and exhaust tube holes as shown in Figure 6 If a metal sampling tube is used install the filters over the tube end 6 Field Wiring Installation Guidelines All wiring must be installed in compliance with the National Electrical Code and the local codes ...

Страница 5: ...water and no more than 1 2 inches of water Because most commercially available manometers cannot accurately measure very low pressure differentials applications with less than 500 FPM of duct air speed may require one of the following 1 the use of a current sourcing pressure transmitter Dwyer Series 607 per Section 9 1 4 or 2 the use of aerosol smoke per section 9 1 2 9 1 2 Air Flow Test using Aer...

Страница 6: ...to verify correct operation of the system Remove the detector board to cause a trouble condition locally and at the system control panel Figure 8 Procedure for verifying air flow F300 28 00 6 I56 1974 006R HIGH LOW 9 VOLT BATTERY 9 VOLT BATTERY 9 VOLT BATTERY TO SAMPLING TUBE TO EXHAUST TUBE DIFFERENTIAL PRESSURE TRANSMITTER MODEL 607 01 15 TO 36 VDC SUPPLY 1000 OHM 5 1 WATT RESISTOR VOLT METER FL...

Страница 7: ...be out of service Disable the device or system undergoing maintenance to prevent unwanted alarms and possible dispatch of the fire department 9 3 Maintenance of Duct Smoke Detectors 9 3 1 Air Filters 1 Turn off power to the system 2 Remove and inspect sampling tube filters 3 If filters are heavily coated with dirt replace them with new filters p n F36 09 11 If they are not heavily coated use a vac...

Страница 8: ...ver there is no guarantee that interfer ence will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation be...