Honeywell Fire-Lite Alarms D350RPL Скачать руководство пользователя страница 2

F300-28-00 

I56-1974-006R

WARNING

LIMITATIONS OF DUCT DETECTORS

 

WARNING

The National Fire Protection Association has established that DUCT DETECTORS MUST NOT BE USED AS A SUBSTITUTE FOR OPEN 
AREA DETECTOR PROTECTION as a means of providing life safety. Nor are they a substitute for early warning in a building’s regular 
fire detection system.

It is strongly recommended that the user read NFPA Standards 90A, 72, and 101.

This device will not operate without electrical power. Fire situations may cause an interruption of power. The system safeguards should 
be discussed with your local fire protection specialist.

This device will not sense smoke unless the ventilation system is operating.

In order to function properly, this detector must be installed according to the instructions. Do not exceed the electrical or ambient 
specifications or the detector will not function properly. This detector must be protected from the elements.

INSTALLATION SEQUENCE

Step 1. 

Verify duct air flow direction and velocity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Step 2. 

Drill the mounting holes  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Step 2.1   Install the sampling tube for ducts less than 1

1

2

 feet (0.46m) wide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Step 3. 

Secure the detector housing to the duct . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Step 4. 

Install the sampling tube for ducts greater than 1

1

2

 feet (0.46m) wide   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Step 4.1  Installation for ducts greater than 1

1

2

 feet (0.46m) but less than 8 feet (2.4m) wide  . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Step 4.2  Installation for ducts more than 8 feet (2.4m) wide  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Step 5. 

Install the filters  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Step 6. 

Field wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Step 7. 

Perform detector check  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Step 8. 

Install the cover  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Step 9. 

Detector Maintenance and Test Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

[1] Verify Duct Air Flow Direction And Velocity

The D350RPL duct smoke detector is designed to be used in air handling systems having air velocities of 100 to 4000 feet per minute 
(0.5 to 20.32 m/s). Be sure to check engineering specifications to ensure that the air velocity in the duct falls within these parameters. 
If necessary, use a velocity meter to check the air velocity in the duct. See Air Flow Test, section 9.1.

[2] Drill The Mounting Holes

Remove the paper backing from the mounting template supplied. Affix the template to the duct at the desired mounting location. Make 
sure the template lies flat and smooth on the duct. Center punch holes A and B. Drill the holes as indicated on the template. 

[2.1] Sampling Tube Installation for Ducts Less Than 1

1⁄2

 Feet (0.46m) Wide (see Figure 2)

1.  Remove the front cover.
2.  Slide the plastic sampling tube into the housing bushing.
3.  Align the holes in the bushing with the holes in the sampling tube. Make sure there are 6 exposed holes on the plastic sampling 

tube. Secure with the #8 self-tapping screw into the bottom of the permanent tube (shown in Figure 2).

Figure 2. Plastic sampling tube connected to duct smoke detector:

 

 

 

 

 

 

 

NOTE:

  For  ducts  greater  than  1

1

2

  feet  (0.46m)  in  width,  refer  to 

 

 

 

 

 

 

 

sections [4], [4.1] and [4.2].

H0110-00

Содержание Fire-Lite Alarms D350RPL

Страница 1: ...m control panel to provide a local alarm indication There is also a remote alarm output for use with auxiliary devices The D350RPL has remote test capability with the RTS451 RTS451KEY Remote Test Station The D350RPL incorporates a cover tamper feature When the cover is removed for more than 20 minutes the unit loses communication at the panel a trouble is indicated at the panel and the alarm relay...

Страница 2: ...but less than 8 feet 2 4m wide 3 Step 4 2 Installation for ducts more than 8 feet 2 4m wide 4 Step 5 Install the filters 4 Step 6 Field wiring 4 Step 7 Perform detector check 5 Step 8 Install the cover 5 Step 9 Detector Maintenance and Test Procedures 5 1 Verify Duct Air Flow Direction And Velocity The D350RPL duct smoke detector is designed to be used in air handling systems having air velocities...

Страница 3: ...rom the detector If the tube is shorter than the width of the air duct install the end cap into the sampling tube as shown in Figure 4 Sampling tubes over 3 ft 0 91m long must be supported at the end opposite the duct smoke detector 2 Slide the tube into the housing bushing that meets the air flow first Position the tube so that the arrow points into the air flow as shown in Figure 4 3 Secure the ...

Страница 4: ...4 25 to 32mm hole where the flange will be used 5 Install The Filters To install the sampling tube filters simply push the filters into the sampling and exhaust tube holes as shown in Figure 6 If a metal sampling tube is used install the filters over the tube end 6 Field Wiring Installation Guidelines All wiring must be installed in compliance with the National Electrical Code and the local codes ...

Страница 5: ...water and no more than 1 2 inches of water Because most commercially available manometers cannot accurately measure very low pressure differentials applications with less than 500 FPM of duct air speed may require one of the following 1 the use of a current sourcing pressure transmitter Dwyer Series 607 per Section 9 1 4 or 2 the use of aerosol smoke per section 9 1 2 9 1 2 Air Flow Test using Aer...

Страница 6: ...to verify correct operation of the system Remove the detector board to cause a trouble condition locally and at the system control panel Figure 8 Procedure for verifying air flow F300 28 00 6 I56 1974 006R HIGH LOW 9 VOLT BATTERY 9 VOLT BATTERY 9 VOLT BATTERY TO SAMPLING TUBE TO EXHAUST TUBE DIFFERENTIAL PRESSURE TRANSMITTER MODEL 607 01 15 TO 36 VDC SUPPLY 1000 OHM 5 1 WATT RESISTOR VOLT METER FL...

Страница 7: ...be out of service Disable the device or system undergoing maintenance to prevent unwanted alarms and possible dispatch of the fire department 9 3 Maintenance of Duct Smoke Detectors 9 3 1 Air Filters 1 Turn off power to the system 2 Remove and inspect sampling tube filters 3 If filters are heavily coated with dirt replace them with new filters p n F36 09 11 If they are not heavily coated use a vac...

Страница 8: ...ver there is no guarantee that interfer ence will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation be...

Отзывы: