Step 2: 

 Carefully swing the bottom edge of the board towards the back of 

the board until it touches the short standoff attached to the chassis.

Step 3: 

 Align the long standoff with the short standoff and tighten.

FIGURE 6B. INSTALLATION OF CRF-300-6 MOdULE IN FRONT 
ChASSIS POSITION:

2

1

3

Step 1: 

 Insert the bottom edge of the CRF-300-6 module down into a front 

slot of the chassis.

Step 2:    Carefully swing the upper edge of the board towards the back of 

the chassis until it touches the 11/4″ (31.75mm) standoffs installed 

on the rear module.

Step 3:    Align two 4-40 screws with the two standoffs and tighten.

Step 4:    Address and wire the modules according to the instructions in this 

manual.

WIRING

NOTE:  All  wiring  must  conform  to  applicable  local  codes,  ordinances,  and 

regulations.
1.   Install module wiring in accordance with the job drawings and appropri-

ate wiring diagrams.  

2.   Make electrical connections by stripping approximately 1/4˝ (6.35mm) 

of insulation from the end of the wire sliding the bare end of the wire 

under the clamping plate, and tightening the clamping plate screw.

3.   Set the address on the modules per the job drawing. Use the rotary code 

switches to set the address of the first module (between 01 and 154). The 
remaining  modules  are  automatically  assigned  to  the  next  five  higher 
addresses. For example, if the base address switch is set to 28, the next 
five modules will be addressed to 29, 30, 31, 32, and 33. DO NOT set 
the lowest address above 154, as the other modules will be assigned to 

nonexistent addresses. 

NOTE: Some panels support extended addressing. In order to set the module 
above address 99 on compatible systems, carefully remove the stop on the up

-

per rotary switch. If the panel does not support extended addressing, do not 
set the lowest address above 94.
4.    A  shunt  is  provided  to  disable  a  maximum  of  three  unused  modules. 

Modules are disabled from the highest address and work downward. If 
two modules are disabled, the lowest four addresses will be functional, 
while the highest two will be disabled. For example, if the shunt for Ad

-

dress Disable is placed on “two” and the base address switch is set to 28, 
the modules will be assigned to 28, 29, 30 and 31.

NOTE: Power must not be applied to the unit when changing functionality of 

the shunts.

F300-19-00 

I56-1875-006

3. Module Installation

There are two methods for installing a module in the rear position of a chas-

sis. Method one is for installation of a rear module only, when no module will 
be installed in front of it. Refer to Figure 5 for instructions. Method two is for 

installation  of  a  rear  module  when  another  module  will  be  installed  in  the 

chassis position in front of it.  Refer to Figures 6a and 6b for method two. All 
necessary screws and standoffs are supplied with the modules.

FIGURE 5. INSTALLATION OF REAR MOdULE ONLY, METhOd ONE:

2

1

3

Step 1: 

 Insert the bottom of the CRF-300-6 module down into a rear slot on 

the chassis. 

Step 2: 

 Carefully swing the upper edge of the board back towards the back 

of the chassis until it touches the two standoffs.

Step 3: 

 Align two 4-40 screws with the two standoffs and tighten.

Step 4: 

 Address and wire the modules according to the instructions in this 

manual.

The  steps  in  Figures  6a  and  6b  describe  and  illustrate  module  installation 
when the rear chassis position and the position in front of it will be filled.  

Front position installation is possible only if the rear position is filled with a 

module.

FIGURE 6A. INSTALLATION OF CRF-300-6 MOdULE IN A REAR 
ChASSIS POSITION, METhOd TWO:

1

Step 1: 

 Insert the bottom edge of the CRF-300-6 module down into a rear 

slot of the chassis.

C0243-00

C0245-00

C0244-00

firealarmresources.com

Содержание Fire-Lite Alarms CRF-300-6

Страница 1: ...arm Current 32 mA assumes all six relays have been switched once and all six LEDs solid on Temperature Range 32 F to 120 F 0 C to 49 C Humidity 10 to 93 Non condensing Dimensions 6 8 H 5 8 W 1 0 D Accessories CH 6 Chassis BB 6 Cabinet BB 2 Cabinet Wire Gauge 12 18 AWG Relay Current 30 mA Relay Pulse 15 6 mS pulse duration pulse under panel control CRF 300 6 Six Relay Control Module Contents includ...

Страница 2: ...les wide and two modules deep Figure 1 CH 6 Chassis The BB 2 cabinet has a built in chassis that will accommodate one or two CRF 300 6 modules Figure 2 BB 2 Cabinet 0 1 2 3 4 5 6 7 8 9 0 7 8 6 5 4 3 2 1 9 10 11 12 13 14 15 BASE ADDRESS ADDRESS DISABLE NONE ONE TWO THREE 0 1 2 3 4 5 6 7 8 9 0 7 8 6 5 4 3 2 1 9 10 11 12 13 14 15 BASE ADDRESS ADDRESS DISABLE NONE ONE TWO THREE The front CRF 300 6 mod...

Страница 3: ...d addressing do not set the lowest address above 94 4 A shunt is provided to disable a maximum of three unused modules Modules are disabled from the highest address and work downward If two modules are disabled the lowest four addresses will be functional while the highest two will be disabled For example if the shunt for Ad dress Disable is placed on two and the base address switch is set to 28 t...

Страница 4: ...f the NEC For easier wiring assign all power limited wiring to one side rather than alternating with non power limited PROGRAMMING The CRF 300 6 module operates with the following Fire Alarm Control Panels MS 9200 MS 9600 0 1 2 3 4 5 6 7 8 9 0 7 8 6 5 4 3 2 1 9 10 11 12 13 14 15 N C N O COMMON ADDRESS 5 N C N O COMMON ADDRESS 4 N C N O COMMON ADDRESS 3 N C N O COMMON ADDRESS 2 N C N O COMMON ADDRE...

Отзывы: