F300-19-00
1
I56-1875-006
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to
the appropriate Fire•Lite control panel installation manual for detailed sys
-
tem information. If the modules will be installed in an existing operational
system, inform the operator and local authority that the system will be tempo
-
rarily out of service. Disconnect the power to the control panel before install
-
ing the modules. This system contains static sensitive components. Always
ground yourself with a proper wrist strap before handling any circuits so that
static charges are removed from the body. The module housing should also
be grounded.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The CRF-300-6 Six Relay Control Module is intended for use in an intelligent
alarm system. Each module is intended for Form-C switching applications,
which do not require wiring supervision for the load circuit. A single isolated
set of dry relay contacts is provided for each module, which is capable of
being wired for either normally open or normally closed for each operation.
Each module has its own address. A pair of rotary code switches is used to set
the address of the first module from 01 to 154. The remaining modules are au-
tomatically assigned to the next five higher addresses. Provisions are included
for disabling a maximum of three unused modules to release the addresses to
be used elsewhere. Each CRF-300-6 module also has panel controlled green
LED indicators. The panel can cause the LEDs to blink, latch on, or latch off.
SPECIFICATIONS
Normal Operating Voltage:
15-32 VDC
Stand-By Current:
1.45 mA
Alarm Current:
32 mA (assumes all six relays have been switched once and all six LEDs solid on)
Temperature Range:
32°F to 120°F (0°C to 49°C)
Humidity:
10 to 93% Non-condensing
Dimensions:
6.8˝H × 5.8˝W × 1.0˝D
Accessories:
CH-6 Chassis; BB-6 Cabinet; BB-2 Cabinet
Wire Gauge:
12-18 AWG
Relay Current:
30 mA/Relay Pulse (15.6 mS pulse duration) pulse under panel control
CRF-300-6 Six Relay Control Module
Contents include:
(6) 1 × 3 Terminal Blocks
(1) 1 × 4 Terminal Blocks
(2) 11/4˝ Stand offs
(4) Machine Screws
(1) Shunt (NOTE: For the disable position, not more than one shunt shall be
installed at the same time)
(2) Nuts
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compat
-
ible Fire•Lite system control panel (list available from Fire•Lite).
COMPONENTS
Following are descriptions of the CRF-300-6 mounting frameworks. There are
two mounting options for CRF-300-6 modules:
Up to six CRF-300-6 modules can be installed on a CH-6 in a BB-6
•
cabinet
One or two CRF-300-6 modules can be installed in a BB-2 cabinet
•
WARNING
All relay switch contacts are shipped in the standby state (open) state, but
may have transferred to the activated (closed) state during shipping. To en
-
sure that the switch contacts are in their correct state, modules must be made
to communicate with the panel before connecting circuits controlled by the
module.
CURRENT RATING
MAXIMUM VOLTAGE
LOAD DESCRIPTION
APPLICATION
3 A
30 VDC
Resistive
Non-coded
2 A
30 VDC
Resistive
Coded
.9 A
110 VDC
Resistive
Non-coded
.9 A
125 VDC
Resistive
Non-coded
.5 A
30 VDC
Inductive (L/R=5ms)
Coded
1 A
30 VDC
Inductive (L/R=2ms)
Coded
.3 A
125 VAC
Inductive (PF=.35)
Non-coded
1.5 A
25 VAC
Inductive (PF = .35)
Non-coded
.7 A
70.7 VAC
Inductive (PF=.35)
Non-coded
2 A
25 VAC
Inductive (PF=.35)
Non-coded
I56-1875-006
INSTALLATION ANd MAINTENANCE INSTRUCTIONS