Model TC844A1007 Filtrex

 Intelligent Photoelectronic Sensor

Installation Instructions

Before installing sensors, please thoroughly read the

 Guide for Proper Use of System Smoke Detectors

, which provides detailed infor-

mation on sensor spacing, placement, zoning, and special applications. Copies of this guide are available from Honeywell.
NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: This sensor must be tested and maintained regularly following NFPA 72 requirements. It should be cleaned at least once 
a year.
GENERAL DESCRIPTION
Filtrex® uses a small air intake fan and a high density replaceable filter. Air and smoke are drawn into a photoelectric sensing cham-
ber while airborne particulate and water mist are removed. The addressable-analog detector transmits an analog representation of 
smoke density over a communication line to a control panel. Rotary-decade switches are provided for setting the sensor’s address. 
Two LEDs on the sensor are controlled by the panel to indicate sensor status.

The Filtrex smoke detector is intended for use in normal environmental conditions, where dust and other airborne particulate are pres-
ent at elevated levels. These elevated levels tend to cause false alarms and high maintenance in standard detectors. Filtrex provides 
a protective enclosure for a photoelectric smoke detector chamber and allows smoke detection in areas where heat detection was the 
only practical alternative for fire sensing.
Filtrex requires compatible addressable communications to function properly. Connect this detector to listed-compatible control panels 
only.

SPECIFICATIONS

 

Operating Voltage Range: 

15 to  32 VDC

Detector Current: 

230 

µ

A @ 24 VDC (without communication)

 

 

285 

µ

A @ 24 VDC (one communication every 5 sec. with LED enabled)

Auxiliary Power Supply Voltage: 

15 to 30 VDC filtered; Ripple voltage may not drop below 15 volts.

Auxiliary Power Supply Current – 
 

Peak: 

123 mA max.

 

Average: 

27 mA max.

Operating Humidity Range:  

10% to 93% Relative Humidity, noncondensing

Operating Temperature Range: 

0° to 50°C (32° to 122°F)

Height:    

2.8 inches (43 mm)

Diameter: 

6.1 inches (155 mm) installed in 14507371-008

 

 

4.0 inches (102 mm) installed in SSDB524FTXE

Weight:     

7.3 oz. (207 g)                                  

Mounting Base: 

Requires 14507371-008 (U.S.), SSDB524FTXE (Europe)

H400-22-00 

I56-1326-006R

Honeywell, 1985 Douglas Drive North, Golden Valley MN 55422

 

 

 

 

 

LISTED COMPATIBLE CONTROL PANEL

AUX.

POWER

SUPPLY

+

+

AUX

+

AUX

AUX

+

AUX

2(–) 3(R

A) 4(S)

1(+)

1(+)

2(–) 3(R

A) 4(S

)

Figure 1. Wiring diagram:

C0121-00

Содержание Filtrex TC844A1007

Страница 1: ...rborne particulate are pres ent at elevated levels These elevated levels tend to cause false alarms and high maintenance in standard detectors Filtrex provides a protective enclosure for a photoelectric smoke detector chamber and allows smoke detection in areas where heat detection was the only practical alternative for fire sensing Filtrex requires compatible addressable communications to functio...

Страница 2: ...ectronically simulates smoke in the sensing cham ber testing the detector electronics and connections to the control panel 1 Hold the test magnet in the magnet test area as shown in Figure 3 2 The detector should alarm the panel Two LEDs on the detector are controlled by the panel to indicate sensor status Coded signals transmitted from the panel can cause the LEDs to blink latch on or latch off R...

Страница 3: ...f Filtrex while replacing the filter If a clogged filter was the cause of the trouble condition nor mal detector operation should resume automatically within five minutes If the trouble condition persists the detector must be returned for repair or replacement Installing Filtrex into Base 1 Align the detector at a right angle to the base with the five wires and connector adjacent to the connector ...

Страница 4: ...e and install the XLS1000 FireAlarm Control Panel with a 3 AADC Analog Addressable Device Controller as described in form no 95 7545 XLS1000 Installation and Service Manual When configuring the database using the SDU use the TC806 Photoelectric Smoke Detector parameters for setting up the TC844A1007 Filtrex Intelligent Photo Smoke Sensor The TC844A1007 responds to the XLS1000 panel the same as a T...

Отзывы: