FIGURE 11. FF-SRE6029 TROUBLESHOOTING FLOW DIAGRAM 
 

 

Machine Down

Yes

Apply correct voltage AND/

OR check for correct

operation of previous

connected safety device.

Replace the

safety module.

Yes

Are K1 AND

 

K2

LEDs ON?

No

No

Yes

The problem
is external to

the module.

Check for

external

causes

(wiring, etc.).

Damaged

contacts.  Ensure

maximum load is

specification.

Replace module.

Are the

outputs contacts

13/14, ..., 43/44

closed?

Are K1 AND K2

LEDs OFF?

Are the contacts

51/52 AND Y1/Y2

closed ?

Replace safety

module and

activate restart

circuitry.

Is

voltage between

A1/A2 AND A3/A4 present

AND within

specifications?

Yes

Machine
Working

Is the problem

resolved?

No

Yes

Yes

No

No

No

within

 

 

 

FSR

E

6029_14 

 

8

  

 

 

 

 

 

 

 

 

 

107137-20 -EN  FR26  GLO  305  Printed in Germany

 

Содержание FF-SRE6029

Страница 1: ...masterelectronics com onlinecomponents com are authorized e commerce distributors of electronic components See full Datasheet below BUY NOW BUY NOW HONEYWELL FF SRE60292 ...

Страница 2: ...PROVALS CE The product packaging and documentation of FF SR Series products carry the CE mark the CE declaration of conformity is attached on the last page cURus pending This product is currently being assessed by Underwriters Laboratories Inc according to Canadian and U S safety requirements DIRECTIVE COMPLIANCE Machinery Directive 98 37 EC Low Voltage Directive 73 23 EC Electromagnetic Compatibi...

Страница 3: ...e 15 C to 55 C 5 F to 131 F at 90 humidity max Sealing Housing IP 40 Terminals IP 20 Housing material Thermoplastic Vibration resistance IEC EN 60 068 2 6 Amplitude 0 35 mm Frequency 10 to 55 Hz Wire connection Solid wire 1 x 4 mm 2 12 AWG or 2 x 2 5 mm 2 14 AWG Stranded wire with sleeve 1 x 2 5 mm 2 14 AWG or 2 x 1 5 mm 2 16 AWG Wire conductor attachment M3 5 screw terminals Mounting Quick instal...

Страница 4: ...oval FIGURE 4 MOUNTING DIMENSIONS for reference only Rail c b a a Width 22 5 mm 0 89 in b Height 90 mm 3 55 in c Depth 121 mm 4 77 in FIGURE 5 INSTALLATION DIAGRAM FSR1 FSRE5929 6 CONTROL RELIABILITY Control Reliability essentially means that the device system or interface shall be designed constructed and interfaced such that any single component failure within the device interface or system shal...

Страница 5: ...the machine control circuitry by the module s safety contacts to stop the hazard and remove power As soon as the safety device is released power is applied to A1 A2 A3 A4 and the relays K1 and K2 energise The normally open contacts will close and the normally closed contact will open Both relays K1 and K2 must be energized to have the normally open contacts in a closed condition If one of the safe...

Страница 6: ...t the FF SRE6029 extension module to safety devices WITHOUT the EDM function e g FF SYA FF SG FF SLG or FF SLG30 The External Device Monitoring EDM function checks the correct operation of the internal relays before each FF SRE6029 activation and is able to detect failures of the internal relays e g welded safety relay contacts ALWAYS connect the normally closed contact Y1 Y2 of the extension modu...

Страница 7: ... The normally open contacts will close and the normally closed contacts will open The LED relay output indicators all illuminate This action will allow the machine to operate FSRE6029_12 APPLICATION NOTES Note A Dual channel output safety devices with relay outputs or safety switches examples This may be a safety device with dual output safety switching devices OSSD emergency stop push button safe...

Страница 8: ...acts of the FF SRE6029 module will close and the normally closed contacts will open The LED relay output indicators K1 and K2 illuminate This action will allow the machine to operate FSRE6029_13 APPLICATION NOTES Note A Dual channel output safety devices with static safety outputs AND External Device Monitoring EDM function e g FF SYB safety light curtains Note B CONFIGURATION CARDS Various mode s...

Страница 9: ...heck for external causes wiring etc Damaged contacts Ensure maximum load is specification Replace module Are the outputs contacts 13 14 43 44 closed Are K1 AND K2 LEDs OFF Are the contacts 51 52 AND Y1 Y2 closed Replace safety module and activate restart circuitry Is voltage between A1 A2 AND A3 A4 present AND within specifications Yes Machine Working Is the problem resolved No Yes Yes No No No wi...

Страница 10: ...nd through our literature and the Honeywell Website it is up to the customer to determine the suitability of the product in the application Specifications may change at any time without notice The information we supply is believed to be accurate and reliable as of this printing However we assume no responsibility for its use TELEPHONE 61 0 2 9370 4500 Australia 33 0 1 60 19 80 40 France 49 0 69 80...

Отзывы: