SPECIFICATIONS
Input
Nominal voltage
24 Vdc (-10 %, +10 %)
Nominal consumption
dc: 1,5 W
Output
Contacts
4 NO, 1 NC (plus 1 NC for External Device Monitoring loop)
Contact type
Safety relay, positive-guided
Response time
Max. 15 ms (delay on de-energisation)
Delay on energisation
Typ. 25 ms
Switching Capability
Power factor = 1 with resistive load
Current Range (min. to max.)
10 mA to 5 A
Voltage Range (min. to max.)
0,1 to 250 Vac
Switching capability per
EN 60947-5-1
AC15: NO contact: 3 A/230 Vac, NC contact: 2 A/250 Vac
DC13: NO contact, NC contact: 8 A / 24 Vdc
Power factor = 1 at 230 Vac (see figure 1, note 1)
current
operations
current
operations
0,5 A
5 500 000
2 A
1 000 000
Typical Electrical Life Expectancy
1 A
2 000 000
5 A
250 000
Limitation Factor F (see figure 2, note 2)
cos
ϕ
F
cos
ϕ
F
0,3
0,45
0,7
0,85
Typical Power Factor (cos
ϕ
)
0,5
0,7
1
1
Operating frequency
1200 operating cycles/h
Fuse rating
6 A time delayed (max.)
Mechanical life
20 000 000 operating cycles
General
Temperature range
-15
°
C to + 55
°
C (5
°
F to 131
°
F) at 90 % humidity (max.)
Sealing
Housing IP 40; Terminals IP 20
Housing material
Thermoplastic
Vibration resistance
(IEC/EN 60 068-2-6)
Amplitude 0,35 mm; Frequency 10 to 55 Hz
Wire connection
Solid wire: 1 x 4 mm
2
[12 AWG] or 2 x 2,5 mm
2
[14 AWG]
Stranded wire with sleeve: 1 x 2,5 mm
2
[14 AWG] or 2 x 1,5 mm
2
[16 AWG]
Wire/conductor attachment
M3.5 screw terminals
Mounting
Quick install rail mounting IEC/EN 60715 (width: 35 mm (1.38 in))
Weight
205 g (0.45 lb)
NOTE 1:
Install arc suppressors
across load to avoid module contact
arcing and ensure specified contact life
expectancy.
NOTE 2:
Total operations = operations
(power factor 1) x limitation factor F.
Example:
U = 230 Vac, I = 1 A,
power factor cos
ϕ
= 0,5
Switching power P = U x I = 230 VA
Contact life (cos
ϕ
= 1, P = 230 VA) =
2 000 000 operations (see Figure 1)
Limitation factor F (cos
ϕ
= 0,5) = 0,7
(see Figure 2)
Contact life (cos
ϕ
= 0,5, P = 230 VA) =
F x contact life (cos
ϕ
= , P= 230 VA) =
2 000 000 x 0,7 = 1 400 000 operations.
FIGURE 1. TYPICAL CONTACT
LIFE FOR 100 % RESISTIVE LOAD
(power factor cos
ϕ
= 1, note 1)
10
7
5
3
2
7
7
0,5
1,0
1,5
2,0
5
Oper
ations
Switching power [kVA]
3
2
7
10
6
10
5
FIGURE 2. LIMITATION FACTOR FOR
INDUCTIVE LOADS
(power factor cos
ϕ
< 1, note 2)
Limitation factor F
Power factor