F200E CHARGED-MEDIA AIR CLEANER

68-0238

3

Applications With Air Conditioning

Mount the media air cleaner upstream of the evaporator coil
in a cooling system. The filter will help to keep the coil clean
and reduce maintenance.

Applications With A Humidifier

The media air cleaner is compatible with humidifiers. Avoid
applications where water mist will reach the media. If an
atomizing humidifier is used, the filter media will require
replacement more often because of minerals in the water.

Choose Mounting Position

The media air cleaner can be mounted in any position, but
the arrow on the cartridge must point in the same direction as
the airflow. See Figs. 3-10 for proper location of the media air
cleaner for a variety of furnace installations. Note that the
media air cleaner cabinet is sturdy enough to easily support
the weight of the furnace and evaporator coil. See Fig. 4.

Fig. 3. Highboy furnace, with side installation.

Media air filter is mounted vertically where return

enters side inlet of furnace.

Media Replacement :
Replace the filter at least annually or when the built-in
pressure sensors in the F200E door detect that airflow is
impaired and the filter requires cleaning. This condition
causes the indicator light on the F200E door t begin flashing
and the transmitter to send a signal to the wall-mounted RF
Indicator that the filter needs replacing.

After replacing the filter, press the reset button on the F200E
door to reset both the door indicator light and the RF
AIRWATCH Air Cleaner Indicator. (See Table 1 for
AIRWATCH operation.)

Fig. 2. Capacity, Pressure Drop and Area of

F100F Filter Media.

PLANNING THE INSTALLATION

Location

The media air cleaner should be installed where all the air
passing through the system is circulated through it. The best
location is in the return air duct next to the blower compartment
so the media air cleaner can help to keep the blower motor and
evaporator coils clean. Do not mount in the supply air duct.

For most efficient air cleaning, spread airflow evenly across
the face of the media. If the duct is a different size than the
media air filter cabinet, gradual transitions are required. If
the duct turns sharply just before the air filter, turning vanes
are required.

Choose a location that is readily accessible for checking and
replacing the filter. Allow at least 26 in. (660 mm) clearance in
front of the unit for removal of the cartridge.

Install the media air filter where the temperature will not
exceed the ratings in the Specifications.

Fig. 4. Highboy furnace, with installation beneath

furnace. Media air cleaner is mounted horizontally where

return enters from below.

0

500

1000

1500

2000

0.000

0.050

0.100

0.150

0.200

0.250

0.300

16 X 20

16 X 25
20 X 20

20 X 25

FILTER SIZE

PRESSURE DROP (IN. WC)

AIRFLOW (CFM)

M14785

WHEN FIRST INSTALLED. PRESSURE DROP INCREASES AS FILTER
BECOMES LOADED. REPLACE FILTER WHEN PRESSURE DROP
REACHES 0.5 IN. WC. (0.1 kPa). 

1

1

M14786

M14787

Filter Size (in.)

Part Number

16 x 25

FC200E1029

16 x 20

FC200E1003

20 x 25

FC200E1037

20 x 20

FC200E1011

Содержание F200E

Страница 1: ...reased pressure drop threshold at filter Filter change status is transmitted to wall mounted AIRWATCH Indicator The RF AIRWATCH Indicator is included SPECIFICATIONS IMPORTANT The specifications in this publication do not include normal manufacturing tolerances therefore an individual unit may not exactly match the listed specifications This product is tested and calibrated under closely controlled...

Страница 2: ...ated for greater media capacity Filter Element Underwriters Laboratories Inc UL 900 Class 2 Listed Capacity And Pressure Drop See Fig 2 Initial Pressure Drop 0 177 in wc at 492 fpm Temperature Rating 40 to 140 F 40 to 60 C Dimensions See Fig 1 Fig 1 Installation dimensions in in mm of air cleaner Mounting Mounts in any position in the return air duct usually next to the furnace blower compartment ...

Страница 3: ...ton on the F200E door to reset both the door indicator light and the RF AIRWATCH Air Cleaner Indicator See Table 1 for AIRWATCH operation Fig 2 Capacity Pressure Drop and Area of F100F Filter Media PLANNING THE INSTALLATION Location The media air cleaner should be installed where all the air passing through the system is circulated through it The best location is in the return air duct next to the...

Страница 4: ...ing in closet door Fig 6 Lowboy furnace with media air cleaner mounted horizontally in return plenum just above furnace and opposite heating plenum Fig 7 Counterflow furnace with media air cleaner mounted horizontally in return duct or plenum just above furnace M941A Fig 8 Central fan installation with media air cleaner mounted horizontally in central return duct M14788 M14789 M14790 ...

Страница 5: ... of expansion on each side of a transition fitting Turning Vanes If the media air cleaner is installed next to an elbow or angle fitting add turning vanes inside the angle to distribute airflow more evenly across the face of the media See Fig 12 Offsets If the duct connection to the furnace in a side installation allows less than 7 in 178 mm for mounting media air cleaner cabinet attach an offset ...

Страница 6: ...ll them whenever an abrupt 90 degree elbow is installed directly against the media air cleaner cabinet Fasten Cabinet To Ductwork Fasten side of cabinet to the ductwork using sheet metal screws rivets or slip joints as appropriate Connect Ductwork Connect the vertical duct section to the elbow If the vertical drop of the duct is less than 7 in 178 mm from the side of the furnace shorten the horizo...

Страница 7: ... again at step 2 Mount AIRWATCH Indicator 1 Remove the AIRWATCH Indicator from the base a Depress the tab on the bottom edge of the base b Pull off the bottom of the front cover 2 Position the base on the wall in the desired mounting position using the holes in the base as a template mark the locations for the anchors and screws provided Also mark location of round hole in center of base when usin...

Страница 8: ...e 1 AIRWATCH Indicator LCD Description AIRWATCH Indicator Condition Meaning Action No indicator on AIRWATCH has no power replace battery On Battery indicator on continuously AIRWATCH is functioning normally On Battery indicator flashing Flashing two seconds on six seconds off Replace battery in the F200E door Do not press any reset buttons after battery change Flashing two seconds on two seconds o...

Отзывы: