Honeywell F114 Скачать руководство пользователя страница 2

F114 AND F115 CEILING SURFACE MOUNTED MEDIA AIR CLEANERS

68-0201-2  Revised 11-07

2

ORDERING INFORMATION

If you have additional questions, need further information, or would like to comment on our products or services, please write
or phone:

1.

Your local Honeywell Commercial Air Products Distributor.

2.

Air-Pure Systems

16873 Fish Point Rd. SE
Prior Lake, MN  55372-1714
Phone: (800) 998-1919
Fax: (800) 221-3248

www.cleanairfacility.com

SPECIFICATIONS

IMPORTANT

The specifications given in this publication do not
include normal manufacturing tolerances. Therefore,
this unit may not exactly match the listed
specifications. This product is tested and calibrated
under closely controlled conditions, and some minor
differences in performance can be expected if those
conditions are changed.

Models:

Refer to Table 1 for model descriptions.

Color:

F114: white cabinet and cover.
F115: white cabinet and cover.

Blower/Motor:

F114: two-speed, direct-drive, forward curve.
F115: single-speed, direct-drive, forward curve.

Table 1. F114 and F115 Description.

Efficiency

Model

Voltage

Particulates at 0.3

Micron (D.O.P. Test)

Approximate CPZ™

components in pounds

Air Volume in cfm

(m3/hr)

F114A

120 Vac, 60 Hz, 1PHS, 3.6A

99.97% HEPA

N/A

HI = 325 (550);

LOW = 180 (306)

220-240 Vac, 60 Hz, 1PHS, 1.7A

99.97% HEPA

NA

HI = 325 (550)

LOW = 180 (306)

F114C

120 Vac, 60 Hz, 1PHS, 3.6A

95%

7

HI = 350 (595);

LOW = 200 (340)

220-240 Vac, 50/60 Hz, 1PHS, 1.7A

95%

7

HI = 320 (544);

LOW = 165 (280)

F115A

120 Vac, 60 Hz, 1PHS, 7.2A

99.97% HEPA

N/A

600 (1020)

220/240 Vac, 60 Hz, 1PHS, 8.6A

99.97% HEPA

N/A

600 (1020)

F115C

120 Vac, 60 Hz, 1PHS, 7.2A

95%

12

600 (1020)

220/240 Vac, 50/60 Hz, 1PHS, 3.6A

95%

12

550 to 600   

(935 to 1020)

a

Not applicable.

Содержание F114

Страница 1: ...ed in any situation that requires the reduction of contamination from an enclosed area FEATURES High Efficiency Particulate AIR HEPA filter models are 99 97 efficient and the D O P particle filter models are 95 efficient at 0 3 micron particles Both models are more efficient on particles smaller and larger F114 two speed direct drive forward curve motor blower models deliver up to 325 cfm 550 m3 h...

Страница 2: ...s in performance can be expected if those conditions are changed Models Refer to Table 1 for model descriptions Color F114 white cabinet and cover F115 white cabinet and cover Blower Motor F114 two speed direct drive forward curve F115 single speed direct drive forward curve Table 1 F114 and F115 Description Efficiency Model Voltage Particulates at 0 3 Micron D O P Test Approximate CPZ components ...

Страница 3: ...cleaning the media air cleaner Choose Location The air cleaner is mounted horizontally and can be used in almost any air cleaning application For the most efficient operation centrally locate the air cleaner to the area to be cleaned For the best air patterns avoid discharging the air directly at an obstruction such as a ceiling beam decorative cornice or pillar The discharge air pattern has a ran...

Страница 4: ...ed service technician 4 After installation is complete check out product operation as provided in these instructions CAUTION Electrical Shock Hazard Power source can shock Do not connect the power source until after the air cleaner is mounted This will prevent electrical shock or equipment damage Be sure to turn off the air cleaner before servicing it If the air cleaner must be turned on for an el...

Страница 5: ... cartridges on the filter base 10 Insert the CPZ cartridge with the cartridge base notches against the motor towers 11 Attach the filter cover plates 12 Replace the air cleaner cover OPERATION The F114 and F115 Ceiling Surface Mounted Media Air Cleaners provide their own air circulation When the air cleaner is powered the blower motor draws the contaminated air into the air cleaner Particles that ...

Страница 6: ...e the air cleaner and turn the power on PARTS LIST Refer to Table 2 or 3 and Fig 6 or 7 for a parts list and an exploded view of the parts Table 2 F114 Ceiling Surface Mounted Media Air Cleaner Parts List e c n e r e f e R g i F o N n o i t p i r c s e D y t Q k c a P r e b m u N r e d r O o N e c n e r e f e R 1 r e v o c e t a l p n o i t c e p s n I 1 3 4 2 0 0 0 2 3 2 0 4 1 0 9 2 h c t i w s n...

Страница 7: ...EILING SURFACE MOUNTED MEDIA AIR CLEANERS 7 68 0201 2 Revised 11 07 PLENUM EARLY MODELS 11 AND 12 0NLY M12711 1 2 3 4 5 6 7 8 10 12 11 9 Fig 6 Exploded view of F114 Ceiling Surface Mounted Media Air Cleaner components ...

Страница 8: ... H 0 6 0 5 V 0 4 2 0 2 2 1 9 3 8 1 0 0 2 3 3 e t a l p d i M 1 1 4 2 0 0 0 2 3 4 0 2 0 0 9 4 x o b 1 r e t l i f e r P 4 9 2 2 0 0 0 2 3 5 1 0 6 3 s e x o b 0 1 0 4 0 3 2 0 0 0 2 3 6 1 0 6 3 5 4 s e r i u q e r r e t l i f A P E H 1 6 0 2 0 0 0 2 3 0 0 5 1 2 4 s e r i u q e r r e t l i f e l c i t r a P P O D 1 7 1 2 0 0 0 2 3 0 1 7 8 2 6 4 s e r i u q e r r e t s i n a c Z P C e l b a s o p s i D...

Страница 9: ...15 CEILING SURFACE MOUNTED MEDIA AIR CLEANERS 9 68 0201 2 Revised 11 07 ACCESS PLATE INSPECTION PLATE PLENUM M12712 8 1 2 3 4 5 6 7 Fig 7 Exploded view of F115 Ceiling Surface Mounted Media Air Cleaner components ...

Страница 10: ... BE LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING DIRECTLY OR INDIRECTLY FROM ANY BREACH OF WARRANTY EXPRESS OR IMPLIED OR ANY OTHER FAILURE OF THIS PRODUCT Some states do not allow the exclusion or limitation or incidental or consequential damages so this limitation may not apply to you THE WARRANTIES SET FORTH HEREIN ARE EXCLUSIVE AND AIR P...