5. C300 Configuration Form Reference
5.3. CEEC300 Function Block
136
Series 8 C300 Controller User's Guide
Honeywell
R500
April 2017
Plain Text
Parameter Name
User
Configurable
Notes
Instance Count
BLKTYPCOUNT
No
Shows the number of
instances currently
loaded to the controller.
CAB Types Info tab
The CAB Types Info tab contains information about the CAB types loaded in the CEE.
The following table summarizes the parameter data you can monitor on the
CAB Types
Info
tab of the configuration form for the selected CEEC300 block.
Plain Text
Parameter Name
User
Configurable
Notes
CAB Supported
Version
CC3SUPRTDV
No
Provides the version
level of the CAB/C300
run-time supported by
the C300. Only CAB
types which require this
version level or lower
can be loaded to the
C300.
Enable CAB Runtime
ENABLECAB
Yes
Displays whether the
CAB in a C300 is
enabled or disabled.
For application
engineers to be able to
load CAB programs to a
C300, this parameter
must be turned
“On.”
This parameter is
“Off”
by default. You must
turn this parameter
“On”
before the first CAB
load. If you want to
disable CAB in a C300
where it was previously
enabled, you must first
delete all CAB
instances and types
from the controller.
Содержание Experion C300
Страница 8: ......
Страница 18: ......
Страница 30: ......
Страница 34: ......
Страница 45: ......
Страница 90: ......
Страница 107: ......
Страница 164: ......
Страница 199: ......
Страница 221: ......
Страница 236: ......
Страница 242: ......
Страница 285: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...