Connection Example

Single UC1200PF 

Controlling water

LightSpot  presence-detecting washroom control

Only suitably qualified personnel should install this equipment.

This  is  a  high  performance  presence  detector  with  photocell.    The  photocell  can  operate  in  three  modes:   
Passive, Active or Disabled.  Further information can be found overleaf.

Fixing

The UC1200PF is suitable for flush mounting in a suspended ceiling tile, maximum 54mm thick and with a 
minimum clearance of 125mm between the front surface of the tile and the hard ceiling behind.  The UC1200PF 
should be mounted in the centre of the group of luminaires to be controlled.     Cut a 50mm diameter (64mm if 
using an FR64 flush ring or PB64 plasterboard fixing kit) circular hole in the tile, feed the flying lead and detector 
through the hole and secure into position with the locking ring. Twisting the locking ring will release the detector 
should this be necessary.

Note:

 Do not position within 25cm of a luminaire.

Solenoid Valve

The solenoid valve must be plumbed into the water feed to the urinal header tank and connected to the detector 
using 230V cable.

Multiple UC1200PF 

Larger areas can be covered by connecting extra units in parallel.  The total load current must not exceed 6 Amps 
in case only one unit is activated.  

N

E

L

Permanent 
or switched
supply

LIVE IN

LIVE IN

NEUTRAL

NEUTRAL

EARTH

EARTH

LIGHTING,

FAN OR VALVE

LightSpot

LightSpot

N

E

L

Permanent 
or switched
supply

LightSpot

LIVE IN

NEUTRAL

EARTH

SOLENOID 
VALVE

LIVE OUT

LIVE OUT

LIVE OUT

Important Additional Notes

1.

All terminals on this product are provided for final connections.  It is not intended that the product be used as a junction box 
for looping cables. 

2.

A means for disconnection must be incorporated in the fixed wiring in accordance with the current wiring regulations.

3.

This equipment switches lights no more frequently than would a responsible human occupant.  However, manufacturers of 
some  lighting types (e.g. ‘2D’  luminaires) may specify  a  maximum  number of switching cycles in order to achieve  a 
predicted  lamp  life.    Please  check  with  the  manufacturer  of  the  luminaires  to  ensure  that  they  are  compatible  with 
automatic controls in this respect. 

Содержание Ex-Or UC1200PF

Страница 1: ...allation and Commissioning Instructions Note HP2000 or HP10 HP18 required for commissioning Please note that the HP10 and HP18 offer different limited programming options LightSpot Washroom Series UC1200PF ...

Страница 2: ...enoid valve must be plumbed into the water feed to the urinal header tank and connected to the detector using 230V cable Multiple UC1200PF Larger areas can be covered by connecting extra units in parallel The total load current must not exceed 6Amps in case only one unit is activated N E L Permanent or switched supply LIVE IN LIVE IN NEUTRAL NEUTRAL EARTH EARTH LIGHTING FAN OR VALVE LightSpot Ligh...

Страница 3: ...fficient natural light is available It will not turn the load off whilst an area is occupied Active The photocell will turn the controlled load on and off as required whilst natural light levels fluctuate during a period of occupancy This mode of operation operates in conjunction with a passing cloud timer PCT The PCT is asymmetrical in operation the load will be switched on immediately that the l...

Страница 4: ...the control of water for washroom management applications urinals In order to maintain good standards of hygiene the products feature a washroom mode 24hr Cycle that if enabled ensures that when urinals have not been used for 24 hours i e the controlled area has been unoccupied a hygiene flush occurs Please note that when controlling lighting and urinals it is not possible to have the photocell in...

Отзывы: