background image

Important Additional Notes

1. 

All terminals on this product are provided for final connections.  It is not intended that the product be used as a 
junction box for looping cables.  

2. 

Although nominally 12V, the dimming output is not SELV and therefore should be treated with the same respect as 
mains with regard to wiring practice.  

3. 

Take care when choosing a location for this equipment since this type of device is capable of detecting large 
moving metal objects well beyond the normal range at which it is sensitive to human targets.

4. 

Please note that, although configurable as a regulating photocell, [closed-loop dimming according to daylight], 
due to the probable corner-of-room location where there will be excessive influence by daylight reflected from the 
walls, this product is not intended to achieve precise light level regulation measured on the working plane.

5.    This  equipment  switches  lights  no  more  frequently  than  would  a  responsible  human  occupant.    However, 

manufacturers of some lighting types (e.g. ‘2D’ luminaires) may specify a maximum number of switching cycles  in 
order to achieve a predicted lamp life.  Please check with the manufacturer of the luminaires to ensure that they 
are compatible with automatic controls in this respect. 

7

Содержание Ex-Or MLS2500D

Страница 1: ...kSet Pro required for commissioning MLS2500D MLS2500DF MLS2500DWL MLS2500DWLF MLS2500DALI ML2500DALIF MLS2500DALIWL MLS2500DALIWLF Digital Mid Range Series Detector with Wireless OneSwitch facility MLS2500D WL MLS2500DALI WL MLS2500D WL F MLS2500DALI WL F ...

Страница 2: ... 3mm of thread is visible and then twisting the detector off the back box Note the arrow symbol moulded into the bottom of the back box The fixing holes allow for mounting on a BESA box or direct to a rigid surface Secure the back box firmly to a rigid surface so that the arrow points into the controlled area 4b MLS2500DF Semi flush version Use a hole saw to drill a 76mm hole into the ceiling tile...

Страница 3: ...control circuit will not affect the operation of those lights that remain powered and under the control of the detector When switching via the relay output multiple MLS2500Ds relay outputs may be connected in parallel provided the controlled load does not exceed 10 Amps If digital ballasts are also being controlled the digital outputs from different detectors must never be connected one to another...

Страница 4: ...can be re programmed any number of times Factory Default Settings These are the settings to which the units have been programmed before they leave the factory Parameter Power Up Response Off Delay On Sensitivity Off Sensitivity Bus Connect 1st Zone 2nd Zone 3rd Zone 4th Zone Corridor 1 Begin End Corridor 2 Begin End Global 1 Rx Global 2 Rx Manual I P Start Lamps Entry Scene Lamp Max Dimming Fade t...

Страница 5: ...SABLED If the photocell is configured as DISABLED for relay Switching Control it will have no effect on the control of that load which will be ON continuously during periods of occupancy unless commanded OFF via manual switch or infrared control The photocell readings are still available for use by the Regulating Control module while in this mode Programming the Photocell Set points The parameters...

Страница 6: ...ts to be on and above which you would not want the lights to be on 3 Start the internal self programming mechanism by pressing UTILITIES LIGHTSPOT MLS LCM SET LIGHT LEVEL OK QuickSet Pro or Scene 1 HC5A The detector takes a photocell reading adds a small amount and stores the value in SET POINT HIGH Then it turns the lights off makes another measurement and stores the value in SET POINT LOW The li...

Страница 7: ...antargets 4 Please note that although configurable as a regulating photocell closed loop dimming according to daylight due to the probable corner of roomlocation where there will be excessive influence by daylight reflected from the walls this productis not intendedto achievepreciselightlevelregulationmeasuredon the workingplane 5 This equipment switches lights no more frequently than would a resp...

Страница 8: ...at 230V MAXIMUM RECOMMENDED LOAD DSI DALI 25 Ballasts MAXIMUM RECOMMENDED MOUNTING HEIGHT 3 5m RANGE Adjustable up to 20m OFF DELAY 1 min 96 hours plus 10 second walk test mode PHOTOCELL Passive Active Regulating adjustable 50 5000 lux MATERIAL Flame retardant PC ABS COLOUR White RAL9010 WEIGHT 180g flush version 160g surface version IP RATING 4X o o OPERATING TEMPERATURE 0 C to 40 C Contact Ex Or...

Отзывы: