background image

ii) The Primary Interest is the Switching Control Output

With the photocell configured as ACTIVE or PASSIVE:-

1) If the lights are not already on, switch them on manually by pressing ‘UTILITIES / LIGHTSPOT/MLS/LCM / 
IR-REMOTE / HC5 / Lu / OK’ (QuickSet Pro) or "+" (HC5A). Fluorescent lights do not reach full output 
until up to 15 minutes after being switched on, so ensure that the lights are fully warmed up before continuing.  

2) Wait until the time of day when the natural light level is at the point below which you 

would

 want the lights to 

be on, and above which you 

would not

 want the lights to be on.

3) Start the internal self-programming mechanism by pressing ‘UTILITIES / LIGHTSPOT/MLS/LCM / SET 
LIGHT LEVEL / OK’ (QuickSet Pro) or Scene 1 (HC5A). The detector takes a photocell reading, adds a small 
amount and stores the value in SET-POINT HIGH. Then it turns the lights off, makes another measurement 
and stores the value in SET-POINT LOW.   The lights now switch on again to acknowledge a successful 
programming operation.

The two switching thresholds have now been set, and the difference between them is equal to slightly more 
than the contribution made by the electric lighting. This is the perfect amount of hysteresis to ensure that the 
lights will not oscillate.  

6

Содержание Ex-Or MLS2500D

Страница 1: ...kSet Pro required for commissioning MLS2500D MLS2500DF MLS2500DWL MLS2500DWLF MLS2500DALI ML2500DALIF MLS2500DALIWL MLS2500DALIWLF Digital Mid Range Series Detector with Wireless OneSwitch facility MLS2500D WL MLS2500DALI WL MLS2500D WL F MLS2500DALI WL F ...

Страница 2: ... 3mm of thread is visible and then twisting the detector off the back box Note the arrow symbol moulded into the bottom of the back box The fixing holes allow for mounting on a BESA box or direct to a rigid surface Secure the back box firmly to a rigid surface so that the arrow points into the controlled area 4b MLS2500DF Semi flush version Use a hole saw to drill a 76mm hole into the ceiling tile...

Страница 3: ...control circuit will not affect the operation of those lights that remain powered and under the control of the detector When switching via the relay output multiple MLS2500Ds relay outputs may be connected in parallel provided the controlled load does not exceed 10 Amps If digital ballasts are also being controlled the digital outputs from different detectors must never be connected one to another...

Страница 4: ...can be re programmed any number of times Factory Default Settings These are the settings to which the units have been programmed before they leave the factory Parameter Power Up Response Off Delay On Sensitivity Off Sensitivity Bus Connect 1st Zone 2nd Zone 3rd Zone 4th Zone Corridor 1 Begin End Corridor 2 Begin End Global 1 Rx Global 2 Rx Manual I P Start Lamps Entry Scene Lamp Max Dimming Fade t...

Страница 5: ...SABLED If the photocell is configured as DISABLED for relay Switching Control it will have no effect on the control of that load which will be ON continuously during periods of occupancy unless commanded OFF via manual switch or infrared control The photocell readings are still available for use by the Regulating Control module while in this mode Programming the Photocell Set points The parameters...

Страница 6: ...ts to be on and above which you would not want the lights to be on 3 Start the internal self programming mechanism by pressing UTILITIES LIGHTSPOT MLS LCM SET LIGHT LEVEL OK QuickSet Pro or Scene 1 HC5A The detector takes a photocell reading adds a small amount and stores the value in SET POINT HIGH Then it turns the lights off makes another measurement and stores the value in SET POINT LOW The li...

Страница 7: ...antargets 4 Please note that although configurable as a regulating photocell closed loop dimming according to daylight due to the probable corner of roomlocation where there will be excessive influence by daylight reflected from the walls this productis not intendedto achievepreciselightlevelregulationmeasuredon the workingplane 5 This equipment switches lights no more frequently than would a resp...

Страница 8: ...at 230V MAXIMUM RECOMMENDED LOAD DSI DALI 25 Ballasts MAXIMUM RECOMMENDED MOUNTING HEIGHT 3 5m RANGE Adjustable up to 20m OFF DELAY 1 min 96 hours plus 10 second walk test mode PHOTOCELL Passive Active Regulating adjustable 50 5000 lux MATERIAL Flame retardant PC ABS COLOUR White RAL9010 WEIGHT 180g flush version 160g surface version IP RATING 4X o o OPERATING TEMPERATURE 0 C to 40 C Contact Ex Or...

Отзывы: