The CDW12U5 can be commissioned using the QuickSet Pro hand-held programmer or from a dedicated programme running on a portable PC.  Communication from the PC can be by 
means of a USB Infrared Transceiver which can signal directly to the CDW12U5's onboard infrared port over a short range or via any attached detector over longer ranges. Alternatively a 
specialised wired serial link can be established with the CDW12U5 itself.   The main parameters available for configuration are shown below. Parameters may be re-programmed any 
number of times and all settings will be retained in the event of a power loss.

Commissioning

PARAMETERS

OPTIONS (Defaults, where applicable, shown in bold)

Per Box Parameters:

Switches 1A-5B & 6A-7B (RF1 & 2): Mode

User may choose any option for Switch A or Switch B (see section at end of table for details of SELV switch options).

Detector 1-5: Range (On & Off Sensitivity)

Max: 100%, 75% or 50%  /  High: 100%, 75% or 50%  /  

Med

: 100%, 75% or 

50%

  /  Low: 100%, 75% or 50%  /  Min: 100% or 75%

Detector 1-5: Sensitivity Fine

Mode A

, Mode B or Mode C -

 Applies when Sensitivity is set to Max and during occupancy only (Mode A = Normal, B & C = More Sensitive)

Common: Address

0-127 - 

MLS address for DALI Emergency test.  

Default = 0

Common: Switch Map

Normal 

/ Direct / Direct 2 / Zero Off Dly / Modes 04-07 (for future use) -

 Pre-set switch mappings (except Zero Off Dly - instant off option) 

Common: LED Inhibit

Yes / 

No

 - 

Enab les or disab les the detector’s LEDs.

Common: Inhibit DALI Init

Yes / 

No

 - 

Prevents the DALI b allasts from b eing initialised every time the b ox powers up.

Common: Missing Detector

Normal

 / On Full - 

Puts all outputs on if there’s a detector assigned to a channel and that detector isn’t present.

Common: Slow Dim (mins)

0-254  - 

Fade time setting, for use with Slow Dim and Slow Brighten switch functions.  

Default = 0

Common: Bus Absent All On

Yes / 

No

 - 

All lights default to ON in the event of a b us failure.

Assigned Detectors

Detector 1 - Detector 5 Assigned or Not Assigned to this Channel.

Pcell Source

None (--)

, 1,2,3,4,5 - 

Photocell 1-5 (in Detectors 1-5) Assigned or Not Assigned to this channel.

Assigned Switches

Switch 1A - Switch 5B & Switch 6A - 7B (RF) Assigned or Not Assigned to this channel.

Power Up

On

 / Off

Occ Trigger Mode

Presence 

/ Absence / Manual

Low Lux Level (Auto Absence)

0-254  (

0 = feature disabled

) - 

Used in manual modes: When it is dark, lights respond to movement automatically without requiring switch press.

Sw Auto Detect

Yes / 

No

 - 

Used in manual modes: If set to Yes, presence detection is automatic until a switch press is detected.

Manual I/P

Local 

/ Share  (

Local = Ob ey locally only; Share = Ob ey locally and trasmit command on MLS b us)

Occupied Scene

Scene 1-6  

 Scene1

Alt. Occ. Scene A & B

Scene 1-6 or

 -- (feature disabled)

 -  

Determines different actions on entry dependent on time of day. 

Start Lamps

Max

 / Min

Occupied Timer

10 seconds to 96 hours, Disabled.  

 20 mins

Photocell 

Regulate (

100%

, 90%, 80%, 70%, 60%, 50%) / Passive / Active / Disabled

Bright Out

Yes / 

No

Set-Point Low / High 

Photocell Lower and Upper Thresholds: 0-1023 (used in Regulating Scene 1).  

Low = 350; High = 450

Scene 2-6

Output 0-100% or -- (no change) 

Scene 2 = 80%; 3 = 40%; 4 = 20%; 5 = 10%; 6 = 5%

Transition Scene

Scene 1-6 or 

-- (feature disabled) 

Scene interposed b etween 'Occ Timer' & 'Background Level' to allow movement to restore lights at existing level.  

Transition Timer

10 seconds to 96 hours - 

Determines length of transition scene. 

 10 secs

Background Level

Off

Minimum, 25% or Scene 6  

(these options show XTN suffix)

 for 3 x Occupied Timer, then Off.

Minimum, 25% or Scene 6, 5, 4, 3 or 2 

(these options show BLD suffix)

 until the building has been vacated.

Minimum, 25% or Scene 6, 5, 4, 3 or 2  

(Background Timer parameter applies to these options which have no suffix).

Alt. Background Scene A & B

Scene 1-6 or 

-- (no scene)

 - 

Determines different actions when the area is vacant dependent on time of day.

Background Tmr

10 seconds to 96 hours or 

-- (none)

 - 

Applies to 'Alt Exit Scenes' and some 'Background Level' scenes (i.e. not XTN and BLD options). When Background Timer 

expires, channel's output turns off.

Fade to Off

Yes / 

No

Bus Connect

Yes

 / No

Zones 1-4

None (--)

, Zone number 1-100 / Common 1,2,3

Zones 1-4 TRX

Tx Rx 

/ Tx Only / Rx Only - 

Determines how zone parameters 1-4 b ehave with respect to b us commands.

Corridor 1-2: Begin / End

None (--)

, Zone number 1-100 / Bld

Corridor Scene

Scene 1-6 or -- (

no scene

) -

 Movement within an area's Corridor Begin/End span will cause that area to go to the chosen scene.  Direct movement within zones 1-4 

will override this and the channel will go to its Entry Scene. 

Global 1-2 Rx

Yes

 / No

Ballast

1% DSI

, 3% DSI, 10% DSI, 1% DALI, 3% DALI, 10% DALI (Non-Dimming - use default i.e. 1% DSI)

Lamp Max

100%

, 90%, 80%, 70%, 50%, 45%, 40%, 35%, 30%, 25%, 20%, 15%, 10%

Burn-In Hrs

Burn-in 100 hrs / Cancel / Resume 

 (See Application Note AN4028 - limited functionality via QuickSet Pro)

Quick Burn-In

Yes / 

No

 - 

If set to Yes, output remains on until 100-hr b urn-in is completed.

Burn-In Dimming

Yes / 

No

 -

 If  set to Yes, allows temporary (30 secs) dimming in response to manual inputs, even though in 100-hr b urn-in mode.

Offset Dimming

None (--)

 to 100% in 10% increments. 

Allows selected channels to b e configured to b e b righter than a reference channel according to chosen 'output weightings' 

(e.g. Ref Ch = 0% (window row), Ch2 = 10% b righter (adjacent to window row), Ch3 = 30% b righter (furthest from windows) - all would work together to achieve 
chosen lux level, maintaining respective percentage differences in output).  

Per Channel Parameters:

SELV Switch Options

Description

Sustain

Imitates movement seen, as a result output of Channel remains ON till the assigned switch with 'SUSTAIN' is active.

Brighten

Raises the light level. Works only with dimmable ballasts. 

Dim

Lowers the light level.  Works only with dimmable ballasts.

Off

Turns lamp OFF.

Scene 1-6

Recalls Scene assigned (any Scene 1 to 6 as configured).

On

Turns lamp ON.

Partition

Initiates logical partition of a room. Refer to Application Notes AN4002 & AN4004 for more details.

OneSwitch

Simple momentary push-to-make wallswitch that can be used to raise or lower the lighting level or toggle the output of the unit ON or OFF.  Short press toggles 
output level between ON & OFF, long press will ramp the light level Up or Down.

On-Dim

Short Press will turn the output ON, long press will lower the light level.

Off-Brighten

Short Press will turn the output OFF, long press will raise the light level.

On / Brighten

Short Press will turn the output ON, long press will raise the light level.

Off / Dim

Short Press will turn the output OFF, long press will lower the light level.

Emergency Tst

Imitates manual test of emergency luminaire by turning OFF the Maintained Live.

Emergency End

Restores Maintained Live to end the Emergency Test.

Last Out

"Last man out" switch, reduces the Occupied Timer to 10 seconds for a fast time-out when leaving the building.

Door Open / Door Closed

Connected to switches detecting whether door is open or closed. Choice depends on type of operation (normally contact would be closed when door is closed).

Keycard In / Keycard Out

Connected to switches detecting whether keycard is inserted or not. Choice depends on type of operation.

Edge: On, Off, Scene 1-6

Edge-triggered commands as above - sent only once as the switch is pressed.

Edge: Brighten / Dim

Each press increments or decrements the DALI output.

Last Out-On

Short press = fast time-out for "last man out"; Long press =  turns on at Entry Scene for "first man in".

Time of Day A & B

Cause the channels to use Alt. Occupied Scenes A or B and Alt. Background Scenes A or B.

Unoccupied 10%

Sends a 'Time Out Now, Go to DALI 10%' message on the MLS bus.

Partition Open / Closed

Initiates logical partition of a room - for use with EnOcean reed switch transmitters.

Slow Brighten / Dim

Switch input held causes slow ramp / slow fade.  Fade time adjustable in Common menu, 1 min to 254 mins.