Honeywell Ex-Or CDW12U5 Скачать руководство пользователя страница 2

Channel 1

Channel 2

Channel 3

Channel 4

Channel 5

Channel 6

186 

P

C

B

1

 

LIVE
(MAINTAINED LIVE)

EARTH

NEUTRAL

MAINS POWER
CONNECTIONS

THIS EQUIPMENT MUST BE
EARTHED

REMOVE LINK IF  A SEPARATE
MAINTAINED LIVE SUPPLY IS
TO BE CONNECTED.

MLS Bus 1 In
MLS Bus 2 In
MLS Bus 1 Out
MLS Bus 2 Out

MLS BUS CONNECTIONS

1.5mm² TWISTED PAIR IN 
AND 1.5mm² TWISTED PAIR OUT

CABLE
CHAMBER

Pre-Installed
Rigid Link

Connections Available on each Luminaire Socket

.

Switched Live - 6A max per channel, 16A max per box. 

Neutral

Maintained Live - 2A max per box.

-

      

Dimming Control

+

10 x DSI/DALI ballasts max per channel.
40 x DSI/DALI ballasts max per box.
Analogue 1-10V ballasts: 20mA, see details 
on back page.

Connecting the Switches

The CDW12U5 is equipped to take a set of up to five SELV switches which will typically be 
two way, centre-off, momentary rockers, (e.g. the MK K4900 range). The logical function of 
a switch can be configured from a wide range of options and its action can be associated 
with any combination of channels. The switch connection consists of a 3-pole pluggable 
terminal block comprising a common and two returns from normally open contacts.   The 
LCM is supplied fully populated with five plugs.

MLS Interface
Card (if fitted)

Note  that  if  the  SELV  status  of  any  one  of  the  switches  is 
compromised  by  reason  of  inadequate  insulation  or 
segregation of the cabling, then the SELV status of all other 
switches AND OF THE SENSORS will also be compromised.

Introduction

The CDW12U5 is an intelligent lighting control module (LCM) or connection 
box providing connections for up to twelve luminaires, up to five sensors 
and  up  to  five  switch  inputs. The  unit  is  designed  to  simplify  installation 
whilst providing an intelligent managed lighting system, including provision 
for emergency lighting.

Fixing

The box should be attached to a suitable smooth, flat surface, using the two 
end-located fixing points. Consideration should be given to the need for 
access to install and maintain the lighting system when choosing a location 
for the box.
The box must not be distorted when fixing. If the box is to be mounted on an 
uneven surface it may be necessary to use packing pieces or self-adhesive 
stand-off feet. 
When the box is to be rod-fixed, the fixing should be substantial enough to 
withstand the action of plugging and unplugging the connectors.

Electrical Connection

The connections to this equipment should be made only by a suitably 
qualified person and in accordance with current wiring regulations.
A means of disconnection must be incorporated in the fixed mains 
wiring to this box in accordance with current wiring regulations.

It  is  imperative  that  the  MLS  Bus  be  wired  in  the  correct  type  of  cable. 
Normally  it  should  be  1.5mm²  unscreened  twisted  pair.  See Application 
Note AN4001.  

Do not connect Mains to the MLS Bus.

The cover of the cable chamber is removed by inserting the tip of a flat 
bladed screwdriver into the catch recess and exerting light pressure on the 
handle in an inboard direction while lifting the long outboard edge of the 
cover. 
The cable entries, for 20mm conduit, bushes or glands are semi-pierced in 
the walls of the cable chamber and can easily be removed from the outside 
with a 20mm hole saw.
If the cables are not routed right into the box through conduit or trunking, a 
cable restraining gland must be fitted at the cable entry for strain relief.

Connecting the Luminaires

Separate versions of the CDW12U5 are provided to control DSI, DALI and 
1-10V Ballasts. (See Part Numbers list on the back page.)
  

  Note: Ballast types CANNOT BE MIXED on a single CDW12U5 

The  CDW12U5  is  equipped  with  twelve  GST  18/6  sockets  for  the 
connection  of  individual  luminaires.  These  connections  are  equipped  to 
take Ex-Or's Latching   Plug   Shells.   Alternatively non-latching "Wieland 
style" plugs with hoods of up to 21mm depth may be fitted.
The  luminaire  sockets  are    grouped  into  six  channels,  each  capable  of 
independent control, as follows:
2 channels each controlling 3 luminaire sockets,
2 channels each controlling 2 luminaire sockets,
2 channels each controlling a single luminaire socket.
The CDW12U5 may be commissioned with configurations which allow two 
or more of the six channels to act together, in any combination required.

Connecting the Sensors

The  following SELV sensors are designed to interface to the CDW12U5:

MLS2500CDR       

   Corner-mount Microwave sensor with photocell, semi-flush 

mounted. Available surface mounted (SM suffix)       

MLS2401CDR       

360º Microwave sensor with photocell, flush  mounted. Available 

surface mounted (SM suffix)

MLSM2002CDR 

  Control Module for 360º Mini PIR with photocell used with DHS 

or DHW mini detector head to form integral  luminaire-mounted 
unit

MLSM2002CDRDHPBW Mini Detector with Control Module & Plasterboard Fixing Kit
MLS3000CDR 

360º PIR sensor with photocell (flush or surface mount:  F or SM 

suffix)

MLS3003CDR 

360º PIR sensor with photocell with photocell with tilting lens 

(flush  or surface mount: F or SM suffix)

MLS3003CDRMB  

Mid-Bay (for mounting up 12m high) 360º PIR sensor with 

photocell  with tilting lens (flush or surface mount: F or SM suffix)

MLS3003CDRHB  

Hi-Bay(for mounting up to 16m high) 360º PIR sensor with 

photocell  with tilting lens (flush or surface mount: F or SM suffix)

All connect to the  CDW12U5 by means of an Ethernet-style  RJ45 connector terminated 
patch lead which are available ready-made in 3m, 5m and 10m lengths. Up to five detectors 
may  be  connected  to  a  CDW12U5  box.  The  maximum  allowable  cable  length  from  the 
CDW12U5 to a detector is 100m.

Positioning the Sensors

 (for Fixing Details see installation instructions)

The MLS2500CDR is designed to project below the ceiling and to sense a volume of space 
defined by an slanting cone, radiating from its flat face. Typically sited in the corner of a room 
ceiling diagonally opposite the door, it can then sense presence over the entire room.  At the 
maximum sensitivity setting it can sense an area extending to 20m from its own position.

The MLS2401CDR is designed to be set in the plane of the ceiling and to sense a  conical 
space vertically below such that its diameter at floor level is equal to 2.8 x the detector's height 
above floor level (typically 7m diameter with a ceiling height of 2.5m).

Note that in the above two cases microwave presence detection is not completely 
blocked  by  materials  such  as  plasterboard,  wood,  and  glass,  so  the  possibility  of 
unwanted presence detection through lightly built partitions should be considered 
when determining sensor positioning and sensitivity settings

.   

MLS3000CDR & MLS3003CDR should be positioned in the centre of the occupied space.  
They sense a conical space vertically below with the following aspect ratios:

Avoid mounting next to an AC unit. For details of tilting lens, see installation instructions.

None of the sensor types above should be positioned within 0.25m of a luminaire.

The MLSM2002CDR and its associated DHS or DHW mini detector head can be mounted 
within the structure of the luminaire with only the small oval face of the sensor showing.  See 
installation instructions for this product.  (For remote mounting in plasterboard or suspended 
ceilings, use MLSM2002CDRDHPBW.)

For connection of the SELV switches, multi-core cable such as 3-core 300/500V 0.75mm² 
cable to CMA Reference 3183Y or, for LS0H, to CMA Reference 3183B or CAT5 cable for 
example  may  be  used.  The  maximum  allowable  cable  length  between  the  switch 
mechanism and the CDW12U5 switch terminal block is 100m. 

Three separate singles cables should not be used.

Aspect Ratio (diameter : height)

Type

Max recommended

mounting height

Office

Mid-Bay

Hi-Bay

Micro Detection -

High Sensitivity

Macro Detection -

Standard Sensitivity

3.5m

12m

16m

N/A

N/A

4:1

 (10m diameter @ 2.5m height)

2:1

(20m diameter @10m height)

1.9:1

(27m diameter @14m height)

2.8:1

(7m diameter @ 2.5m height)

 

Отзывы: