Refurbishment Zone Transponder RZT 8000
FB 789807.10 / 05.17
19
1.1 Loop
devices
esserbus
®
esserbus
®
PLus
1
2
3
4
5
6
Fig. 7: Loop devices
Management system
Fire brigade operating panel
FACP
esserbus
®
transponder
Third-party detector connecting module RZT 8000
Detectors different manufacturer (third-party detector)
2 Features
The RZT 8000 third-party detector connecting module has four detector zones inputs and two relay outputs.
It may be used for connecting four additional standard detector zones with non-addressable third-party
detectors to the loop. The two relay outputs are available for general control purposes.
Output current max. 125 mA per detector zone
The detector states “prealarm“ or “detector fault“ may also be displayed.
Variable reset delay of the detector zone (0 to 15 seconds)
The detector zones can be operated in ‘dual-detector dependency type B’
Two relays with programmable operating modes
Programmable with the service and programming software tools 8000
Monitoring of the external power supply is possible
The 24 V DC detector zone voltage is generated inside the module (808630.10 only)