Honeywell Eclipse Скачать руководство пользователя страница 3

Flame Safety, Ignition Components · Edition 12.20

EN-3

 

Do not allow the scanner to operate at temperatures above the 
manufacturer’s published limit. Scanners can be overheated by 
high ambient temperatures, heat conducted and radiated from 
burner and furnace surfaces, or a combination of the two.

 

On most installations, scanners can be kept cool by purge air 
blown into the scanner adaptor

Adjustable 

Orifice

UV Scanner

Scanner

Adapter

Tubing

Connect Purge

Air Line to Burner

Air Housing Tap or

Combustion Air Line

(DO NOT connect to a preheated air line.)

Cooling the UV Scanner

Eclipse UV scanner adaptors and Heat Block Seals include tapped 
connections for purge lines. The adjustable orifice cock in Figure 
"Cooling the UV Scanner" permits setting the purge air at the opti-
mum flow rate.
On some burners, the scanner connection sights through the length 
of the combustion air housing. The cold combustion air should suf-
fice to keep the scanner cool, so no additional purge air is required.
Preheated air burners pose a special problem, because the larger 
amount of heat conducted and radiated from the burner can easily 
overheat the scanner.

 

Always use a Heat Block Seal such as Eclipe’s HBS on pre-
heated air burners. These adaptors include a quartz lense and 
a non-metallic insulating nipple to reduce the heat conducted 
back to the scanner.

 

Cool purge air will probably also be required.

 

In extreme cases, even these measures may not be sufficient, and 
it may be necessary to use a radiation shield or to blow cooling 
air over the scanner.

WIRInG

 CAUtIon

Installation and trouble-shooting of flame supervisory circuits 
should be done by qualified electricians, technicians or engineers 
experienced in all facets of this type of control equipment.

electrical wiring compliances

 

All the electrical wiring must comply with all applicable local codes 
and/or standards such as NFPA Standard 70, IEC60364, CSA 
C22, BS7671 and be acceptable to the local authority having 
jurisdiction.

Handling flame supervisory components

 

Exercise extreme caution in handling all flame supervisory com-
ponents. Many parts of the system operate at high voltage and 
pose an electrocution hazard.

Follow manufacturer’s recommendations

Follow the flame detector manufacturer’s recommendations regarding 
wire gauges, insulation grades and line lengths.
Wire type and length may weaken signal strength due to capacitive 
coupling to ground.
On some installations, the wiring and its conduit may be exposed 
to higher-than-normal temperatures. In these cases, use wiring with 
high temperature insulation.

Wiring splices

 1 

Make as few wiring splices as possible between the detector and 
its relay, as each splice is a potential source of current leakage 
or grounding.

 2 

Make sure the bare wire ends at each splice are clean and not 
oxidized. Secure splices with twist or crimp connectors, and tape, 
if necessary, to ensure that no bare metal is exposed.

 3 

Make sure the connectors and tape are rated for the temperature 
at the splice location.

 CAUtIon

Use Caution regarding wires through boxes!

 

– Take care not to cut or nick the wires when pulling them 

through conduit or junction boxes.

Wires from several Flame Detectors

 

Wires from several flame detectors may be run together in a 
common conduit, but do not place them in the same conduit with 
high voltage ignition wires. Some manufacturers permit detector 
lead wires in the same conduit as 120 VAC control wiring, but 
may limit the length of run in a shared conduit. For longer runs, 
separate conduits are required.

 

Also, long runs may require shielding to prevent cross interference 
and inducing a false signal onto a wire of a detector with no flame 
from a detector wire that is sensing a flame.

 

Make sure that you connect the flame sensor of a burner to the 
electrical circuit of that burner.

Grounding

 1 

Make sure the flame relay is properly grounded.

 2 

UV scanners generally require grounding as well - this can be 
done through the burner.

 

However, if the scanner is mounted on a Heat Block Seal using 
a non-metallic nipple, there will not be a ground connection to 
the burner. Likewise, do not use non-conducting pipe dope on 
scanner or adaptor threads.

 

Likewise, do not use non-conducting pipe dope on scanner or 
adaptor threads.

spark Interference

Electric spark ignition produces strong ultraviolet radiation. A UV 
scanner can detect this radiation on some burners, either by direct 
line of sight or by reflections from burner parts. Test the effect of 
the ignition system on the flame signal and control sequence both 
without and with flow of fuel to the burner. Flame rod signals can also 
be affected due to electrical interference and sharing of the ground 
connections. The signal may be increased, decreased or very erratic 
while the ignition is on.
The following steps may help reduce spark interference:

 1 

Separate or shield the detector wiring from the ignition wiring.

 2 

Ensure proper grounding of the ignition transformer to burner 
housing.

 3 

Reverse the wires feeding the primary to the ignition transformer.

 4 

Check for proper spark gap.

 5 

Clean, repair or replace faulty wiring and connectors.

 6 

Move the location of the ignition transformer.

 7 

Block UV scanner sighting with an orifice adapter.

 8 

Use a half-wave ignition transformer.

tRoUBLeLsHootInG

Refer to the product literature for the specific type of flame supervising 
equipment in use. In addition, check that the installation was made 
according to the recommendations in this operating instruction.

Содержание Eclipse

Страница 1: ...ll interventions may only be carried out by qualified gas techni cians Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Disclaimer Notice In accordance with the manufacture s policy of continual product improvement the product presented in this brochure is subject to change without notice...

Страница 2: ... contain ions capable of conducting electrical current An AC voltage on the flame rod will conduct current through the flame to a grounding surface usually the metal parts of the burner The signal will be rectified to DC with a 4 to 1 ratio of surface areas of the burner ground and flame rod that are in contact with the flame On receipt of the DC signal the controller will send power to keep the a...

Страница 3: ...detector and its relay as each splice is a potential source of current leakage or grounding 2 Make sure the bare wire ends at each splice are clean and not oxidized Secure splices with twist or crimp connectors and tape if necessary to ensure that no bare metal is exposed 3 Make sure the connectors and tape are rated for the temperature at the splice location CAUTION Use Caution regarding wires th...

Страница 4: ... Thermal Solutions family of products includes Honeywell Combustion Safety Eclipse Exothermics Hauck Kromschröder and Maxon To learn more about our products visit ThermalSolutions honeywell com or contact your Honeywell Sales Engineer Eclipse Inc 1665 Elmwood Rd Rockford IL 61103 United States www eclipsenet com ThermalSolutions honeywell com FOR MORE INFORMATION ...

Отзывы: