background image

W

innox · Edition 12.20

EN-2

Audience and Purpose

This manual has been written for people who are al-
ready familiar with all aspects of a gas burner and its add-
on components, also referred to as “the burner system”.  
These aspects are: 

 

– Installation

 

– Use

 

– Maintenance
The audience is expected to have previous experience with this 
type of equipment.
The purpose of this manual is to make sure that you carry out the 
installation of a safe, effective, and trouble-free system.

Further documents

For further information about this product see Technical Information 

safety instructions

Information that is relevant for safety is indicated in the instructions 
as follows:

 DAnGeR

Indicates a hazardous situation which, if not avoided, will result in 
death or serious injury.

 WARnInG

Indicates a hazardous situation which, if not avoided, could 
result in death or serious injury.

 CAUtIon

Indicates a hazardous situation which, if not avoided, could 
result in minor or moderate injury.

All interventions may only be carried out by qualified gas techni-
cians. Electrical interventions may only be carried out by qualified 
electricians.

safety

Important notices which help provide safe burner operation will be 
found in this section. To avoid personal injury and damage to the prop-
erty or facility, the following warnings must be observed. All involved 
personnel should read this entire manual carefully before attempting 
to start or operate this system. If any part of the information in this 
manual is not understood, contact Honeywell before continuing.

 DAnGeR

The burners covered in this manual are designed to mix fuel with 
oxygen and burn the resulting mixture. All fuel burning devices 
are capable of producing fires and explosions when improperly 
applied, installed, adjusted, controlled or maintained.

 

– Do not bypass any safety feature; fire or explosion could result.

 

– Never try to light the burner if it shows signs of damage or 

malfunction.

 WARnInG

 

– The burner is likely to have HOT surfaces. Always wear 

protective clothing when approaching the burner.

 

– Honeywell products are designed to minimize the use of 

materials that contain crystalline silica. Examples of these 
chemicals are: respirable crystalline silica from bricks, cement 
or other masonry products and respirable refractory ceramic 
fibers from insulating blankets, boards, or gaskets. Despite 
these efforts, dust created by sanding, sawing, grinding, 
cutting and other construction activities could release crystal-
line silica. Crystalline silica is known to cause cancer, and 
health risks from the exposure to these chemicals vary 
depending on the frequency and length of exposure to these 
chemicals. To reduce the risk, limit exposure to these chemi-
cals, work in a well-ventilated area and wear approved person-
al protective safety equipment for these chemicals.

 CAUtIon

 

– This manual gives information for the use of these burners for 

their specific design purpose. Do not deviate from any 
instructions or application limits in this manual without written 
advice from Honeywell.

Capabilities

Only qualified personnel, with good mechanical aptitude and ex-
perience with combustion equipment, should adjust, maintain, or 
troubleshoot any mechanical or electrical part of this system.

operator training

The best safety precaution is an alert and trained operator. Train 
new operators thoroughly and have them demonstrate an adequate 
understanding of the equipment and its operation. A regular retraining 
schedule should be administered to ensure operators maintain a 
high degree of proficiency.

Replacement Parts

Order replacement parts from Honeywell only. Any customer-sup-
plied valves or switches should carry UL, FM, CSA, CGA and/or CE 
approval where applicable.

PRoDUCt DesCRIPtIon

The Winnox is a nozzle-mix, low-emissions burner designed for 
direct and indirect air heating, as well as oven applications up to 
1800°F (980°C).
The burner package includes a combustion air blower and ratio 
regulator to fire over a wide gas turndown range at a controlled ratio.
The wide variety of options and configurations are available due to 
the modular design of the burner.
The burner is designed for:

 

– Low NO

X

 and CO emissions 

 

– Efficient ratio controlled combustion

 

– Reliable burner operation

 

– Simple burner adjustment

 

– Direct spark ignition

 

– Multiple fuel capability

IntRoDUCtIon

In this section you will find the information and instructions needed 
to install the burner and system components.

Handling and storage
Handling

 

Make sure the area is clean.

 

Protect the components from weather, damage, dirt and moisture.

 

Protect the components from excessive temperatures and hu-
midity.

storage

 

Make sure the components are clean and free of damage.

 

Store the components in a cool, clean, dry room.

 

After making sure everything is present and in good condition, 
keep the components in original packages as long as possible.

Position of Components

The position and amount of components are determined by the kind 
of control method chosen. All the control methods can be found here: 
Technical Information Winnox - System Design. Use the schematics
 
in that chapter to build your system. 

Approval of Components
Limit Controls and safety equipment

All limit controls and safety equipment must comply with all applicable 
local codes and/or standards and must be listed for combustion 
safety by an independent testing agency. Typical application ex-
amples include:

 

– American: NFPA 86 with listing marks from UL, FM, CSA

 

– European: EN 746-2 with CE mark from TuV, Gastec, Advanti-

ca

Содержание Eclipse Winnox WX0850

Страница 1: ... breach of warranty negligence strict liability or otherwise is limited to the furnishing of replacement parts and Honeywell Eclipse will not be liable for any other injury loss damage or expenses whether direct or consequential including but not limited to loss of use income or damage to material arising in connection with the sale installation use of inability to use or the repair or replacement...

Страница 2: ...ls To reduce the risk limit exposure to these chemi cals work in a well ventilated area and wear approved person al protective safety equipment for these chemicals CAUTION This manual gives information for the use of these burners for their specific design purpose Do not deviate from any instructions or application limits in this manual without written advice from Honeywell Capabilities Only quali...

Страница 3: ...age frequency and stability of the electrical power Fuel type and supply pressure of the fuel Availability of enough fresh clean combustion air Humidity altitude and temperature of air Presence of damaging corrosive gases in the air Prevent direct exposure to water INSTALL FLAME SENSOR 1 Install the flame sensor into the 1 2 NPT opening in the rear cover 2 Make sure that you connect the flame sens...

Страница 4: ...er piping The burner is factory assembled and shipped as ordered Note If you have to realign the pipes please observe the following CAUTION Do not attempt to redirect piping by removing the inner circle boltsE Internal burner parts will be damaged 1 Remove the outer A four bolts only E A A Redirect piping 2 Rotate the rear cover and replace bolts When reassembling ensure the following B C D F Burn...

Страница 5: ... there are no leaks in the gas and air lines 2 Make sure all the components of the flame monitoring control system are properly installed This includes verifying that all switch es are installed in correct locations and all wiring pressure and impulse lines are properly connected 3 Make sure components of spark ignition system are installed and functioning properly 4 Make sure that the blower rota...

Страница 6: ...the air butterfly valve towards the back of the burner as shown in figure Air butterfly valve open direction If it doesn t refer to the actuator s literature for instructions on how to reverse the direction Closed Open in this direction only Open Back Air butterfly valve open direction Step 2 Set low fire air 1 Start combustion air blower 2 Drive control motor to low fire position 3 Measure the ai...

Страница 7: ... flame signal is too low use the bypass regulator B and or the adjustable limiting orifice C to increase the pressure at Tap E and provide better flame signal However this can have a negative impact on emissions and or nozzle life 10Close all pressure taps Pilot start option D B C Tap E A Main gas shut off valve train Pilot gas shut off valve train Low fire start with pilot start option WARNING Th...

Страница 8: ...as butterfly valve to 75 open See step 4 figure Manual butterfly valve adjustment Note To adjust manual butterfly valve a Loosen set screw b Turn dial c Tighten set screw 2 With burner lit drive control motor to high fire position 3 Measure air loading line pressure from tap C to the chamber See step 2 figure Air differential pressure 4 Refer here page 13 Air ΔP vs Input Find your measured high fi...

Страница 9: ...s 4 Check ignition spark plugs and proper gap 5 Check valve motors and control valves for free smooth action and adjustment 6 Check for proper operation of the ventilating equipment 7 Test the interlock sequence of all safety equipment manually make each interlock fail noting that related equipment closes or stops as specified by the manufacturer 8 Test flame monitoring control system by manually ...

Страница 10: ...valve position The burner goes out when it cycles to high fire Not enough gas pressure into the ratio regulator Check the start up settings Measure the gas pressures and adjust them where necessary Check for valve train pressure loss Loading line to the ratio regulator is leaking Repair the leak in the loading line Not enough gas flowing to the burner Adjust the ratio regulator to increase the gas...

Страница 11: ... 5 3 7 WX0500 WX0600 7 5 5 5 WX0850 15 11 Input remote blower All information is based on laboratory testing Different chamber conditions will affect the data Eclipse reserves the right to change the construction and or config urations of our products at any time without being obliged to adjust earlier supplies accordingly WX0050 Pressure at air inlet 9 w c 22 5 mbar WX0100 WX0600 Pressure at air ...

Страница 12: ...59 WX0400 347 158 WX0500 505 229 WX0600 456 207 WX0850 1435 651 Burner without blower Model Weight lbs kg WX0050 107 49 WX0100 124 56 WX0200 180 82 WX0300 228 104 WX0400 224 102 WX0500 338 153 WX0600 289 131 WX0850 1135 515 Fuel type HHV WOBBE Index Fuel Symbol Gross heating value HHV Speci fic gravity WOBBE Index Natural Gas CH4 90 1000 BTU ft3 11 1 kWh m3 0 60 1290 BTU ft3 Propa ne C3H8 2525 BTU...

Страница 13: ...10 15 20 25 30 0 600 1200 1800 2400 3000 3600 0 10 20 30 40 50 60 70 0 200 400 600 800 1000 Air p vs Input Input kW Air P mbar 10 Air P w c 10 Input kBtu h WX0300 0 5 10 15 20 25 30 0 10 20 30 40 50 60 70 80 0 1000 2000 3000 4000 5000 0 250 500 750 1000 1250 1500 Air p vs Input Input kW Air P mbar 10 Air P w c 10 Input kBtu h WX0400 0 5 10 15 20 25 30 0 10 20 30 40 50 60 70 80 0 1000 2000 3000 400...

Страница 14: ...150 180 50 600 Control and operation curve Excess air Input kW Typical Ratio Control Input kBtu h WX0050 0 0 200 400 600 800 1000 1200 0 60 120 180 240 300 360 10 20 30 40 50 NOX Emission On ratio NO X ppm 3 O 2 Input kW NOX Naturel gas NOX Propane Butane Input kBtu h WX0100 0 0 200 400 600 800 1000 1200 0 60 120 180 240 300 360 20 40 60 80 100 120 140 160 Control and operation curve Excess air In...

Страница 15: ...kBtu h WX0400 0 1000 2000 3000 4000 5000 6000 0 300 600 900 1200 1500 1800 0 10 20 30 40 50 NOX Emission On ratio NO X ppm 3 O 2 Input kW NOX Naturel gas NOX Propane Butane Input kBtu h WX0500 0 50 100 150 200 250 300 350 400 0 1000 2000 3000 4000 5000 6000 0 300 600 900 1200 1500 1800 Control and operation curve Excess air Input kW Input kBtu h Typical Ratio Control WX0500 0 10 20 30 40 50 0 1500...

Страница 16: ...60 70 80 90 7 9 NOX Emission On ratio NO X ppm 3 O 2 Input kW Input MMBtu h NOX Naturel gas NOX Propane Butane WX0850 2 4 6 8 1 3 5 0 0 100 200 300 400 500 600 700 800 500 1000 1500 2000 2500 0 900 7 9 Control and operation curve Excess air Input kW Input MMBtu h Typical Ratio Control WX0850 ...

Страница 17: ...3 26 ø22 21 5 12 1 14 38 9 50 Hz 35 1 60 Hz 7 3 24 1 16 5 6 1 8 2 WX0850 ø33 3 ø30 1 35 6 ø32 24 4 23 4 20 4 40 8 7 8 39 9 27 5 9 3 8 3 Packaged blower mm B F E K D P 0 4 10 N C M G L A H n x ø0 5 ø12 NPT or Rc fuel Iinlet Bypass fuel regulator UV Scanner Location Model A B C D E F G H K L M N n P NPT Rc WX0050 ø340 ø245 381 ø300 298 229 217 518 178 528 209 156 4 3 4 WX0100 ø385 300 440 ø345 316 2...

Страница 18: ...18 23 9 24 1 16 5 22 7 8 1 2 WX0850 ø33 3 ø29 4 ø29 1 ø32 4 7 5 9 11 4 19 12 12 9 39 3 39 9 27 5 36 8 8 1 2 1 WX0300 WX0400 BPT or Rc Remote blower mm H D n x ø0 5 ø12 A K L E I P J B C F M N G 0 4 10 Welded pipe air inlet NPT1 or Rc pilot fuel Iinlet Model A B C D E F G H I J K L M N n P NPT RC WX0050 ø340 ø226 ø220 ø300 81 149 245 138 76 105 528 528 209 365 4 1 2 WX0100 ø385 ø281 ø275 ø345 81 14...

Страница 19: ...the end of the product life number of operating cy cles reached dispose of the packaging and product in a corresponding recycling centre Do not dispose of the unit with the usual domestic refuse Do not burn the product On request old units may be returned carriage paid to the manufac turer in accordance with the relevant waste legislation requirements ...

Страница 20: ...ermal Solutions family of products includes Honeywell Combustion Safety Eclipse Exothermics Hauck Kromschröder and Maxon To learn more about our products visit ThermalSolutions honeywell com or contact your Honeywell Sales Engineer Eclipse Inc 1665 Elmwood Rd Rockford IL 61103 United States ThermalSolutions honeywell com FOR MORE INFORMATION ...

Отзывы: