64
Emergency Command Center Manual —
P/N LS10001-000FL-E:G 5/3/2016
Programming
Main Menu - User Programming
Device Control Timeout
Enter the maximum amount of time (
30-300
seconds) that one of the
devices (Primary Operator Console, Local Operator Console, Remote Page Unit, or Remote Micro-
phone) can remain in manual control of the ECC system.
Paging Timeout
Enter the maximum amount of time (
30-300
seconds) that the microphone’s
PTT switch can be held.
3.2.3 Address Assignment
Remote Microphone / Operator Console Address Assignments
Any combination of up to eight (8) remote consoles (ECC-LOC, ECC-RPU, and ECC-RM) can be
used in the system. Odd numbered addresses are not selectable. Addresses must be sequential, even
numbers. Identify which consoles are installed at addresses 4, 6, 8, 10, 12, 14, 16, and 18 as either
Local Operator Console
or
Remote Microphone
. Note that the ECC-RPU and ECC-RM are both
considered remote microphones. Refer to Section 2.14, “Addressing External Data Bus Devices”
for information on dipswitch settings.
Mic Gain is the microphone's transmitting “volume control”. The gain number is automatically
entered when a remote console is programmed.
Figure 3.6 RM/Console Address Assignments
c
o
n
s
o
le
a
d
d
re
s
s
.j
p
g
Содержание ECC-50/100
Страница 83: ...Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 83 Notes ...
Страница 95: ...Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 95 Notes ...
Страница 102: ...102 Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 Notes ...
Страница 106: ...106 Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 Slide in Labels ...
Страница 108: ...108 Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 Slide in Labels ...
Страница 114: ...Cut along dotted line ...
Страница 116: ...World Headquarters 1 Firelite Place Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www firelite com ...