background image

4

EA122A
OPERATION  •  SERVICE

Operation

Service

!

!

The EA122A operates as follows:
Opening the air vent (turning valve body counterclock-

wise) exposes the EA122A to the system. Water and air may
enter the vent chamber. The float will fall through any air in
the chamber. This opens the vent seat.

The red vent cap allows air to pass through the open vent.

As the air is released through the vent cap, water replaces the

air in the vent chamber and the float rises. This closes the
vent seat. When additional air enters the vent chamber, the
operation repeats.

If the vent seat remains open, water will rise through the

vent and cause the swelling disks inside the red cap to close
off the vent. Closing the air vent (turning valve body clock-
wise) isolates the EA122A from the system, allowing
service.

CAUTION

The EA122A may be hot due to system temperature
extremes. Use caution when adjusting vent to pre-
vent burning hands.

Dirt may collect in the seat area of the air vent float

assembly, causing the vent to malfunction. Clean the vent
periodically to prevent this problem.

NOTE: The EA122A may be serviced without depressuriz-

ing or draining the system.

To clean the seat area, proceed as follows:
1. Turn the vent body clockwise to the closed position,

isolating the vent from the system. See Fig. 4.

2. Remove the float assembly by unscrewing the outer

ring at the top of the body and lifting up the black cover
assembly. See Fig. 5.

3. Carefully clean any dirt or debris from the seat area.

9. Make sure the red vent cap is tightened all the way

to the stop position for proper leakage guard operation.
Use hands only to tighten.

Fig. 5—EA122A construction.

CAUTION

Do not bend spring on float assembly or damage to
the vent may result.

4. Carefully clean any dirt or debris from inside the

vent chamber.

5. Replace the float assembly, making sure that the O

ring is seated properly (see Fig. 5).

6. Replace black cover assembly on air vent body.
7. Using hands only, replace outer ring, turning until

handtight.

8. Operate the EA122A by turning the air vent body

counter- clockwise to the open position. Use hands only. See
Fig. 4.

M5493

CONSTRUCTED 
FOR EASY, IN-LINE 
SERVICE.

SHUTOFF IS 
BUILT-IN.

  

NO DRAIN-DOWN 
REQUIRED.

JUST TWIST AND YOU'RE READY 
TO SERVICE!  TWIST AGAIN AND 
YOU'RE BACK ON LINE.

RED VENT CAP
WITH LEAKAGE GUARD

VENT LEVER

SPRING

BLACK COVER
ASSEMBLY

O-RING

SEAT AREA—
MAKE SURE 
AREA IS FREE OF 
DIRT AND DEBRIS.

FLOAT

Содержание EA122A

Страница 1: ...tant materials for use with water systems containing glycol mineral oils or petro leum based oils For use with water systems up to 230 F 110 C Not suitable for steam systems Uses 1 8 in NPT male pipe thread Maintains quiet and efficient operation CONTENTS Specifications 2 Ordering Information 2 Installation 3 Operation 4 Service 4 Troubleshooting 5 EA122A AutomaticAir Vent The Honeywell Braukmann ...

Страница 2: ...ption Model Number Automatic Air Vent with leakage EA122A1002 guard and Skega seal ACCESSORIES Description Part Number Cover Assembly includes cover float P122B1002 assembly and vent cap Safe Waste Connector Connects top vent Q122A1001 to 1 4 in O D tube Vent cap Red Includes leakage guard 204992 OPERATING RATINGS Maximum Pressure 90 psi Maximum Temperature 230 F 110 C SAFETY RATINGS Maximum Press...

Страница 3: ...ion as specified in the Location section 2 Turn EA122A until vent fits tightly on piping Use a wrench to securely tighten hex 3 If safety drain connection is desired install a pipe between vent discharge and drain using Q122A1001 Safe Waste Connector 4 Make sure that the red vent cap is securely tightened and that the valve is in the closed position by turning vent body clockwise See Fig 4 Use han...

Страница 4: ...riz ing or draining the system To clean the seat area proceed as follows 1 Turn the vent body clockwise to the closed position isolating the vent from the system See Fig 4 2 Remove the float assembly by unscrewing the outer ring at the top of the body and lifting up the black cover assembly See Fig 5 3 Carefully clean any dirt or debris from the seat area 9 Make sure the red vent cap is tightened ...

Страница 5: ...tached to the vent lever as shown in Fig 5 Water is leaking from the EA122A 1 Make sure the red vent cap is tightened all the way to the stop position 2 Adjustthevalvetotheclosedpositionbyturningtheventbodyclockwise 3 Clean the vent as described in the Service section 4 If internal parts appear damaged or deteriorated replace cover assembly part no P122B1002 5 62 3038 CAUTION TheEA122Amaybehotduet...

Страница 6: ...6 ...

Страница 7: ...7 62 3038 ...

Страница 8: ...Printed in U S A Honeywell Braukmann Helping You Control Your World Honeywell Inc 1985 Douglas Drive North Golden Valley Minnesota 55422 ...