Honeywell E529.RF Скачать руководство пользователя страница 4

 

 

 

 

PN 292-100 

 

Copyright 2013 INNCOM by Honeywell

 

 

4.  Use the OFF/AUTO button to test Heat/Cool 

functions (depending on the HVAC system, fan 
operation may only subside to a minimal level). 
Press OFF/AUTO to return to Auto mode. Press 
the FAN button to cycle fan speed from LO to 
MED to HI.Press the ecoMODE™ button. Verify 
that the LCD displays notification that the 
ecoMODE option has been chosen.  

5.  Test the PIR by entering the 

Run

 menu and 

selecting Value 11. On execution, the LCD shows 
Pir and the unit emits a buzzing noise when 
movement is detected by the passive infrared 
module. 

6.  Test the door monitor by entering the Run menu 

and selecting value 12.  

7.  If balcony door or window sensors are linked to the 

e529.RF, open the linked opening. Verify that the 
e529.RF displays notification that the door or 
window is open. 

Testing e529.RF IRAS and RF network 
connections 

1.  Use the PING parameter to test each device on 

the network. 

2.  Verify that e529.RF LCD displays a dot in lower 

right corner of the screen indicating RF link to 
HVAC partner. 

3.  Enter the RUN menu value 2. Execute a test of 

the IWAN. If the test is successful, the Room ID 
will scroll across the LCD, indicating 
communication with the server. 

FCC Statement 

 

This equipment has been tested and found to comply with the 
limits for Class B digital device, pursuant of part 15 of the FCC 
Rules. These limits are designed to provide reasonable protection 
against harmful interference in a residential installation. This 
equipment generates, uses and can radiate radio frequency 
energy and , if not installed and used in accordance with the 
guarantee that interference will not occur in a particular 
installation. If this equipment does cause harmful interference to 
radio or television reception, which can be determined by turning 
the equipment off and on, the user is encouraged to try to correct 
the interference by one or more of the following measures: 
 

 

Reorient or relocate the receiving antenna. 

 

Increase the separation between the equipment and 
receiver. 

 

Connect the equipment into an outlet on a circuit 
different from that to which the receiver is connected. 

 

 

Consult the dealer or experienced radio/TV technician 
for help 

Содержание E529.RF

Страница 1: ...s To minimize external conditions interference with room temperature measurement locate the e529 RF away from external doors or windows and areas in direct sunlight Mounting Instructions Separate the e529 RF body and the mounting plate by pulling the bottom of the mounting plate away from the e529 RF body and then pull the mounting plate down NOTE If the back mounting plate is rotated more than 2 ...

Страница 2: ...the PAN ID on the commissioning list o Press DISPLAY The e529 RF beeps to confirm the Pan ID value is stored and the LCD returns to the menu list rF Selects the RF channel for IRAS communication The number will be included on the commissioning list o Enter Service Mode if not already there o Scroll to rF and enter using OFF AUTO o Use UP DOWN to set the RF channel between 11 and 26 o Press DISPLAY...

Страница 3: ...ative humidity if sensor available 25 Tests the built in light sensor 26 Tests battery power 255 full charge PnG Sends a signal to connected devices and registers response o Enter Service Mode if not already there o Scroll to PnG o Scroll to the address of the device to be pinged After 2 seconds the version of the partner device will scroll across the LCD verifying communication with the e529 RF N...

Страница 4: ...of the screen indicating RF link to HVAC partner 3 Enter the RUN menu value 2 Execute a test of the IWAN If the test is successful the Room ID will scroll across the LCD indicating communication with the server FCC Statement This equipment has been tested and found to comply with the limits for Class B digital device pursuant of part 15 of the FCC Rules These limits are designed to provide reasona...

Страница 5: ...PN 292 120 5 ...