Select a parameter; press OFF/AUTO again to get the
value of the parameter
-
P0, 1: Set Room ID (Room ID should be set using rId)
-
P2, 3: Set PAN ID (set PAN ID using the PAn
parameter). Not required for RF
-
P4: Set the transmission (Tx) radio power. Tx may need
to be boosted to meet local conditions.
-
P5: Set the RF channel (set RF channel using the rF
parameter)
-
P6: Set the e529.RF local address (default is 13)
-
P7: Set the P5 channel (default channel is 1)
-
P8: Set P5 partner (default partner is e528.36_X529.RF)
run
—Selects built-in tests of the e529.RF
o
Enter Service Mode if not already there
o
Scroll to run and enter using OFF/AUTO.
o
Use the UP/DOWN arrows to select one of the following
tests. Use the DISPLAY button to begin test
-
1
—Reset: On execution, the LCD screen flashes red,
then briefly shows reset information from a bound device
-
2
—CI Connectivity test
-
3
—Broadcast Room ID, Network ID, and PAN ID to RF
bridge device
-
11
—PIR test: On execution, the LCD shows Pir and the
unit emits a loud noise when movement is detected by
the passive infrared module.
-
12
—Door Test: On execution, the e529 responds with a
beep when the door switch is actuated
-
13
—Window Test: On execution, the E529 responds with
a beep when the window switch is actuated
-
14
—Remote PIR Test: On execution, the LCD shows PIr
and the unit emits a noise when movement is detected
by a remote device with a passive infrared module
-
20
—Reset counter: On execution, the LCD displays the
number of times that the unit has been reset, then reverts
to the test number
-
23
— Press DISPLAY to start a real-time temperature
test. The Set temperature ticks up every second for one
minute.
-
24
—Tests room relative humidity (if sensor available)
-
25
—Tests the built-in light sensor
-
26
—Tests battery power (255 = full charge)
-
PnG
—Sends a signal to connected devices and registers
response
o
Enter Service Mode if not already there
o
Scroll to
PnG
o
Scroll to the address of the device to be pinged. After 2
seconds, the version of the partner device will scroll across
the LCD, verifying communication with the e529.RF
Note:
Pressing DISPLAY after a device has
been pinged allows entry into the NVRAM of
partner devices. Activity in the NVRAM space
can severely affect functionality. This parameter
should be used only by INNCOM technicians.
Commissioning Process
As noted in the Application Overview, the e529.RF
may be employed in 3 scenarios. For each scenario,
establishing the unique room ID, binding devices, and
establishing communication will be different. Some
devices for instance, initiate binding (reverse bind)
and some must be
actively “taught” (forward bind).
Consult the Commissioning instructions for the
particular device. See also the e529.RF User Manual
for detailed instructions.
Testing
Testing the e529.RF Operational Controls
The e529.RF and the other INNCOM devices in a
room setup or network have been subjected to
rigorous unit, integration, operational and production
testing prior to shipment for installation. The
installation technician needs only to test generally
that the thermostat functions as intended.
1. At power ON, confirm all segments and characters
are displayed on the LCD display.
2. Press the DISPLAY button to verify that the LCD
briefly shows the Room (measured) temperature
(which should be close to or equal the Set
temperature). If the e529.RF is networked to an
outdoor sensor, press DISPLAY again to check
that outside temperature is displayed.
3. Press the °F/°C button once to verify that the
temperature scale changes. Verify that the LCD
resets to the default scale in 5 seconds.